CHAPTER 24
1948 Guide
inlet valve, a water gage, and a relief valve. A source of supply of com pressed air for renewing the air cushion is highly desirable, especially in large, high pressure, hot water heating systems where it is inconvenient, if not impracticable, to drain down the water in the system so as to permit introduction of atmospheric pressure air.
For every hot water heating system the designer should calculate the volume of water contained in the radiators, piping system, boiler, etc., in'order to select the proper size of expansion tank. The water content of the piping can be obtained from Table 6. For a rough selection of size, however, it is sometimes assumed that 50 per cent of the volume of water is contained in the radiators, and that the water content per square foot of radiator heating surface is 0.2 gal for column radiators and 0.13 gal for tube typ radiators.
Another rough method for determining the size of an expansion tank to be located above the highest radiator is to divide the square feet of radiation by the factor 40 to obtain the required capacity in' gallons of the expansion tank.
. : Pipe Size, In. `
1H 1H
1H
Table 6. Volume of Water in Standard Pipe
Lineal Ft of Pipe Containing I Gal
63ll 36.1 22.2 12.8
9.47
Pipe Size. In.
2 2X 3 4 5 6
Lineal Ft of Pipe Containing 1 Gal
6.75 4.02 2.60 1.52 0.96 0.67
INSTALLATION DETAILS
' Items that should be considered in the design of this type of system are:
All piping must be so pitched that all air in the system can be vented either through
an open, expansion tank, radiators or automatic relief valves.. When piping must be
run around an obstacle such as a beam, it is advisable to drop the piping below the beam.
If looped over the beam, it becomes necessary to provide for venting of air from the
high point of the pipe..
. . ..
When changing the, size of horizontal runs of pipe, eccentric fittings should be used to keep the tops of the pipes in line to permit free passage of air along the pipe.
All piping must be arranged so that the entire system can be drained. Sections of piping individually valved shall have corresponding drain valves.
In large buildings, the piping may be zoned according to exposure of building, usage of building, or method of control.
All piping must be installed so that it is free to expand and contract with changes of temperature without producing undue stresses in the pipes or connections. For this purpose it is generally sufficient to.allow for a variation in length of 1 in. for 100 ft of pipe.
The pipe system should be designed so that each circuit has its correct friction for
balanced water distribution. This may be done by change of pipe size or change in pip ing detail.
The connections from the boiler to the mains should be short and direct, to reduce thefriction and should allow for expansion.
- The mains and branches should pitch up and away from the heater, generally not less than 1 in, in -10 ft.
The connections from mains to branches and to risers should be such that circulation through the risers will start in the right direction. Hence, in a one-pipe system the flow connection must be nearer the heater than the return connection. In a correctly-
designed two-pipe system, the pressure in the flow main is higher than that in the return
Hot Water Heating Systems and'Piping
471
main, and a slight variation in the distances of the flow and return connections from the heater is not material; blit it is generally best to have the two connections about equally
distant from the heater. i Generally,.connections to risers or radiators are'taken out'of the top of mains either
45 or 90 deg.
>, .
. " -
Supply connections are usually made at the bottom of radiators so that circulation
will not be stopped by accumulation ?0f air, as would be the case with a top supply
connection. Short radiators are'sometimes connected for-top supply and' bottom re turn on the same end. When so'connected, attention must be given to venting of air
from the top of the radiator somewhat oftener than when bottom connections are used.
Unless used as heating surface, all piping, both flow and return, should be insulated.
All large systems should be provided with extra stop and drain valves, suitably located
so that parts of the system may be isolated for repairs without making it necessary .to
drain the water from the entire system.
":
Fig. 17. Illustration of Vertical Zoning in Hot W/ater Heating System in a 12-Story Building
ZONING
In large hot water systems improved control and economy can. be achieved by separating the systems into sections or zones (vertical or horizontal) which can be operated independently of each other. Vari ations in heat requirement of the different zones as influenced by the exposure of the building, solar heat, weather conditions, heat from processes, type of occupancy, building chimney'effect, etc. can readily be compensated for when heat can be supplied only where needed.
In tall buildings, vertical zoning such as shown in Fig. 17 not. only provides the advantages of control and economy, but also reduces the water pressure in the system to that caused only by the number of.floors served by each section. As shown in Fig. 17 a steam boiler can con veniently be used to supply steam to the heat exchangers supplying
heated water to each zone.