CHAPTER 34
1949 Guide
positioned by a thermostat or other controlling device, and is arranged to give a definite motor position for a given force from the thermostat without regard for motor hysteresis, friction, or pressure variations of the controlled fluid.
A sequence controller is used, to operate , two or more devices in a pre arranged sequence. It is generally used in connection with refrigeration compressors, and may be arranged to prevent simultaneous starting in
the event of temporary electrical shutdown or control medium failure.
Manual switches are available in the two-positipn or proportional types. Two-position switches change, the flow of energy from one line to one or
more other lines; or from one pajr of lines to another pair of lines. Pro portioning switches vary the flow of energy as determined by the manual
setting of the switch.:
.
RESIDENTIAL CONTROL SYSTEMS
The control equipment function in a residence may vary from the regula tion of a coal-fired heating plant to the completely automatic control of an all year air conditioning system. Regardless of the type of heating or air conditioning system used, the control system should be selected care fully to insure safety and comfort of the occupants and also economy of operation.
Heating Unit Controls
Typical controls for the appliances used to supply heat in residences are as follows:
'1. Hand Fired Coal Burners. The control of a hand fired coal burner for a boiler or furnace normally consists of, a room thermostat operating a two position electric control motor which in turn opens the draft damper and closes the check damper on a demand for heat. The motor then closes the draft damper and opens the check damper when the thermostat is satisfied. A limit control on the boiler or furnace Bhould be connected to the motor so that it may check the fire whenever a predeter mined temperature or pressure has been exceeded. A manually operated basement switch is usually included on the motor so that the draft may be opened and the check closed when the boiler or furnace is being filled with coal.
2. Coal Fired Stokers. Domestic stokers are usually controlled by a room thermo stat, a limit control,'and a stoker relay. When the thermostat calls for heat, the relay causes the stoker motor to increase the flow of fuel and air to the burner to itsmaximum rate. When the thermostat is satisfied, the relay provides for a minimum flow of fuel and air to the burner to maintain the fire at its minimum rate. The limit control prevents the continuance of the maximum fuel rate if the temperature or pressure in the boiler or furnace exceeds a predetermined value and also stops the feeding of fuel if the fire goes out. Automatic ignition usually is not available and the firing of a stoker is normally on or off.
3. Automatic Oil Burners. Automatic oil burner Controls normally consist of a room thermostat, a limit control, a combustion safety control, and a control relay. On a call for heat by the thermostat, the relay starts the oil burner motor which sup plies oil and air to the burner. An ignition device consisting of an electric spark or & gas flame ignites the oil automatically. If for any reason the oil and gas mixture does not ignite, a time delay mechanism in the relay is operated by the combustion safety control after a predetermined length of time to cause the oil and air supply to be shut off. If the oil and air mixture ignites properly the burner continues to run until the thermostat is satisfied or until the limit control affected by the temperature or pres sure in the boiler or furnace, stops the burner.
4. Automatic Gas Burners. The controls for an automatic gas burner usually in- . elude a room thermostat, a limit control, a safety.pilot, gas pressure regulator and a gas valve (solenoid, motorized or diaphragm type). Upon a demand for heat at the thermostat, the gas valve is opened, admitting gas to'the burner. The safety pilot ignites the gas which continues to burn until the thermostat is satisfied or until the limit control shuts off the gas valve. The. limit control may also reduce (throttle) the gas flame as required to maintain a desired temperature or pressure of the heating
Automatic Control
667
medium. If the pilot flame is extinguished for any reason either before or after the main gas valve is turned on, the safety pilot closes the gas valve, thus eliminating the danger of delivering gas to the burner without ignition.
5. Electric Heating. Electric heating has become popular in those areas where electric power is plentiful and inexpensive. The electric heating elements may be located in each individual room and turned on and off by thermostats in each room or the heat may be supplied by a central heating system. In the case of a central heat ing system the control is usually of the proportioning type which energizes from five to ten heating elements in sequence according to the demand for heat by means of a sequence controller consisting of a series of switches operated by a proportioning motor. A limit switch recycles the sequence controller if the furnace or boiler ex ceeds a predetermined temperature.
Limit Controls
A high limit control for steam consists of a pressure control having bellows, responsive to the boiler pressure, which breaks an electric contact when the steam pressure exceeds a predetermined point, thereby preventing the burner from delivering additional heat to the boiler. A low water cut-off should also be used to stop the burner if the water in the boiler drops to a dangerous level.
A high limit control for a hot water boiler consists of an immersion thermostat (usually equipped with a bi-metal helix) inserted in a well in the boiler. This control stops the burner when a predetermined water temperature has been reached in the boiler.
In a warm air system the high limit control is a thermostat including a bi-metal helix inserted in the bonnet of the furnace. It will shut off the source of heat when a predetermined furnace temperature is exceeded.
System Control
There are several types of system control in common use for residential applications. They are usually of the two position (on-off) type or of the proportioning type. .
1. Two Position {On-Off) Control. The most simple type of domestic control is the type in which the room thermostat starts the burner or other source of heat when the temperature of the air at the thermostat falls below the thermostat setting and stops the source of heat when the air temperature rites above the setting. If forced warm air or forced hot water is used, the fan or circulator may be turned on and off at ap proximately the same time as the source qt heat.
2. Proportioning Control. When a proportioning type of control is used, the flame of the burner may be varied or the burner may.be cycled (started and stopped) fre quently to provide for time modulation so that the heat input to the home is propor tioned continuously to the heat loss from the home. The fan of a forced warm air system of the circulator of a forced hot water system may be run almost continuously, thereby providing for the constant flow of heat into the home. Such operation elim inates the cold drafts, on the floor as caused by cold air dropping from cool walls and windows during the off period of an on-off system.
Room Thermostats
Room thermostats usually employ a bi-metal element or a vapor filled bellows as the temperature sensitive element. They may be of the plain or single temperature type; or of the day-night type providing for auto matic night lowering and morning increase of the control point. The automatic setback type usually includes a clock mechanism which accom plishes this result. Opinions vary regarding the amount of fuel that can be saved by automatic setback. Tests made both in the Warm-Air Heat ing Research Residence and the I-B-R Research Home at the University of Illinois indicate that, on thermostatically controlled systems, a possible