428 CHAPTER 29 1960 Guide ticeable only on the outside of the gland and stem of the valve where thin deposits of salt are left after evaporation. The insulation of high-temperature water lines is similar to that of steam lines.* The selection of the economical thick ness of pipe insulation is discussed in Chapter 32. Thermometers and Pressure Gages Pressure gages should be installed in the pump discharge and suction and at locations where pressure readings will assist operation and maintenance. Thermometers (prefer ably dial type) or thermometer wells should be installed in the flow and return pipes, the pump suction and discharge, and at any other points.of major temperature change or where temperatures are of importance in operating the sys tem. Thermometers and gages are desirable in the piping at the entrance to each building, hot water converter, or steam converter. (See Chapter 44.) SPACE HEATING EQUIPMENT In industrial areas, space heating equipment may often be operated with high-temperature water due to its avail ability. Convectors and radiators may require water tem peratures in the low and medium temperature range (120 to 180 F or 200 to 250 F) depending upon how close they are to the occupants and upon the pressure for which they are designed. The water velocity through the heating equipment affects its capacity. This must be taken into account in se lecting the equipment because, if a large water-temperature drop is used, the rate of circulation is reduced and conse quently the velocity of flow may be reduced sufficiently to lower appreciably the rate of heat transfer. (See Chapter 5.) The high temperatures of these systems make them ideally suited for direct use in radiant panel surfaces. Since radiant output is a fourth-power function of the surface tempera ture, the surface area requirements are materially reduced over low temperature water systems. The surfaces may be flat panels consisting of a steel tube, usually % or Vi in., welded to sheet steel turned up at the edges for stiffening. Several variations of this are available. Steel pipe may also be used with an aluminum, or similar, reflector to reflect the heat downward and to prevent smudging of the surfaces above the pipe. Table 2.,.. Head Loss fn Fittings* {For turimUai flew) Foot of Sam* Szo Flpo HarioQ Eqod loct* fitting* to 8 6 5 4 3 2K 2 iK <K t K M Globe Valve....;......................................... Gate Valve.................................................... 90 Welding Elbow...................................... 45* Welding Elbow...................................... 340 270 200 170 135 105 83 7 5.75 4.5 3.5 3 2.2 1.7 11 8.5 6.5 5.5 4.5 3.5 2.6 76 4.5 3.6 3 2.4 1.7 70 1.5 2.2 1.5 55 1.2 1.8 1.2 45 1 1.5 1 36 0.8 1.2 0.8 28 0.6 0.9 0.6 21 0.5 0.7 0.5 22M* Welding Elbow................................... Welding Tee*............................................... 54 W 20 17 14 13 10 3 2.5 2 1.6 1.3 1.1 0.9 0.7 0.6 0.5 0.3 16 13 11 8 6.5 5.5 4 3.5 2.8 2.2 1.6 10 8.5 7 5 4 8.5 2.8 2.5 1.8 1.5 1.1 8 7 5.5 4 3.2 2.6 2 1.7 1.4 1.2 0.8 CmcmMc From \ 10 8 4 5 4 3 Jw ' 2 IK IK 1 K K \. 10 8 6 5 4 3 2K 2 1M IK 1 K H 1 2.5 3.5 1.2 10 3.5 12 7.5 1.5 12 9.6 4.5 10 7 7.5 3 2 0.5 1.5 5 6 e E 'f LAIIGIh G. 2.8 2.2 1.3 0.5 1.8 .3.8 5 5 2.2 1.8 1.7 1.2 1.4 1.5 0.6 1.2 1.4 \0 0.8 0.7 \ 0 2.5 0.8 3.8 2.8 9 432 3 2.5 2.5 c ONT RAC TIN 3 1.5 1 0.7 0 0.3 1.25 2 2 1 0:8 0.75 0.6 0.6 0.6 0 0.5 0.5 00 0.5 \ 0 1.3 0.5 1.8 1.5 0.8 0.5 0.3 0.3 0 * Compiled from data published by Tub* Turn*, Inc., a Division of the National Cylinder Gas Co. Ueed by permaaion- b Watm deflected throodi branch. * Water flowing straight through fitting. * For eccentric reducers, the values read for wmcefitric rreducers most be increased by * Equivalent teocth of pipe having a Fannh ,t of 0406. High-Temperature Water Systems 429 TEMPERATURE CONTROL The principles discussed under Control of Flow in Chapter 43 apply, to high-temperature water systems, but added con sideration should be given to the selection and location of control components. Valve Selection Valve selection and siting are very important because of the relatively high temperature drops and Kmaiw flows en countered in high-temperature water systems. To obtain good control, the valve must be sized so that it is effective over its full range of stem travel. It is recommended that the valve size be selected on-the hatis of a pressure drop at full flow equal to approximately 50 percent of the pressure dif ference between supply and return mains at the location of the equipment served. The pressure drop across the valve must not be sufficient to result in a downstream pressure below the saturation pressure at the temperature existing at any point or flashing into steam will result. A valve with equal percentage flow characteristics is desirable. Sometimes fig. 14....Methods of Venting High-Temperature Water Mains two small valves are used rather than one large valve to improve the controllability of the system. Stainless steel trim is recommended, and all valve body materials and par-king should be suitable for the high temperatures and pressures encountered. The valve should have a dose-off rating at least equal to the maximum head produced by the circu lating pump. Generally, two-way valves are more desirable than the three-way type because of the equal percentage flow characteristics mid the smaller capacities available in two-way valves. Single-seated valves are recommended in preference to double-seated valves since the latter do not provide tight closing. Valve Location Control valves preferably should be located in the return lines freon heat transfer units in order to reduce the valve operating temperature and to prevent the high-temperature water from flashing to steam at the lower discharge pressure. Sometimes valves are located as low as practicable to in crease the 6tstic head at the valve and further minimize the possibility of flashing. This problem is minimimri in sys tems pressurized by inert gas, since a greater difference is maintained between the system and saturation pressure. Typical Applications A typical application is the control of the temperature of water leaving a heat exchanger in which high-temperature water is used as the heating medium. The temperature measuring element should be located where it can best detect changes and thus prevent overheating of the outlet water and possible flashing. When the measuring element is lo cated in the leaving water, there must be a continuous flow through the exchanger and past the element. If the water leaving the exchanger is used for space heating, the set point of the thermostat in this water (which controls the temperature of the leaving water by controlling the inlet temperature to the exchanger) can be readjusted in accord ance with outdoor temperature. fig. 15.... Arrangement of Boiler Feed Where Exhaust Steam Is Available