1937 .American Society of Heating and Ventilating Engineers Guide,
Aii Quantity'
The air supply to occupied spaces must always be adequate to satisfy the physiological requirements of the occupants. " It must be sufficient to maintain the desired temperature, humidity, and purity with reasonable uniformity and without drafts. In many practical instances there are two air quantities to be considered, (a) outdoor air supply, and (b) total air supply. The difference between the two gives the amount of air to be recirculated.
Table 3. Minimum Outdoor Air Requirements to Remove Objectionable Body Odors
(Provisional values subject to revision upon completion of 'work)
Type of Occupants
Am Space per Person Cu Ft
Outdoor Am Supplt CFM per Person
Heating season with or without recirculation. Air not conditioned.
Sedentary adults of average socio-economic status-- Sedentary adults of average socio-economic status-- Sedentary adults of average socio-economic status.-- Sedentary adults of average socio-economic status.....
100 200 300 500
25 16, v12
7
200 23
Grade school children of average class........................... Grade school children of average class........................... Grade school children of average class........................... Grade school children of average class...........................
Grade school children of poor class............ .....................
Grade school children of better class. .........................
100 200 300 500
200
200
29 21 17 11
m
18"
Grade school children of best class................:................
100
22
Heating season. Air humidified by means of centrifugal humidifier. Water atomization rate 8 to 10 gph. Total air circulation 80 cfm per person.
Sedentary Adults.
200 12
Summer season. Air cooled and dehumidified by means of a spray dehumidifUr. Spray water changed daily. Total air circulation 80 cfm per person.
Sedentary Adults.
200 <4
^Impressions upon entering room from relatively clean air at threshold odor intensity.
When the only source of contamination is the occupant, the minimum quantity of outdoor air needed appears to be that necessary to remove objectionable body odors, or tobacco smoke. The concentration of body odor in a room, in turn, depends upon a number of factors, including socio-economic status of occupants, outdoor air supply, air space allowed per person, odor adsorbing capacity of air conditioning processes, tem perature, and other factors of secondary importance. With any given group of occupants and type of air conditioner the intensity of body odor perceived upon entering a room from relatively clean air was found to
74
~Chapter 3--Physical and Physiological Principles of Air Conditioning
inversely with the logarithm of outdoor air supply and the logarithm ofthe air space allowed per person.
The minimum outdoor air supply necessary to remove objectionable hndv odors under various conditions, as determined experimentally at the Harvard School of Public Health44, is given in Table 3.
Outdoor air requirements for the removal of objectionable tobacco smoke odors have yet to be determined. Practical values in the field vary from 5 to 15 cfm per person; this air quantity may and should be a part
Fig. 7. Relation Among Rate of Air Change per Occupant, Moisture Content of Enclosure, and Dry-Bulb Temperature of Incoming Air
of that necessary for other requirements, i.e., removal of body odors, heat, moisture, etc.
The total quantity of air to be circulated through an enclosure is governed largely by the needs for controlling temperature and air dis tribution when, either heating or cooling is required. The factors which determine total air quantity include the type and nature of the building, locality, climate, height or rooms, floor area, window area, extent of occupancy, and last but not least, the method of'distribution.
Serious difficulties are often encountered in attempting to cool a room
"Loc. Cit. Note 3.
75