CHAPTER 26
1960 Guide
in feet. The length of run is not usually known at the out set;. hence/ it may be necessary to assume some pipe size at the start. Such an assumption frequently is considerably in error, and a more common and practical method is to assume the length of run and to check this assumption after the pipes are sized. For this purpose the length of run usu ally is taken as double the actual length of pipe.
BASIC CHART FOR STEAM PIPE SIZING
fig. 22 is the basic chart for determining the weight-flow rate and velocity of steam in Schedule 40 pipe for various values of presure drop per 100 ft, based on zero psig saturated steam. By use of the multiplier charts it may be used at all saturation pressures between 0 and 200 psig.
TABLES FOR PIPE SIZING FOR LOW-PRESSURE
The basic chart. Fig. 22, can be used for Rising pipe on low-pressure systems. The values in Table 5 which are taken from the basic chart provide a more rapid means of selecting pipe sizes for the various presure drops listed and for systems operated at 3.5 and 12 psig. Hie weight-flow rates shown for 3.5 psig can be used for saturated pressures from 1 to 6 psig, and those shown for 12 psig can be used for saturated pressures from 8 to 16 psig with an error not exceeding 8 percent.
Both fig. 22 and Table 5 are for use where the flow of
Table 6.... Steam Pipe Capacities for Low-Pressure Systems
(for l/ta on One-Pipe Systems or Twit-Pip* Systems m which Condoncote Row* Against the Sfaom Row)
Tills table b bosedon data developed through reseordi investigation* of (bo American Society of Heating, Refrigerating ond Air-Conditioning Engineers
Capacity in Pounds par Hear
Two-Pip* Syitenu
One-Pip* Systems
Siza, Inchas Condense te flowing
ogoln*it steam
Supply
Vertical Horizontal
Radiator valve* and
connection*
Radiator ond riser
A
Z* C
0*.
E
F*
H 1 lH 1H 2
2M 3 3H 4 5
6 8 10 12 16
8 14 31 48 97
159 282 387 511 1,050
1,800 3,750 7,000 11,500 22,000
_
9 19 27 49
99 175 288 425 788
1,400 3,000 5,700 9,500 19,000
6 11 20 38 72
116 200 286 380 --
-- --
-- --
--
__ 7 16 23 42
_
-- -- --
_--
-- -- --
--
7 7 16 16 23
42 65 119 186 278
545 __ -- --
--
Nets: 8teem et en event* pressure of 1 psi* b used ee e besb of celcaletint
cepedtiee.
* Do not ose Cofaunn B (or pxwsuie drops of bee then Hs pe> per 100 ft of
equivalent nm. Os# Pi*. S3 or Table 5 instead.
b Do not ose Colonic D for premise drape of less tbao pei per 100 ft of
equivalent ran except on rieee J in. end over. Van Fig. SS or Table i instead.
* Pitch of borisontal runouts to riaera end radiator* should be not less than H
in. per ft.
> pit-n y-**>"*
runouts over 8 ft in leoxth should
he one pipe (be farcer than called for in tbb table.
condensate does not inhibit the flow of steam. Columns B
and C of Table 6 are for
where steam and condensate
flow in opposite directions as in risers or runouts that are
not dripped. Columns D, B, and F are for one-pipe systems
and include risers, radiator valves and vertical connections,
and radiator and riser runout sizes, all of which are based on
the critical velocities of the steam to permit the counterflow
of condensate without noise.
Return piping may be sized with the aid of Table 7, where
pipe capacities for wet, dry, and vacuum return lines are
shown for several values of pressure drop per 100 ft of
equivalent length. It is customary to use the same pressure
drop on both the steam and return sides of o system.
Example S: What pressure drop should be used for the steam
piping of a system if the measured length of the longest run is 500 ft, and the initial pressure is not to be over 2 psig?
Solution: It will be assumed, if the measured length of the
longest nm is 500 ft, that when the allowance for fittings is added, the equivalent length of nm will not exceed 1000 ft. Then, with the pressure drop not over one-half of the initial pressure, the drop could be 1 pai or less. With a pressure drop of l psi and a length of run of 1000 ft, the drop per 100 ft
would be 0.1 psi. addle if the total drop were 05 psi, the drop per 100 ft would be 055 psi. In both cases the pipe could be
sized for a desired capacity according to the 0.1 and 055 pres sure drop lines in Fig. 22. On completion of the sizing, the drop could be checked by taking the longest line and actually
calculating the equivalent length of run from the pipe sizes de termined. If the calculated drop is less than that assumed, the pipe size is all right; if it is more, it is probable that there are an
unusual number of fitting involved, and either the lines must be straightened or the column for the next lower drop must be used, and the lines resized. Ordinarily, resizing will be un necessary.
CHARTS FOR SIZING PIPE FOR HIGH-PRESSURE
Many installations of heating systems for large industrialtype buildings have been designed for the use of high-pres sure steam, that is, without the use of pressure-reducing valves. Such systems usually involve the use of unit heaters or large built-up fan units with blast heating coils. Pressures on these systems vary from 30 to 150 psi. Temperatures are controlled by a modulating- or throttling-type thermostatic valve controlled by the air temperature in the room, fan inlet, or fan outlet.
Figs. 23, 24, 25, and 26 provide charts for sizing steam piping for systems of 30, 50, 100, and 150 psig at various pressure drops. These charts are based on the Moody Fric tion Factor, which takes into account the Reynolds number and the roughness of the internal pipe surfaces, and contain the same information as the basic chart of Fig. 22 but in a more convenient form.
Return pipe capacities given in Tables 8 and 9 are based on the following assumed pressures in the return piping:
Pressure Drop Ut/100 Ft
H
X H 1 2
Pressure in Return Line (Prig)
30 psi System
150 pii System
X 1H 1 25
3 7H 4 10
20
The pressure loss and line loss as given were substituted in the Babcock steam flow formula, and the resulting capac ity was multiplied by 12 for 30-psig systems and by 16 for
Steam Heating Systems
379
Table 7.... Return Main and Riser Capacities for Low-Pressure Systems--Pounds per.Hour
(Reference fa Hu* table will be mode by column letter G through Y) jhb table b based on pipe size dote developed (hnxigh (be reward* investigations of The American Society of Heating, Refrigerating ond
Air-ConditiOAing Engineer*
Pqp* Size t
HjMorHOi Drop per 100 Ft
Wet Dry Vac
Drop per 100 Ft Wet Dry Vac.
Hfi Psi or 1 O* Drop per 100 Ft
Wet Dry Voc
X P** er 2 Ox Drop per 100 Ft
Wet Dry Voc
H Psi or 4 Oz Drop per 100 Ft
X P* or 8 O* Drop per 100 Ft
Wet Dry Vac
G
H t JK l
MHO P
OR
S
TUV
i IH e D 5
3V4
125 62 213 130 338 206
470 760 1,460 2,750 1,970 2,930
6
42 100 142
200
145 71 143 175 80 175 250 103 249 350 115 350
248 149 244 300 168 300 425 217 426 COO 241 600
393 236 388 475 265 475 675 340 674 950 378 950
810 535 815 1,000 575 1,000 1,400 740 1,420 2,000 825 2,000
1,580 868 1,360 1,680 950 1,680 2,350 1,230 2,380 3,350 1,360 3,350
2,130 1,560 2,180 2,680 1,750 2,680 3,750 2,250 3,800 5,350 2,500 5,350
3,300 2,200 3,250 4,000 2,500 4,000 5,500 3,230 5,680 8,000 3,580 8,000
4,580 3,350 4,500 5,500 3,750 5,500 7,750 4,830 7.810 11,000 5,380 11,000
7,880
9,680
13,700
19,400
12,600
15,500
22,000
31,000
494 848 1,340
2,830 4,730 7,560 11.300 15,500 27.300 43,800
IX IX 2
2H 3 3H 4 5
48
113 248 375
750
48 143 113 244 248 388 375 815 750 1,360
2,180 3,250 4,480 7,880 12,600
48 175 113 300 248 475 375 1,000 750 1,680
2,680 4,000 5,500 9,680 15,500
48 249 113 426 248 674 375 1,420 750 2,380
3,800 5,680 7,810 13,700 22,000
48 350 113 600 248 950 375 2,000 750 3,350
5,350 8,000 11,000 19,400 31,000
1,340 2,830 4,730
7,560 11.300 15,500 27.300 43,800
Table 8....Return Pipe Capacities for 30 Psig Steam Systems*
Capacity Expressed in Pound* per Hour
Pipe Six* inches
Drop in Premire--Pound* per 100 Ft in Length
KH X%
1
X 115 170 245 308 365 l 230 340 490 615 730
Ii?K)
485 710 1,025 1,290 1,530 790 1,160 1,670 2,100 2,600
2 1,580 2,360 3,400 4,300 5,050 2H 2,650 3,900 5,600 7,100 8,400 3 4,850 7,100 10,300 12,900 15,300 3H 7,200 10,600 15,300 19,200 22,800
4 10,200 15,000 21,600 27,000 32,300 5 19,000 27,800 40,300 55,500 60,000 6 31,000 45,500 65,500 83,000 98,000
* Hate: The above table is baaed on rtom at picaauie* of 0 to 4 pai*.
150-psig systems to obtain the values given in Tables 8 and 9. The return-line pressures used were found by observation of operating systems. The Babcock formula was used in this case since information on* condensate flow in return lines based on the Moody Friction Factor is not readily available.
SIZING PIPING FOR ONE-PIPE GRAVITY SYSTEMS
Gravity one-pipe air-vent systems, in which the equivalent length of run does not exceed 200 ft, should be sized by means of Tables 5,6, and 7 and fig. 22 as follows:
1. For the steam main ond dripped runout* to risers where the
Table 9
.. Return Pipe Capacities for 150 Psig Steam Systems*
Capacity Expressed in Pound* per Hour
Pipe Size indie*
Drop in Pressure--Pti per IOO Ft h Length XX X%
2
K
156 232 360 465 5G0
890
313
462
690
910 1,120
1,780
m
650
960 1,500 1,950 2,330
3,700
w
1,070 1,580 2,460 3,160 3;800
6,100
2 2,160 3,300 4,950 6,400 7,700 12,300 2H 3,600 5,350 8,200 10,700 12,800 20,400 3 6,500 9,600 15,000 19,500 23,300 37,200 3X 9,600 14,400 22,300 28,700 34,500 55,000
13,700 20,500 31,600 40,500 49,200 78,500 5 25,600 38,100 58,500 76,000 91,500 146,000 6 42,000 62,500 96,000 125,000 150,000 238,000
NaU: The above table is based on steam at pleasures of 1 to 20 pai*.
steam and condensate flow in the same direction, use He psi drop (Table 5 or Fig. 22).
2. Where the riser runouts are not dripped and the steam and condensate flow in opposite directions, and also for the radiator runouts where the same condition occurs, use Table 6, Column F.
3. For up-feed steam risers carrying condensate back from the radiators, use Table 6, Column D.
4. For doom-feed systems, the main risers of which do not carry any radiator condensate, use Table 6, Column B.
- 5. For the radiator valve site and the stub connection, use Table 6, Column E.
6. For the dry-return main, use Table 7, Column O.
7. For the wet-return main, use Table 7, Column AT.