Q = air flow, cubic feet per minute. , A = free area.of inlets or outlets (assumed equal), square feet..
h = height from inlets to outlets, feet. t = average temperature of indoor air in height h, Fahrenheit degrees. t,, = temperature of outdoor air, Fahrenheit degrees. 9i4 = constant of proportionality, including a value of 65 per cent for effectiveness
of openings. This should be reduced to 50 per.cent (constant 7.2) if con* ditions are not favorable.
HEAT REMOVAL
In problems of heat removal, knowing the amount of heat to be removed and having selected a desirable. temperature difference, the amount of
infiltration and Ventilation
215
COMBINED FORCES OF WIND AND TEMPERATURE
Equations for determining the air flow due to temperature difference and wind have already been given. It must be remembered that when both forces are acting together, even without interference, the resulting' air flow is not equal to the sum of the two estimated quantities. The flow through any opening is proportional to the square root of the sum of the heads acting on that opening.
When the two heads are about equal in value and the ventilating open ings are operated so as to coordinate them, the total air flow through the building is about 10 per cent greater than that produced by either head acting independently under conditions ideal to it. This percentage de-
Fio. 3. Incbba.se in Flow Caused by Excess of One Opening Over Another
air to be passed through the building per minute to maintain' this tempera ture difference can be determined by means of Equation 5,
where
Q = ___ I{ , ... 0.0175(1 -- to)
(5)
Q = air flow, cubic feet per minute. H = heat removed, Btu per minute. 1 -- to =* inside-outside temperature difference, Fahrenheit degrees.
EFFECT OF UNEQUAL OPENINGS
The largest flow per unit area of openings is obtained when inlets and outlets are equal, and the preceding equations are based on this condition. Increasing outlets over inlets, or vice-versa, will increase the air. flow, but not in proportion to the added area. When solving problems having an Unequal distribution of openings, use the smaller area, either inlet or out let, in the equations and add the increase as determined from Fig- 3.
Fig. 4. Determination of Flow Caused by Combined Forces of Wind and Temperature Difference
creases rapidly as one head'increases over the other and the larger will predominate.
The wind velocity and direction, the outdoor temperature, Or the indoor distribution, cannot be predicted with certainty, and refinement in calcu lations is:not justified; consequently, a simplified method can be used. This may be done by using the equations and calculating the flows produced by each force separately under conditions of openings best suited for cooniination of the forces. Then, by determining, as a percentage, the ratio of the flow produced by temperature difference to the sum of the two flows, the actual flow due to the combined forces can be approximated from Fig. 4.
n. ,
= " uruP lorge snop, aju it long, 1UU It wide, and 30 ft hieh.
The cubicd content is 600,000 cu ft, and the height of the air.outlet over that of the
1? 30 ,Pl foe! of 18,000 Btu per lb is used in this shop at the rate of 15'gph 11./5 lb per gal). Desired summer temperature difference is 10 deg and the prevail-