THE DOW CHEMICAL COMPANY ELECTRICAL TECHNOLOGY GLOBAL
ADMINISTRATIVE GUIDELINE G7A-Q099-03 18-OCT-1995 PAGE 1 OF 4
CASE
ELECTRICAL SAFETY AND RELIABILITY AUDIT CHECK LIST
FOR
POWER TRANSFORMERS
TF
TRANSFORMER LOCATION I.D. #
TRANSFORMER EQUIPMENT I.D. t
VOLTAGE
IcVA
jivoe/ /O'Q>
Yes No N/A
1. Is the transformer properly tagged?
2. Is the manufacturer nameplate in place and legible?
3. Is the transformer case free of any signs of corrosion?
4. Is the transformer case adequately painted?
5. Is the transformer case free of any oil leaks?
(Look at case, bushings, radiators, and valve.)
^___________
6. Are oil samples taken regularly?
7. Is the transformer adequately grot ~,d? (Must
have two leads if its capacity is
' KVA and
above)
____ ____ /___________
8. Has the transformers been checked for PCS's and properly labeled?
___________
9. Are vehicle barricades located if needed?
10. If the transformer has open bushings, is there a fence surrounding the transformer?
___________ ___________ _V^
11. Are there warning signs posted on the fence? 12. Is the fence grounded?
____ ____
13. Is the transformer operating free of excessive noise and vibrations?
14. Is the transformer operating below rated capacity?
oo A
T0*MTT4L
THE DOW CHEMICAL COMPANY ELECTRICAL TECHNOLOGY GLOBAL
ADMINISTRATIVE GUIDELINE G7A-0099-03 18-OCT-1995 PAGE 2 OF 4
15. Is the transformer located away from process piping?
16. If transformer is within 20 feet (6 meters) of building, is the building wall non-combustible?
17. Is there easy access for fire fighting?
18. Is the transformer bolted to foundation?
19. Is the transformer on a PPM program?
20. Is the transformer maintenance history being kept?
21. Is high resistance ground system in place?
22. Is ground detector system on PPM schedule?
23. Does transformer have a circuit breaker on the primary? (10,000 kVA and above)
24. Is short circuit protection available?
25. Is protective device coordinated with other devices ?
26. Is dissolved gas analysis data available? (1000 kVA and above)
27. Is there a dike around the transfs contain an oil spill?
r to
28. Is there a pit with oil/water separation?
29. Is the pit protected with a fire barrier?
Case Index Score:
_
j/
y y y y
RADIATORS
Yes No N/A
1. Is the transformer radiator free of any signs of corrosion?
2. Is the transformer radiator adequately painted?
r-?? A 04Sji9 CNFj0FmTt.9
httai.
THE DOW CHEMICAL COMPANY ELECTRICAL TECHNOLOGY GLOBAL
ADMINISTRATIVE GUIDELINE G7A-0099-03 18-OCT-1995 PAGE 3 OF 4
3. Is the transformer radiator free of any oil leaks? (Look at case, bushings, radiators, and valve.)
4. Are the radiators removable with cut-off valves? (2000 kVA and above)
5. Are cooling fans operating properly?
Radiators Index Score:
INSTRUMENTS
Yes No N/A
1. is the oil level at an acceptable level? 2. Is the oil level gauge in good condition?
Z___________ Z___________
3. Is the tank pressure at an acceptable level?
-- j/ --
4. Is the tank pressure gauge in good condition? 5. Is the Suchholz Relay in good condition?
ZZ z
6. Is the Sudden Pressure Relay in good condition? (required for 10 MVA and above)
7. is the Pressure Relief Valve (PRV) in good condition?
___________
,z__
8. Is the transformer running at an acceptable temperature? (below 50 degree C rise above ambient)9 10
_________
9. Is the temperature switch and level switch wired to alarm in a continuously occupied location? [LPP 3.7.6]
z___________
10. Is the breather system in good condition? Instruments Index Score
77------------
THE DOW CHEMICAL COMPANY ELECTRICAL TECHNOLOGY GLOBAL
ADMINISTRATIVE GUIDELINE G7A-0099-03 18-OCT-1995
PAGE 4 OF 4
BUSHINGS
Yes No N/A
1. Are the exposed bushings clean?
2. Is the termination hardware on exposed bushing clean and without any signs of corrosion?
3. Are exposed bushings equipped with lightning protection devices?
Bushings Index Score:
________ /
_
____
CONDUIT/CABLE
Yes No
*
1. Does cabling enter transformer from bottom or side only?
2. Is cabling or duct anchored to foundation?
Conduit Index Score
1
N/A
TAP CHANGER
Yes No N/A
Is the tap changer locked or bolted (and tagged)?
Tap Changer Index Score:
Power Transformer Average Index Score: