CHAPTER 23
V i-v
) 1958 Guide
(24)
where
C = pump capacity, pounds per hour.
Ap = area of slab, square feet.
.-
qt -- total heat requirement (slab output, g,,, plus back and edge losses) Btu per (hour) (square foot).
Cm = specific heat at temperature fm, Btu per (pound) (Fahrenheit degree).
A< = temperature drop through circuit, Fahrenheit degrees.
KINEMATIC VISCOSITY. SQ. TT./SEC. (x ID5)
21.Fig.
Friction Correction Factor for Viscosity
(For Nr. > 3000) .
For a temperature drop of At = 20 F, Equation 24 becomes
G = Ar9t
IQOWmCm
(25)
where
.:..
G -- gallons per minute. tCm = mean specific weight at temperature la, pounds per cubic foot.
1 . ;
An approximate solution for systems using pipe sizes other than 1-in.
IPS can be obtained by using Table 10 or Fig. 21. Table 10 is for use
when the flow is in the laminar zone. Fig. 21 is for flow in the turbulent
zone. For flows where Reynolds number falls between 2000 and 3000;
no reliable prediction for pressure loss can be made. It is generally safe
to assume the flow to be increased to a Reynolds number of 3000 with the
pressure loss estimated at that flow rate.
'
Figure 20 is based on a pipe size of 1 in: IPS. If another pipe size ishsed and the flow is laminar, the correction factor K from Table 10 can be used.
f
j
.[
Panel Heating
-; J
637
Table 6. Heat Output and Fluid' Temperature fob Snow Melting Systems
o
CO
fl
k" 0F
= 10 F
(a - 20 F
F
Rate of Snowfall
A
Velocity V 5 10 15
Velocity V 6 10 15
Velocity 0 5 10 15
Velocity 9 5 10 15
0.08
1.0 . So
151 205 260 127 168 209 102 128 154 75 84 94
108 135 162 97 117 138 85 97 110 70 75 79
0.0 So Ijn
66 66 66 64 64 64 62 62 62' 60 60 60 66 66 66 65 65 65 64 64 64 63 63 63
0.16
1.0 So
218 273 327 193 233 274 165 191 217 135 144 154
142 169 198 129 .149 170 117 129 142 100 105 109
0.0 So
133 133 i& 129 129 129 125 125 125 121 121 121
tm 99 99 99 97 97 97 95 95 95 93 93 93
0.25 1.0 So 292 347 401 265 305 346 235 261 287 203 179 206 234 . 165 186 .206 151 163 176 134
o;o So 208 208 208 ` 202 202 ' 202 195 195 .195 188
137 . 137 137 134 134 134 131 131 131 127
Note: This table is based on a relative humidity of 80 percent for all air temperatures.
Rate of snowfall, inches of water equivalent per hour (See Table 5).
R a = Free area ratio.
'
Co =* Slab output, Btu per (hour) (square foot).
= Air temperature, Fahrenheit.
tm -- Fluid temperature, Fahrenheit. Based on construction as shown in Fig. 19.
v = Wind velocity, miles per hour.
212 221 139 144
188 . 188 127 127
For example, assume a viscosity of 300 SSU, a llow of 5 gpm and a %-in. IPS pipe. Fig. 20 shows that for 1-in. IPS, friction loss would be 15.50 ft/ 100 ft. Table 10 gives K = 2.62 for %-in. pipe; therefore, friction loss would be 15.5 X 2.62 = 40.6 ft/100 ft.
If the flow is in the transition zone or is turbulent, then Fig. 5 of Chapter 21 can be used in conjunction with Fig. 2i. For example, assume a vis cosity of 0.0001 sq ft/sec. (56.5 SSU), a flow rate of 14 gpm and a 1 j^-in. IPS pipe size. Fig. 5, Chapter 21, shows a head loss for water to be 190 milinches per foot or 1.58 ft/100 ft. Figure 21 gives a correction factor K of 1.75 for a viscosity of 0.0001 sq ft/sec; hence, the pressure loss is 1.58 X 1.75 = 2.77 ft/100 ft.
INSTALLATION
TK^ere are certain precautions that must be taken during installation. 1hey concern internal corrosion, flammability, toxicity, cleaning, joints, and hookup. A comprehensive discussion of these precautions may be found in Reference 17.
Safety
Since ethylene glycol and petroleum distillates are slightly toxic, the system should be installed and maintained independently. There should ue no permanent connection between the snow melting system and the nnnking water supply.
Ethylene glycol is not considered flammable. In fact, aqueous soluons of less- than 60 percent glycol are used for fire sprinkler systems.