Document XzVk0g8DdX35YqBeBN6807veJ
TherminoT 60 IC/FF-34
F. 650 600 550 500 450 400 350 300 250 200 150 100
50 0
-50 -- 100
Max. Film Tsmp. 635F. Max. Bulk Temp. 600F.
\0ptimum X Use
f Range
Po_ur -- Point --90F.
... a wide range liquid phase heat transfer fluid for non-pressurized indirect heating and cooling applications from -60 to 600 F.
Heat transfer fluids ire intended only for indirect heating purposes. Under no circumstances should this product contact or in any way contaminate food, animal feed, food products, food packaging materials, pharmaceu ticals or any items which may directly or indirectly be ultimately ingested by humans. Any contact may con taminate these items to the extent that their destruction may be required. Precautions against ignitions and fires should be taken with this product.
Monsanto
NOTICE: "Nothing contained herein is to be construed as a recommendation to use any product in conflict with any patent. MONSANTO MAKES NO WARRANTIES AS TO THE FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OF ANY PRODUCT RE FERRED TO, no guarantee of satisfactory results from reliance upon contained information or recommen dations, and disclaims all liability for any resulting loss or damage.
FUNCTIONAL PRODUCTS/Monsanto Industrial Chemicals Co. 800 North Lindbergh Blvd., St. Louis, Missouri 63166
*ln certain countries of Western Europe and the Far East. Monsanto sells Tnerminol Heat Transfer Fluids under the brand name "Santo!berm '* Heat Transfer Fluids". Corresponding Themiinol and Santotherm fluids are identical in composition.
0634982
I
TOWOLDMON0040267 WATER_PCB-00024736
Therminol 60 ...
Typical Properties
is a synthetic, liquid phase heat transfer fluid with excellent low temperature pumping characteristics (pumpable (<i -60oc), yet thermally stable to allow 600F bulk temperature use. Therminol 60 is ideally suited for both heating and cooling applications between -- 60F and 600F.
Therminol 60 is designed for use in indirect heating systems; to deliver efficient, dependable process heat with no need for system pressurization beyond the normal static head requirements of the pump.
Therminol 60 may oxidize on air contact when hot. Inert gas blanketing is suggested for system ex pansion tanks.
Therminol 60 is not corrosive to nor affected by metals and alloys commonly used in heat transfer systems.
Therminol 60 is not classified as a fire resistant heat transfer fluid. The use of protective devices may be required to minimize fire risk. Consult your insuring underwriter,
Composition Appearance Odor Pour Point Density 75'F. Flash Point, doc. Fire Point, coc. AIT Coefficient of Expansion Boiling Range:
10% 90% Average Molecular Weight
Polyaromattc Compounds Light yellow liquid Faint, aromatic -- 90F. (-67.8X.1 8.33 lbs. 'gal. 310r F, (154X.I 320'F. (160X.) 8353F. (445.8X.,i 0.00082 cc cc/X.
550F. (288X.1 741 F. :394X.) 250
This data is based upon samples tested in the laboratory and is not guaranteed for all samples. Write us for complete sales specifications for Therminol 60 heat transfer fluid.
Variations of Properties With Temperature
Temperature
F -65 -50
0 50 100 150 200 250 300 350 100 150 500 550 600* 650
C -59.4 -45.6 -18
10 38 6G 93 121 149 177 204 232 260 288 315 343
lb. gal. 8.72 8.66 8.50 8.35 8.20 8.05 7.90 7.75 7,60 7.43 7.30 7.12 6,95 6,80 6,65 6.50
Density
lb. ft.1 65.2 64.8 63.6 62.5 61.3 60 2 59.
q
56.9 55.6 54 6 53.3 52.0 50.9 49.7 48.6
Kg. m.3 1046 1038 1019 1001 983
965 947 929 911 891 875 854 833 815 797 7/9
Specific Heat
Thermal Conductivity
Viscosity
Btu. lb. F
0.315
Kcal. Kg. C.
0.315
Stu. Hr. ft. F.
0.0797
Kcal. Hr. m. C, lb. hr. ft.
0.1186
9746
cs. 3850
0.321 0.346
0.321 0.346
0.07S3 0.0780
0.1180 0.1161
2763 160
1100 65.0
0.371
0.371
0.0768
0.1143
32 13.2
0.395
0.395
0.0755
0 1123
11.7 4.90
0.420
0.420
0.0743
0.1106
6.3 2.70
0.445
0.445
0.0731
0.1088
4.0 1.75
0,470 0,495
0.470 0.495
0.0718 0.0705
0.1068 0.1049
2.8 1.25 2.1 0.97
0.518
0.518
0.9693
0.1031
1.6 0.75
0.543 0.563
0.543 0.568
0.0681 0.0668
0 1013 0.0994
1.3 0.62 1.1 0.52
0 593 0.618
0.593 0.61?
0.0656 0.0643
0.0976 0 0957
0.93 0 46 0.81 041
0.643
0.643
0.0630
0.0937
C.69 0.36
0.668
0.668
0.0618
0.0920
0.60 0.32
Vapor Pressure
mm Hg. abs. Kg. cm.3
<2.0 5 12 30
65 130 240 450 760 1200
0.007 0.015 0041 0 088 0 176 0 i:i 0 608 1.036 1 630 _
0634983
TOWOLDMON0040268 WATER_PCB-00024737
HEAT TRANSFER FILM COEFFICIENT, hi -- B tu /H r. -- Sq. Ft. VISCOSITY -- CS
Therminol 60-Physical Properties
>
Thermlnol60-Heat Transfer Coefficients
0634904
TOWOLDMON0040269 WATER_PCB-00024738
Therminol 60 - Pressure Drop
psi./lO O Foot
FLOW--GPM
Therminol 60-Safety of Handling
Therminol 60 is virtually non-toxic based on acute oral and skin absorption studies, and pose no special handling problems. Therminol 60 is not absorbed through unbroken skin in any significant quantity, but can be mildly irritating to the skin on prolonged contact. Therminol 60 should be washed off the skin with soap and water as soon as possible after contact, and fluid soiled clothing should be laundered before reuse.
Therminol 60 may be mildly irritating if eye contact occurs. Immediate flushing of the eye with copious amounts of water will minimize eye irritation or aftereffects.
Handled like any other industrial chemical, Therminol 60 is quite safe to store and use.
Therminol 60 vapors are not toxic, but may cause discomfort if coming off of heated fluid. There is no vapor exposure problem when transferring the
fluid from its shipping container to the heat transfer system. On the other hand, vapors emitted by Therminol 60 heated to elevated temperatures may be mildly irritating upon prolonged exposure. In heat transfer installations, the fluid is used in a closed, non-pressurized system free from leaks and with the expansion tank vent trapped so as to condense any vapors. Consequently, there should be little or no opportunity for workers to come in contact with vapors.
While Therminol 60 poses no serious problems with respect to the environment, as a concerned supplier to industry, Monsanto urges the user to maintain a tight system, to correct leakage promptly, and to exercise care in the handling and disposal of this and all other such products. A tight main tenance program not only protects the environment, but keeps employes comfortable, the working area clean, and the system running smoothly.
0634985
TOWOLDMON0040270 WATER_PCB-00024739