Document XRwMNbzd8jKodBev0LDDadw7K

178 CHAPTER 13 1965 Guide And Data Book PERCENT Of FULL STROKE Fig. 9 .... Typical Row Characteristics that are adjusted for a horizontal air pattern. The diffuser in which die element is mounted should be m the center of the occu pied area of the zone being controlled. CONTROL OF FLOW The successful operation of practically any air-condition ing system is dependent oh the proper control of-'flow in one form or another. The Bow being controlled may be steam,' water, air, or some combination thereof. In each case, a controlled device is used to regulate the flow at the command of a controller. The proper design and sizing of these controlled devices (valves for steam or* water, and dampers for air) are essential to obtain the desired results from the air-condition ing system. ' The performance of a valve or damper is expressed by the control industry in terms of its 'flow characteristics as it'operates through its stroke, based on a constant pressure drop. Three common characteristics are shown in Fig. 9 and may be defined as follows: Quick Opening: Maximum flow is approached rapidly as the device begins to open. 1 Linear: Opening and Sow are related in direct proportion. Equal Percentage: Each - equal increment' of opening in creases the flow by an equal percentage over the previous value. - . Since the pressure drop across a valve or damper seldom remains constant as its opening changes, actual performance usually deviates from the-published characteristic curve. The magnitude of the deviation is determined by the over all system design. For example, in a system arranged so that oontrol valves or dampers can shut off all flow, the pressure'drop across a controlled device' increases from a minimum at design conditions. to the.total system pressure drop-at no.flow.,Fig. 10 shows the extent of the resulting deviations for a valve or damper designed with a linear characteristic, when the selection is based oh various per centages of the total system pressure drop. In order.to approximate the' designed characteristic of the valve or damper, the design pressure, drop should be .a reasonably large percentage of: the. total system pressure drop'or the Fig. 10.... Typical Performance Curves for Linear Devices Selected at Various Percentages of Total System Pressure Drop > system should be designed and controlled in such a mannw that this pressure drop remains relatively constant. Higher pressure drops for controlled devices are obtained by using smaller sizes-in conjunction-with a posable'in crease in size of other equipment in the system. Since sizing techniques are different for steam, water, and air, each is discussed separately. - CONTROL OF STEAM FLOW The size of an automatic steam valve is based on the re quired capacity at maximum load, under the conditions which will exist at that time. The equation for mass flow through an orifice or nozzle can be written as - CA\/P> - Px .' 0) where to the flow of steam in pounds per hour. A = the area of the port opening in square inches. . Pi " the steam supply pressure, pounds > per square inch, absolute. f3* " the downstream pressure, pounds per-.square inch, absolute. C " a constant for a given steam .supply pressure and a given valve body. Valves for two-position operation usually are selected of ft size adequate tosupply the required maximum capacity with a reasonably low pressure drop (Pi -- Pi). It is necessary only to be 6ure that the valve will close against the system pressure and will have ample capacity when fully open.' Proportional valves for steam service must be carefully sized if stable control is to be achieved. Since, in general, the tendency is to oversize euchvalves, it should be remembered that no controller, can produce its best results if handicapped by a valve which is too large. The function of the valve is to vary the value of area A in Equation 1, and it is desirable that the flow vary in proportion to the value of A. The cor rect maximum required capacity must first be 'determined- ^Automatic Cntr' 179 . u be co factor of safety in this determination, bebased on actual heating requirements rather capacity of the coil, since the coil may than necessary. It is also necessary to base the valve \Ton the actual supply pressure Pi which will exist at the "JL since this supply pressure affects both the density of the steam and the pressure drop which will be selected. Selecting the proper pressure drop (Pt - Pi) across the valve when it is wide open and is supplying the maximum .^m requirement is the most important consideration in determining the valve size. For purposes of discussion it will be assumed that Pi is constant and that the valve is supply ing to a heating coil which has air entering at a constant temperature and velocity. Any pressure drop between the valve and the coil will be neglected so that P, represents the pressure ip the coil. The condensing capacity of the coil varies with changing values of Pi. When the valve is fully open, Pi assumes a vahle such that the capacity of the valve and the comf*>n<n`T1g rate of the coil are in balance. If this value of Pi is relatively large, then, as the valve is partially closed. Pi will decrease until the capacity of the valve and the pondfP'uuE rate of the coil are again in balance: Reducing the value of A in Equation 1 results in an increase in the value of y/Pi -- Pi aud partially offsets the effect of closing the valve. This effect is greatest when Pi is nearly equal to Pi and diminishes as Pi decreases. The minimum value which Pi can assume is established by tiie return line pressure (or vacuum) of the system. However, Pi may reach a value which results in the critical velocity through the valve before it has been reduced to its minimum value. If bo, any reduction of Ps beyond this value has no further effect on the valve capacity. The critical velocity exists when Pt is approximately 58 percent of Pi .'The unde sirable effect caused by variations in Pt can be eliminated by selecting a valve size such that P, is at or near its minimum value, or the value corresponding to the critical velocity, whichever b higher, when the valve is wide open. On'low-pressure steam applications it b good practice to base the valve size on a pressure differential equal to 75 or 100 percent of the gage supply pressure. When the supply pressure is.high enough so Pt at the critical velocity (58 percent of Pi) is above atmospheric pressure, the valve size can be based on a pressure differential of 42 percent of Pi absolute. All valves of the same size do not have the same capacity for a given pressure differential. Having established the supply pressure and the pressure differential, the valve manufacturer's tables or charts shouldbe consulted in selecting the proper size of valve for the required capacity. It is important that the supply pressure to an automatic steam valve be constant because it is difficult for a thermostat to produce stable results if the pressure b constantly changing. This situation arises, for example, when a steam boiler b operated by a two-position pressure controller. A pressurereducing valve, which will supply a constant pressure to the steam mains while permitting the boiler pressure to fluctuate between the limits of the pressure controller, b recommended. Lacking this, the differential of the pressure controller should be set as narrow as b consistent with efficient boiler and burner operation. On vacuum return systems the vacuum pump also should operate on a narrow differential. The use of two automatic control valves in parallel will often provide more stable control than a single larger valve, especially on large coils or steam-to-water heat exchangers. The valves should be sized so that one valve handles about one-third of the total capacity and the other about twothirds. They are controlled in sequence so that the small valve operates during periods of light load and the large valve begins to open only after the load exceeds the capacity of the small valve. The steam piping from the valve to the coil inlet, and from the outlet to the trap, should be the full size of the coil tapping or the size specified by the manufacturer of the coil, and should conform to recommended practice, as illustrated in Chapter 8 of the 1964 Guide And Data Book. It is very important that condensate be promptly drained from the cod. When the coil b at reduced pressure, as it will be much of the time, there will not be sufficient difference in pressure between the coil and the return line to obtain any lifting of the condensate. CONTROL OF WATER FLOW The capacity of a proportional valve for water service is not influenced by the supply water pressure, but only by the pressure differential. This is so because water is incompressible and because the inlet pressure is not an important factor in the thermal capacity of a water system. If a certain water circuit has a total resistance of 30 psi at maximum flow, of which 1 psi is through the valve, the resistance of the rest of the circuit b 29 psi. As the valve closes and flow b stopped, the resistance across the valve be comes the entire 30 psi. Therefore, the pressure drop across the valve increased by a ratio of 30:1 as the valve travelled from full open to full closed position. This increase in pressure drop as the valve is closed partially offsets the effect of closing the valve. It is obviously impracticable to design a water system so that there will be no increase in pressure drop across the valve as it closes. However, it b important to design the sys tem, including the valve, in such a manner that the ratio of this increase in pressure drop as the valve closes is kept as low as possible. Thus, if the design pressure drop across the valve is 5 psi instead of 1 psi, the ratio of increase b only 6:1 instead of 30:1, and the performance of the valve will be unproved accordingly. This discussion assumes a circuit in which the entire flow is controlled by a tingle valve. The same reasoning will apply to the more complicated systems involv ing a multiplicity of parallel circuits, each having a valve. In general, it can be said that the pressure drop across a water valve at full flow should be a reasonable percentage of-the resistance of the circuit in which the valve controls the flow. Due consideration should be given to any resultant increase in pumping head and operating costa. As water circuits are subject to variable pressures in ac cordance with the pressure versus flow characteristic of the pump and changes in friction loss in the system as the flow .varies, it is desirable to provide some means of system pres sure control. Three general methods of control can be used to compensate for thb pressure change. One is to maintain the flow in both,the supply and return mains as constant as .possible by installing a control valve in a bypass between the supply and return. The second method is to install an auto matic control valve, in series with the pump, which closes as S' the flow demand of the system decreases. The third method is to apply a variable speed drive to.the pump, since the pressure differential developed by a centrifugal pump is directly pro portional to its speed. The location of the automatic control pressure-sensing device depends upon the system.design and layout. The pressure-sensing point would usually be well out in the system, to get the best possible compromise in pressure variations at the individual unit valves. The bypass control . valve can also best be located out in the water circuit. An automatic control valve in series with the pump would`;be located between the pump and the first branch circuit Pres sure control should be used on both hot and chilled water sys tems. .