CHAPTER 42
1949 Guide
liberties may be taken without impairing the result if all possible degrees of
freedom have been taken into account in the design of the installation.
. When a machine unit is properly isolated it will have a definite amount
of movement which is determined by the ratio of the unbalanced forces to. the total mass of the machine: If this resultant machine movement is too
great for the necessary connections or the satisfaction of the customer it can
be reduced only in two ways without destroying the quality of the isolation;
first, adding mass or dead weight to the machine (such as concrete) common in the application of low speed, partially balanced machinery; second, accurately balancing (both statically and dynamically) all moving parts so
as to eliminate the vibration at the source. This latter method.is the best engineering practice and is the modem trend. However, even with well
balanced machinery, installed in the vicinity of quiet offices it is usually
necessary to isolate properly the equipment to prevent the transmission of
vibration likely to cause complaints.
Where limitation of machine movement is desired during the starting and stopping periods, the application of friction or hydraulic damping
will serve without seriously interfering with the efficiency of the isolation.
REFERENCES
* American Standards for Noise Measurement, Z24.2-1942, American Standards Association.
* American Standards for Sound Level Meters for Measurement of Noise and Other Sounds, Z24.3-1944, American Standards Association.
* Sound Insulation of Wall and Floor Constructions (U. S. Department of Commerce, National Bureau of Standards, Building Materials and Structures Report BMS17 and Supplement).
4 A.S.H.V.E. Research Report No. 1205--Determining Sound Attenuation in Air Conditioning Systems, by D. A. Wilbur and R. F. Simons (A'.S.H.V.E. Transactions, Vol. 48, 1942, p. 267).
For coefficients of commercial sound absorbent materials see Bulletin Acoustical Materials Association, 919 No. Michigan Ave., Chicago, 111.
* Sound Propagation in Ducts Lined with Absorbing Materials, by .L. J. Sivian (Journal Acoustical Society of America, Vol. 9, 1937-38, pp. 135-140).
I Specific Normal Impedance and Sound Absorption Coefficients of Material, by P. E. Sabine (Journal Acoustical Society of America, Vol. 12, pp. 317-323, January, 1941).
Application of Wave Theory of Room Acoustics to the Measurement of Acoustic Impedance, by C. M. Harris (Journal Acoustical Society of America, Vol. 17, pp. 35-46, ' July, 1945).
* Sound Absorption in Rectangular Ducts, by L. L. Beranek (Joumal Acoustical Society of America, Vol. 12, pp. 22S-237, October, 1940).
The Transmission of Sound Inside Pipes, by Philip M. Morse' (Journal Acoustical Society of America, Vol. 11, pp. 205-210, October, 1939).
* Precision Measurements of Acoustic lmpedan.ee by L.. L. Beranek (Joumal Acoustical Society oj' America, Vol. 12, pp. 3-14; July, 1940).
Notes on Acoustic Impedance Measurement, by H. J. Sabine (Journal Acoustical Society of America, Vol. 13, pp. 143-150, October, 1942).
10 The Absorption of Noise in Ventilating Ducts, by Hale J. Sabine (Journal Acous tical Society of America, Vol. 12, p. 53,1940).
II The Prediction of Noise Levels from Mechanical Equipment, by J. S. Parkinson (Healing and Ventilating, March, 1939, pp. 23-26).
Methods of Rating the Noise from Air Conditioning Equipment, by J. S. Parkinson (A.S.H.V.E. Journal. Section, Heating, Piping and Air Conditioning, July, 1940 p. 447)i
11 The Noise Characteristics of Air Supply Outlets, by D. J, Stewart and G. FDrake (A.S:H.V.E. Transactions, Vol. 6, 1937, p. 81).
CHAPTER 43
CENTRAL SYSTEMS FOR AIR CONDITIONING
Features of Systems, Zoning, Apparatus Dew-Point, Cooling Load, Heating Load, Air Quantity and Effective Temperature Difference; Low and High Pressure Induction Convectors, Evaporative Cooling, Precooling, Sensible Cooling with Unwetted Coils, Run-Around System, Selection of Type of System, Location of Apparatus, Design Procedure
THE term, central, applied to an air conditioning system implies that the equipment such as fans, coils, filters and their encasement are designed for assembly in the field rather than in a factory as a unit,. As a central system usually serves several different rooms, individual con trols are required for each room.
FEATURES OF CENTRAL SYSTEMS
One advantage of a central air supply system is that one apparatus serving many rooms may involve a lower investment cost than that for a number of self-contained plants, each serving a single room. A central system may occupy basement or attic space that is relatively unimportant, whereas individual factory-assembled apparatus placed in each room may occupy otherwise valuable space. Another advantage of a central system is accessibility for servicing, since it is possible to provide doors in the encasement for cleaning and inspecting aU of the component parts in a manner usually superior to. that practicable with compact factoryassembled equipment:
Central air conditioning systems usually are connected by ducts with the various rooms served, and preferably have exhaust fans that may effect complete removal and disposal of any desired proportion of the air. The exhaust fan may return air to the supply system for recirculation, as a measure of economy of fuel or refrigeration.
Central air conditioning systems are served by heating and refrigeratT ing equipment which may be located at some distance from the air supply apparatus and which may serve one or more, central air supply systems.
Year-Round Air Supply System
Fig. 1 is a plan of a year-round air. supply system. Outside .air may enter from the left at A, desirably from an intake on the side of the build ing least exposed to solar heat and not close to the ground or to a sun-r heated or dust-gathering roof. A damper B for proportioning the volume of outside air, is interlocked with the return air damper C in such man ner that as the outside air volume increases the return air volume decreases. The return air duct-D, shown diagrammatically, comes from the exhaust fan. All the air, it will be observed, must pass through the filters E and there is ample room on both the inlet and outlet sides of the filters for servicing them. The filters may be of mechanically cleaned type, of replaceable cell type, or may be electronic, as described in more detail, in Chapter 33.
The cleaned air passes to the equipment that changes its temperature and humidity. Except in very warm climates, a heating or tempering
857
'