Chapter 24
1945 (Guide-
This law applies strictly, only to what, is known as ah ideal solution, .that'is, one in which the inter-molecular forces between the substances present in the solution are equal. Actually, no such solutions exist, so that deviations from Raoult's Law are always found in practice. The deviation is called positive when the observed pressure is greater than that-calculated from Raoult's Law, while the term negative deviation refers, to the opposite case. Negative deviations are found wherever chemical attraction exists between the solvent and the solute. Positive deviation occurs when there is a difference in the internal pressure of the components, chemical attraction between them being absent.
In order to make an effective absorption machine, large negative
Refrigeration
451
initially low (weak) in refrigerant concentration. The absorbent absorbs the vapor and the strong absorbent liquor is transferred to the generator through an interchanger with the weak liquor returning from the generator.
A cooling medium, ordinarily water, is used in the absorber to remove the heat of absorption and maintain the absorptive power of the absorber
at a maximum. . '
Like the steam jet system, the absorption system compares most favorably when a cheap source of cooling water and steam or other heat, is available: Unlike the steam jet system, the comparative performance is usually best with a wide range of temperature between the evaporator and absorber, since with a good refrigerant-absorbent combination, the amount of heat and water required for a given refrigerating effect in-
Fig. 5. Performance Characteristics of Compression Refrigeration Machines at Constant Speed
deviations from Raoult's Law must be shown by solutions of the refrig. erant in the liquid absorbent, because the larger the negative deviation,
the greater is the amount of refrigerant that can be cycled, using a given weight of absorbent. Cycling'a large amount of refrigerant for a given weight of absorbent is important because of the heat required to raise the temperature of the mixture and disassociate the-refrigerant and the absorbent. Only the latent heat of the refrigerant can be recovered for useful work.
' Many refrigerant-absorbent combinations have been proposed and quite a number have been tested. A diagrammatic representation of a typical closed absorption system is outlined in Fig. 6. In this system a mixture of refrigerant and absorbent is evaporated in the generator, passes to an analyzer and rectifier where it is purified, and then to a con denser where the refrigerant and remaining absorbent are condensed. It then passes through an expansion valve to an evaporator, where heat is absorbed from a cooling load. From the evaporator the vapor and resi dual absorbent passes to an absorber where it meets absorbent which is
Fig. 6. Closed Absorption System
creases slowly with an increase of evaporator-condenser temperature
range.
'
At the present time the most used refrigerant-absorbent combinations
are: (i) water and ammonia, and (2) dichloromonofluoromethane and
dimethyl ether of tetraethylene glycol. With the latter combination the
boiling points of the refrigerant and absorbent are sufficiently wide apart
that almost pure refrigerant is obtained without the use of a rectifier.
EXPANSION VALVES
The thermostatic expansion valve is a device to regulate the flow of
liquid refrigerant so that the evaporator will always be used to best
advant^e. The evaporator coil must be kept as full as possible without
any chance of liquid refrigerant entering the suction line. The expansion
valve accomplishes this by regulating the supply of refrigerant, so that
the temperature of the gas leaving the evaporator is always slightly
higher than die temperature of the boiling refrigerant inside of it. This
difference in temperature between the outgoing (suction) gas and the
liquid refrigerant in the evaporator is called the superheat of the gas.
The operation of the thermostatic expansion -valve can best be ex
plained by means of a diagram, Fig. 7. A small refrigerant charge in the
control bulb exerts a pressure through the tube to the upper side of the
diaphragm, which tends to open the valve. .
,