This information is provided as a service by Monsanto Chemical Company to help transformer users better understand the operating characteristics and maintenance procedures- with askarel liquid insulation, and how these differ from mineral oil insulation.
The information given on the following p&ggff is based on facts gathered by Monsanto during 30 years as producer of askarel. It represents knowledge gathered from the experience of transformer manufacturers and users over three decades.
Monsanto provides this information primarily as a guide on how to
obtain maximum service with minimum reasonable maintenance of
askarel dielectrics. All questions relating to the building and de
signing of transformers should be referred to regular transformer
suppliers.
Monsanto gratefully acJtnatuledges the assistance, guidance, and the contributions of certain
data by the foUotiring:
.
Prank M. Clark Edward L. Raab
James G. Ford Georgs Shbrobart, Jr.
General Electric General Electric . WesdnghouM Electric Allis Chalmers
PRR 051736
HARTOLDMONOO11660
)
\
t /
-1
1 VO.
AS KAREL - HISTORY OF TRAOE NAME TYPES
"Askarel" is the generic name for a special kind of liquid insulation that is'completely different from ordinary transformer mineral oils. Askarel6 liquid insulation -- whatever the trademarked brand -- is all made from Monsanto's Arocinr-1260 (hexachlordhiphenyl) ... one of the world's best Liquid insulations. This inert compound is chemically stable, fire-resistant, heat stable, non-corrosive, and has high dielectric-strength under the operating conditions encountered in askarel-type transformers. Monsanto manufactures Aroclor 1260 and formulates askarel liquid insulation to the specification of the various transformer manufacturers.
Askarel liquid insulation is made by thinning Aroclor 1260 with trichlorobenrene or tri-, tetrachlorobenzene mix, and by the addition of a small amount of a chloride "scavenger" compound. The first transformer askarel was made in 1932, in accordance with General Electric Company's patents, and was trademarked Pyranol 1488. In '49, General Electric Company patented and began the use of 0.125% tin tetraphenyl scavenger additive, and this new askarel formulation was called Pyranol 1467. Weetinghouse, too, offered an askarel insulation in 1933 under the company's trademark: Inerteen. The following table shows the composition and year of introduction of the two major types of askarel;
Inorfoon PFO `1949^
60
r40/ 0.20
Other Brand Names
Various manufacturers use other trademarked names, like
Chlorextol (Allis Chalmers); Noflamol (Wagner Electric); Asbestol
(Amertran Corp.); Saf-T-Kuhl (Kuhlman Electric). These askarel
insulating liquids are either one type or the other. Some manu
facturers, who designate their insulation by the generic name
askarel, assign a number or code so that Monsanto, when filling a
particular company's order, knows whether to furnish Pyranol 1470
or Inerteen PPO type askarel.
' ..
"Commonly uoed for transforms!*.
PRR 051737
HARTOLDMONOO11661
DIRECTIONS FOR HANDLING OF ASKAREL
In handling, storing, sampling, inspecting askarel -- and in the operating of askarel transformer* take every precaution to guard the askarel insulation from exposure to high humidity and moisture contamination. Keep 5, 30, or C5 gallon drums of askarel dry; turn them over on their sides to keep water off the drum head (it con be sucked in by the drum "breathing").
Stability of Askant Fluids
Askarel liquid insulation is a vary ear*/ully-manufactured, highly pure, chemically .made fluid. It does not vary in composition like the range of mineral oils. And, askarel is heavier than water. 'If water gets into the ' askarel insulation, only a tiny amount (J25 ppm) dissolves -- the rest . floats on topi
Askarel does not deteriorate when exposed to air, heat, hot metal; it does .. not break down over long use to form con/luding or corrosive chemicals;
it does not sludge or oxidize. Askarel will remain perfectly stable year after year unless broken down by exposure to severe arcing.
The only real "enemy" of askarel is contamination by water. Keeping <j*karel water-free will insure long-time service.
In emergency, the two general type* of askarel insulation can be
either mixed birinterchanged and there will be no difference in the
operation of the transformer. Do not, however, mix askarel type
insulation with mineral oiL
-
PRR 051738
t_
HARTOLDMONOO11662
The two different types of askard fluid simply differ in pour point and in die tiny amount of "scavenger" additive. The Pyranol type has the lower pour point; it will still pour at 47* below (T.) zero. The Inerteen type will pour down to 26 below (F.) zero. The different scavenger additives are both effective for absorbing hydrogen chloride -- which can be liberated from askard if it is exposed to strong arcing.
.
However, the additive in Pyranol type askard can "crystallize" out at 14* above (F.) zero and looks like a hazy cloud in the liquid. It does no harm; the crystals disappear after a while when the transformer warms up. This "hard' can be differentiated from water by a dielectric strength check.
Generally there is no need to mix or interchange; Monsanto supplies all
types of askard promptly --- anywhere in the world.
.
Askant should nenr be mixed with miners! oii
because the core binding materials and paint suitable for oil-filled units soften and deteriorate in askard. And, over 2% mineral oil mixed into. askard begins to lower its fire resistance.
USE ORDINARY PERSONAL PRECAUTIONS
:
Transformer askarel has been made, handled, and used for over 30 veara without causing tojdc or other ill effects. It can be handied With only fcainor precautions. If accidentally spilled on hands, serious skin irritation will not occur. However, the liquid has a sol vent action similar to paint thinner on the fats and oils of the skin and skin exposures may lead to drying and chapping.
'
'
Eye contact may result in painful temporary irritation but no per manent damage to tissues. If it gets in the eyes, flush with large amounts of water. As with all eye first-aid, refer to a physician. To relieve irritation, physicians have used a 1% Fontocaine solution as well as opthalmic cortisone acetate solution.
In case o? contact, wash off the skin with Boapand water; remove saturated clothing; clean up spills.
j I
Infrequent exposure to askarel vapors will not cause any ill effects. However, prolonged exposure to high vapor concentrations should be avoided.^If hot fluid must be bandied in a closed or confined area, provide ordinary exhaust ventilation -- or -- wear an organic cartridge respirator approved by the U. S. Bureau of Mines.
\
_.
PRR 051739
*j ;
*! ! j
iv
HARTOLDMONOO11663
/
CHECKPOINTS ON MAINTAINING AS KAREL INSULATION
Taka AS Possible Precautions to Keep Transformer Askars! Dry
Whether askarel transformers are used indoors or outdoors -- the major maintenance checkpoint to assure virtually trouble-free operation is. to eliminate possible contamination of the inside of the shell by moisture. (This is also true for oil-type units.)
The following design information is provided as a guide for the frequency ef inspection, for "modernizing" present units ... and for ordering new equipment. (Your best source of specific design infor mation is your transformer supplier.)
cover: Welded. When the entire transformer cover is welded onto the body of the transformer, this avoids use of a gasket-and eliminates "breathing" of humid air.
gasketing:.
.
Use the proper gasketing for removable hand-hole openings. For maximum stability and fit, place the gasket in a recessed groove. Fine grain cork impregnated with nitrile rubber is suggested for gaskets. This type material is designated as NC757 by Armstrong Cork Co., Lancaster, Pa^ and as M3 ISO by Wolverine Mfg. Co., Inkster, Mich. Suitable cement for this gasketing is dewaxed orange shellac, pigmented with iron oxide (available in pint size from -Westinghouse, Sharon, Pa Style No. 1150419).
Nitrile rubber is sometimes used to seal the hand-hole. Because it is slowly attacked by askarel, this gasket must be recessed to allow minimum contact. Tefion, DuPont's Viton and most silicone "rub bers," while relatively expensive, warrant consideration for long term use requirements, at least for the smaller size gaskets.
firm
Weld all fin connections.
PRR 0517*1
it
fc-
fe-
f
HARTOLDMONOO11665
conntetjonas
'
Weld all major instrument or pipe connections. For incidental taps or nipples -- above liquid wrap the thread with Teflon tape: belovr Liquid, seal threads with askarel-resistant cement, such as Westinghouse 6707-3 (a shellac base with special rubber filler).
bushing connections:
The most satisfactory bushings will be the type with rolled-on flanges with two ring seals rolled into a depression in the porcelain and sealed with silicone rubber rings held under compression. Metalto-glass or metal-to-porcelain sealed bushings are also satisfactory.
Bushings on smaller size transformers (around 100 KVA) can be
sealed with cork-nitrile rubber composition.
.
nitrogen blanket:
.
Blanket the "air space" above the askarel with dry nitrogen. If
the transformer has so many leaks that pressure will not hold --
then bleed in a small amount of nitrogen steadily. Otherwise, "mod
ernize" by welding.
'
Another approach to "designing out',' moisture contamination: call for a "conservator" attachment so that the transformer shell is completely filled with the Askarel. This eliminates the breathing of the air space. The liquid askarel level in the "conservator" is higher than the transformer cover; any water that would "seep" into the shell floats to the surface of the askarel in the conservator!
drying breath, ers:
-
'
Transformers not hermetically sealed, and designed to allow breath
ing, should be fitted with a drying breather containing silica gel or
anhydrous alumina.
A detailed description of this drying arrangement for mineral oil
units is contained in the booklet "Activated Alumina Maintenance
Program" (1955, Aluminum Company of America, Pittsburgh, Pa).
This approach is also suitable for askarel transformers.
-
PRR 051742
!
HARTOLDMONOO11666
If desired-----although these factors are unimportant -- to keep power factor as low as possible and resistivity as high as possible, hang a container of anhydrous alumina in the circulating system of the transformer (askarel as well as mineral oil units),
Expactad Sarv/ea Ufa and Importance of Moisture Protaction
Properly designed and installed askarel transformers will give trouble-free service for a minimum of 30 years. Since their introduction in 1932, the manufacturers report finding the over-all failure rate to be less than 0b% for all units under test and service conditions. The Edison Electric Institute's report (1956-1953) on their member utilities publishes the failure rate for askarel transformers as 0.13 per hundred banks per year! Even the rare reports of failure are invariably found to be due to improper sealing that allows moisture to enter.
The dielectric strength of askarel is highly sensitive to excess moisture; not
sensitive to ordinary dissolved contaminants. While the dielectric strength
can also be lowered by severe arcing, askarel turns noticeably black or has
particles of sooty carbon floating in it if arcing has occurred. Unless severe
, . arcing (internal electrical failure) has occurred, the dielectric strength is
also the "moisture indicator.''
.
New askarel has a minimum dielectric strength of 35 KV at 25C.; a maxi
mum moisture content of 30 ppm. If the dielectric strength is checked period
ically and decreases significandy -- this indicates moisture pick-up,
arcing, or both. When the dielectricstrengthhas dropped to 22 KV or less, an
analysis for water is necessary. If water is found in excess of 100 ppm, its
source should be located and corrections mads.
,
When the moisture content approaches 125 ppm (saturation level), the
dielectric strength of askarel drops below the value required for efficient
insulating. The moisture content should hot be allowed to rise over 70
ppm; it should be held as near as possible to 30 ppm. Maintaining a low
moisture level will assure high dielectric strength and top operating
efficiency.
.
' *> - SJrfe ot "Breakdown Sh+nqthn Te Amount ef Dissolved Water In Atliinl and Mineral Oil
Watst Content (PPM)
Breakdown Ve*e fASTM)
Aikeral
Mineral OS
0
70 KV
50 KV
20 55
39
40 47
30
60 40
26
60 33
22
PRR
051743
i?
? t- '____
>
HARTOLDMONOO11667
ksbaxhgbkbsb^^
--. .l$J)w.i
^rwifViThrfinitfriJjimi^>WlwiTi.
Traneformer Atlcartl ' Shipping SpetHUotlona
. , . . '
.
hopnlln Color, APHA
. 'j *
-. . *
Condition
'
Water content, ppm (ASTM D1633-60)
Acidity, mg. KOH/g. (ASTM D974-66)
. .
Dielectric Strength, 26*C., 0.1 Inch gap (ASTM D8T7`49)
Dielectric ConeUnt, 100*C., 1 KC (ASTM D924-49)
Volume Resistivity, 100*C., 600 volte DC
0.1 inch gap, 10* ohm-cm. ..
'
Inorganic chloride, ppm. Refractive index. 26*C. (ASTM D9Q1-66) Viecoeity et 37.8*C. (ASTM D88-66) Seybolt Universal Second*
Pour point *C. (ASTM D-97-67) Specific gravity 16.6/16.6"C. (ASTM D287)
Bum point (ASTM D92)'
.
Distillation range (ASTM D20-66) corrected for stem and barometric`pressure
. '
Fixed chlorine Comwion test
Color. APHA
TTO5 TO
Acidity, mg. KOH/g. Inorganic chlorides ppm.
Condition
O Scavenger content
Fyranl 1447
160 max. Clear . 30 max. 0.Q1 max.
36 KV, min. 3.7 to 4.0
.
. '
. . .
100
0.10 max. 1.6137 to 1.6147 64 12 f 32 or lower 1.660 to 1.688
None to boiling
Pyrartel 1470
160 max.
Clear 30 max. 0.01 max.
'
36 KV, min. 3,8 to 4.3
.. '
.
100
0.1Q max. 1.6076 to 1.6086 41 to 46 --44 or lower 1.663 to 1.671
Nona to boiling
'
IaaiIaaa 770
160 max. Clear 30 max. 0.01 nuts.
`
36 KV, min. 3.7 to 4.0
100
0.10 max. 1:6137 to 1.6147 64 i 2 --32 or lower 1.660 to 1.668
Nona to boiling
lat drop 40% 90%
200*C. min. below 270*C. 396 to 416*C.
1st drop 36% 66% 66%
96%
210*C. min. lat drop 240 to 256 40% 200 to330 90% 386 to400
396 to416
200*C. min. below 270*C.
396 to 416*C.
69.1% min.
60.5 6%
69.1% min.
After heating'with aluminum for 6hra. at 200 to 220*C.. tha aluminum must not be corroded
eitheg on visual or weight inspection end the eeksrel should meet the following epedficetione:
200 max.
200 max.
200 max.
0.01 max.
0.01 max.
0.01 max.
6.0 max. Clear
6.0 max. Clear
2.0 max. Clear
0.126% tin Utr*phenyl
0.126% tin tetraphenyl
0.18 to 0.22% phenoxy propane oxide
4- Arc formed gi
4-
Leaa than 1.0% of total combustible gooes Including carbon monoxide, hydrogen and volatile
hydrocarbon*.
-
HARTOLDMONOO11668
. . :] -A
5
A :n
5
j ')iI . * t
CHECKPOINTS FOR INSPECTING AS KAREL INSULATION
Periodic Inspection
On a regular schedule -- at six, nine, or twelve month intervals make a simple visual inspection of your askarel insulation and run a dielectric strength check.. If dielectric strength has decreased significantly from last inspection, or if it has gradually decreased to the 22-20 KV range 25C.) -- RUN A CHECK FOR MOIS TURE. Use ASTM D901, D877. (Karl Fischer Method)
WHAT CHECKPOINTS MEAN: Dielectric Strength The dielectric strength of askarel it the major indicator to the operating efficiency of your liquid insulation and of the askarel transformer itself. Besides the "visitor' inspection tests -- the dielectric strength is the only test necessary to run on a routine, basis. Well-sealed askarel transformers have service records of 25 to 30 years on the original askarel. New askarel has a minimum dielectric strength of 35 KV at 25C.; a maximum mois* tore content of 30 ppm.
Visual Inspections Color
New askarel is a clear, faint-yellow liquid. After long-term use, this color may gradually intensify to light brown-
Color Change
Any color Change such as taking on a green, red, or blue cast indi cates extraction. When distinct color pick-up is noted, the complete range of electrical Characteristics should be checked to learn if extracted color is the tell-tale for contamination. Notwithstanding, color change alone is not a danger.signal. When checking out a color change, the-dielectric strength is by far the most important of the electrical characteristics; not the Power Factor dr Volume Resistivity.
Contamination High power factor and low volume resistivity in transformer mineraHoib--. are commonly regarded as "danger signals" that the oU has 3Serwrate3 and broken down chemically.
This h NOT TRUE of ankarat liquid insulation.
PRR 05i?<*5
1
I r-'*.
A
HARTOLDMONOO11669
1
New, unused estate! ehow* thaw electrical mines:
Power Fecto
0.0M.2% @ 60 cyd/20C. (about 1-2.0% % 60 cydea/100*C.)
' ' Volume Reactivity: .100-1000 X 10* ohm-cm. ( 100*C, 500 V, DC, 0.1* gap)
Used askarel from SATISFACTORILY OPERATING TRANS FORMERS normally {and frequently) shows these values:
Power Factor:
20 to 80% @ 60 cyde*/100*CL
Volume Resistivity: about 25 X 10* ohm-cm. (9 100*0,500 V, DC, 0.1* gap)
'
This relatively high power factor and the relatively low volume resistivity of askarel sampled from normal operating transformers ARE TO BE EXPECTED. Even at these levels, the ashore?s dielectric strength is EX CELLENT, STILL in the 30-35 KV range.
The reason is simple: askarel, unlike mineral oil, is a relatively polar
liquid. With double the capacitance of mineral oil, askarel has greater dielec
tric strength. And this property is the important factor for transformer
insulation. Thus, the volume resistivity ofaskarel is more sensitive to traces
of conductive contaminants than oil. However, even in the presence of large
amounts of contaminants, the volume resistivity does not seem to fall below 5
x 20* (ohm-cm). Yet the dielectric strength remains high, because intrinsi
cally askarel remains a non-conductor.
.
-
Apprexlmeto.jteterionfhip Between Power factor. Volume BnUHvity, and Dielectric Strength at Trenttenner Askarel
.
Fewer peeler (40 cyrt**)
100*C
2S*C
2% 5% 15% 20-25% 40-50%
0.06%
0.1% 0.7% 2.0%
- . Volume XeeltMvhy
i 10* ehm-<m. t@ ' 100* C, SOO Vette
DC,0.1*gep)
1500 500 . 100 60-70
25
OMedrie Strength 24*C, Q.1 * gap
' >35 KV >35 KV >35 KV >35 KV >35 KV
Clarity v
Inspect to make sure askarel remains clear in service. Development of turbidity or cloudiness indicates contamination from water, insulation particles, metallic dust, or dirt. Cloudiness or turbidity calls for complete analysis (unless the askarel is Pyr&nol 1470, sampled after extreme cold that has temporarily precipitated the "scavenger")* Heating to 150-200F. and agitating for a few hours will make this type of turbidity disappear; a dielectric atrength (high result) check test will prove this white cloudiness is not water.
PRR 051746
|
j
j 1
i .. ____
HARTOLDMONOO11670
Turbidity
. . ..may be the visual sign of water, or may indicate contamination from core materials, dirty or deteriorating construction materials.
Appearlinate Solubility of Woter in Tramtgrmef A titare! end Mlorl Oil
Taiwyatefwa
Aiwuit> at Ww (RRM) OlttWved
*c
*9.
Atiwat
Mlra4 08
-30 -22 8 8
-20 - 4 16 10
.--18 14 28 13
0 32 41 20
10 60 66 33
20 68 94 66
30
86 128
86
40 104 170 130
Effect ef Cmnwt Insulation Materials on fawer factor and Dtetectric Jtwagffc
(Root Aged 96 hr*. In Atltorel @ 100* C.)
.
Material (nvnenad
-
None (control)
Black varnished doth '
Copper
Preeaboard .
Manila paper
BiJcaiite
.
SheJlac .
Iron
'
Synthetic rubber ' ' .
' .
Askord After lxpc
Rawer Raster,
Olateriric
Rareate Q M
rye, 10C*C
sre
L0 85.0
L3 2.0 1-3
US . 8.0
6.0 70.0
38 KV 42 KV 40 KV 37 KV
39 KV 41 KV 36 KV 39 KV 39 KV
Effect of Common Insulation Materials on Volume Resistivity of Aikemt
Sompto '
'
L New askard before boot aginf
Vefamo tedWMty
x 10* efcn-cm (@
JOO*C. 300 Volte
.
.^
DC. 0.1* coot ,
'
2,000
2. New aakaral after boat aging 96 hr* & 100*C. .
1,900
' 3. After heat aging with 1 cq. Loch specimens of:
a. Phenolic ream tap changer material
-
1.200
b. Paper
' . ' 760
e. Grade A press board (tan) '
600
cL Grd^_A press board (gray)
- .'
600
` a. Grade A press board, laminated strip
'
- 400
L Cotton wrapping
300
g. Glyptal 1276 nwnent, cured 43 bra. @ 110C.
100
High dielectric strength will quickly indicate that any turbidity present is not moisture; that the insulating efficiency of the askard is Still excellent. While relatively high power factor and low volume resistivity are to be ex pected, when turbidity or a foreign color occurs these electrical values may confirm the askard may be in contact with deteriorating construction materials.
PRR 051747
H
HARTOLDMONOO11671
Black Color and Carbon Partidn ...
show that askarel has "arcied,'* especially if in the blackened liquid
small particles of carbon can be seen. Ask&rel that has been exposed
to arcing cannot be "refined" and should be discarded. To check the
visual appearancechemic ally, din moist blue litmus paper in sample.
If paper turns red, the askarel has been arced beyond ability of the
scavenger to capture the hydrogen chloride. .
.
Asian/ Stability
_
jg.
Askarel insulation is one of the most inert, ehemically-stable, heat resistant,
non-corrosive liquids known.Jt will not break down, oxidise or sludge when
exposed to air and high temperatures, 15CPC. or even somewhat higher. Arc
ing, however, will break down the compound, to liberate some hydrogen
W chloride and small amounts of carbory^
-
Appeaxlmoia CoonpoeMaa & Arc Formed Got From Tnrtufwmor Allard .
carbon monoxide carbon dioxide oxygon
a........
hydrogen chloride
(U pet,east
0.3 par cast
0.6 pee out
1-3 pet amt_
97J per cant v- --
It has been calculated and theorized that one kilowatt of arc energy am pro
duce about Tg-j nf
decomposition from askarel; compared with
about 85 cc. of gas from mineral oiL
''
Moisture
If the inspection sample of askarel shows 35-30 KV dielectric
strength by the ASTM method, there is no need to check the
moisture content. However, if dielectric strength has gone down
to the 22-20 KV range, check for moisture using the Karl Fisher
Method, ASTM D-1533.
~
-
Dielectric Strength Is Moisture Indicator
?
The moisture content of new askarel is 30 parts per million maximum. The moisture saturation level is about 125 ppm at ordinary temperatures. When the moisture content approaches 125 ppm (saturation lead), the dielectric strength goes down. The moisture content of askarel should not be allowed to rise over 70 ppm; it should be held as near as possible to 30 ppm. AskareTs dielectric strength am be restored to the 35-30 KV range by simple refinement to take out the dissolved moisture. When the didedric strength indicates it is time to refine the askarel, it is also time to inspect and get rid of any water accumulation in the transformer shdL
PRR 051748
HARTOLDMONOO11672
i
3A\
*7/.T4
'.1
3
i y
at 4 l.< *
i ri
INTERPRETATION OF AS KAREL INSPECTION FINDINGS
Judge the condition of your askarel insulation and the transformer on the basis of your visual inspection, the dielectric strength, and (when dielectric strength is found low), by the amount of the usually confirming high moisture content.
Do NOT judge the conditions on the basis of the. askarel's power
factor or volume resistivity.
'
High Power Factor end law Volume Resistivity
... in used askarel is to be expected; these values are not an indication
of chemical or electrical breakdown . . . even though tuch values often
indicate mineral oiTs breakdown. Askarel and oil are two different chemical
substances. Askarel is (compared to oil) a relatively polar liquid . . . highly
sensitive to traces of ionizable impurities. The dielectric constant of new
aSkSTd it about 4, nearly twice as high as mineral oil. Infinitesimal
amounts of impurities from insulation, dirt, coatings can markedly in
crease the power factor. (The same amount might not affect oil at alL)
Andfurther, unless critical care for cleanliness is taken in making the power
factor test on askarel -- the result can be erroneously still higher! With
a power factor so sensitive and a test procedure to strict -- it is to be
expected that when askarel is put into a new transformer, the power factor
will go up immediately on contact with the materials of. construction.
Authorities agree: the power factor of askarel in use will be high, as much
as 20-30% at 100C. and 60 eye. (about a tenth of this at 20aC.). In
service, the power factor of askarel "goes up" to a greater extent than
mineral oil, but this -- in the absence of Other "signals/* -- has
no significance. .
-
High power factor alone is not a danger sign with askard insulation IN A PROPERLY CONSTRUCTED TRANSFORMER. However, high power factor in the absence of moisture in the shell, coupled with "turbidity* and/or distinct foreign color, can indicate improper con struction.
Volume resistivity, too, may be expected to decline fairly rapidly even in a
normally operating transformer. It should not drop below about 25 x Iff
ohm-cm. and experience shows it will not drop below 5-10 x Iff even in
the presence of heavy contamination, other than water.
.
PRR 051749
u
HARTOLDMONOO11673
' A <f J Sv; M *<*-).
K> ' <!
f
)
>1
i
j i/
r ,mh >,
INSPECTION INTERPRETATION
If askarel isclear, even though darkened to brown; has no sediment
or turbidity; has dielectric strength over 25 KV . . . give it the
inspection "OK**.
.
If askarel is clear; has foreign color of blue, green, red ... it is "extracting color", from internal materials. This is not, of itself, an operating hazard when the dielectric strength stays over 20 KV and moisture remains low. However, this rare occurrence calls for checking into condition of the interior construction and consulting the transformer maker.
If askarel is clear; but dielectric strength drops to 22-20 KV, and moisture rises over 70 ppm . . . the askarel is ready fbr simple "refining".
If dielectric strength has dropped to 22-20 KV or lower range; . and if moisture is 115-125 ppm... the askarel is ready for refining.
. A thorough inspection should be made for water droplets in the transformer shell, and even for "globules" of water floating on the askarel surface. If found, mechanical means should be devised to protect the transformer from "breathing" moist air to prevent recurrence.
If askarel is dark brown to black; if black particles of carbon are seen; and dielectric strength is low ... the askarel has been broken down by arcing. It cannot he refined and should be discarded.
If any of these five simple inspection tests'appear out of the ordi nary or the relationship between appearance and test values is abnormal^ --- contact your transformer supplier for a complete analysis.
Whenever a sample is to be shipped tp the transformer manufac turer (or to Monsanto) for complete analysis, the container must be a 4 to 5-pint amber glass bottle. For your convenience, virions transformer manufacturers and Monsanto will send you the sample bottle filled with new askarel. You simply empty out the new askarel and re-fill the bottle with your sample. Follow the directions shown under: "Sampling."
I
-- "Ti>ii"<,i>^niiiiiimiiitmiiitiii
. --A-
--r* - w"
PRR 051750
P - :
}
HARTOLDMONOO11674
WHAT TO DG...
.
To mhtuaaa inspection and maintananca
These simple tests will show you the condition of your ashard insulation,
but only indirectly the condition of your transformer. They can he relied upon when your inspection sample is carefully taken (so as not to "miss'* moisture on the surface), If you have taken mechanical precautions against moisture entry into your askant transformer --; and can "Jkeep. it dry1' -- these tests will be your assurance that, between checks, you can forget about maintenance.
' '
Check out: Is your transformer completely and hermetically sealed or does it have gasketed areas? (Even the tightest gaskets can "breath".) Do you have d high fluctuating load1 (Hot-Uxoid temperature cycling makes the breath ing faster and harder.) is the air around your transformer cold and dry or hot and moistl
When you have condensation from "breathing" and high humidity -- you can guard against trouble by fitting the transformer with a drying denies (all transformer makers offer these).
.
Or you can bleed-dry nitrogen or dry air through the "air spaed* abacs
the askarei. The important thing to remember is that any mechanical steps
you take to stop'inside condensation will be double protection for trouble-
free-operadon.
.
, .
' '
'
When buying.equipment, specify whether transformers are intended for
outdoor installationor wHl be used in a high moisture area. If so, ids wise
to pay the only slightly increased cost for "designed-in" moisture protec-
Hon; this will more than pay for itself because askard units, properly
protected from moisture entry, wiU give trouble-free operation indefinitely.
''
'
' .
. .
* <
i
i
. PRR 051751
HARTOLDMONOO11675
HARTOLDMONOO11676
` `i -
HARTOLDMONOO11677
*
/
J
/
Sampling Askarel
Take a sample as close to the top of the liquid surface as possible. (Many large askarel transformers have a built-in sampling tube pear the surface for convenient sampling.) Then to make sure that your SAMPLE truly represents your askarel insulation, take another sample from the bottom. If additional sampling tube con nections are contrived on the valves for easier sampling, make the tubes of clean glass, stainless steel, aluminum or tin for rigid types; and silicone or Teflon tubing for flexible types.
% Use NEW containers for the askarel sample. A new and previously unused.small mouth pint glass bottle fitted -with a Bakelite screw cap fitted with an aluminum or tin bottle cap liner is recommended. Be sure that the new bottle does not stand open to collect dust or moisture. Rinse the sample bottle and cap lining two or three times with askarel from the transformer, then fill it. If the sample will be tested, promptly, a clear glass bottle can be used. If sample is to be stored indefinitely, Use an amber glass bottle or wrap clear glass with aluminum foiL
i
4rt. 1. Select a dry day. Do not sample insulation on a warm, moist J day when humidity exceeds 75%, and ...
2. Make sure that the askarel Is at least as warm as the surround ing air. (Gold liquids can condense moisture from humid air.)
Water floats an askarel
If there is any water in your .transformer, it may collect in litde puddles ON TOPof-the askareL And therefore, mote water will probably be dissolved ' in the askarel near the top, where it contacts any collected condensation.
4 If you find low dielectric strength and high moisture in the askarel, you , 1I will probably want to thoroughly dry out the core and coil structure and
consult the manufacturer for instructions.
When you take your askarel sample for testing, take the same precautions (but no more) that you would take when sampling mineral oil. i
t
i
I
!II l
PRR 051754
' .'if*-et
A
,Vr>at ,,
kdati
eaiStaMi
HARTOLDMONOO11678
Refining Askarel for Ro-Usa
Most operators prefer a portable refining apparatus, such as a plate press, fitted 'with a dolly, (available from Sparkler, Mundelein, HL); or the earthen cartridge filter type, (available from Industrial Filter Corp., Lebanon, IncL). Filter paper liners for the plate press axe available from Carl Schleicher & Schuell Co., Keane, N. EL
If you use a filter press, before refining it is advisable to oven-dry the filter paper at 110C. for 3 to 4 hours in an air circulating oven to remove all moisture. If the askarel to be refined contains exces sive moisture-, circulate it hot (55-60C.) through the filter fitted with the paper liners only. After.filtration the dielectric strength should be 35 KV., minimum.
Precautions Any flexible hoses and gaskets on the refining equipment should be lined with or made of materials that will not be softened by contact with askarel fluid. (Silicone or Teflon-lined, or flexible metal materials are suitable.)
i
i it
OuJ to Rato of Obtofvod Wotor Removal by
-
Ftftorin? AekaraJ Through A Popor Pr**a
'
' Pom Tfetowah '
... " PeporFim
.
Wotor la AtJtaral . rm
1.
'
2 ' ' .
3
' 4.
:
5
6
115 35 ; . 22 18 12 10 10
.
. .
PRR 051755
9
HARTOLDMONOO11679
/
Treatment for Maximum Improvement of Power Factor and Volume Resistivity
Use Attapulgus clay or Fuller's earth, dried and activated by
heating for 12 hours at 250F. immediately prior to use, as a coating
on the filter surface. The amount of earth used should be 0.1 to 0.2
per cent by weight of the askarel (askaxel weighs about 13 pounds
per gallon).
-
To deposit the earth evenly* stir one-third of the earth with a small
portion of askarel in a clean container. Pump the mixture through
the filter and follow with two more one-third portions. Then circu
late askarel taken from near the top of the transformer, pass it hot
(55-60C.) through the filter and feed back through the bottom
transformer outlet. Continue circulation until the fluid is clear and
shows the electrical properties are fully restored.
.
Checking Transformer After Refining Askarel Fluid
' After refining the oakanl, the over-all insulation resistances of the trans
former should approximate the values for a new transformer filled with
fresh askarel. If the transformer insulation resistance is judged unsatis
factory, the manufacturer should be contacted for complete inspection and
analysis of the equipment.
'
Effect of Earth Refinement on Removal of Scavengers
Only slight and insignificant.loss (by selective adsorption) of tintetraphenyl and phenoxy propene oxide occurs when askarel is refined by treatment with 0.1 to 0J2 per cent by weight of earth. To remove significant amounts of the scavengers requires repetitious treatment with much larger amounts of earth.
.
- . Amwint of TIn-T*tf#phy1 DoplaHon From Vyranai 1470 By XapH*tov Tpaatwwit WUh One Ptf Can* by WatqM of Forth
`
________ _________________TW-Tafrph<wy)
,
Sampta
No. 1
0.119%
Aftar 4 ImtHionW at WC
0.018%
AIM* 7 treotmaota at WC
" 0.006%
No. 2
0.107%
Aftw 4 fraaftnanW
*C
0.021%
After 4 ftaatmanta f40*C
0.006%
PRR 051756
V
K-
HARTOLDMONOO11680
mill...........
TYPICAL VALUES FOUND IN ASKAREL INSULATION UNDER VARIOUS CONDITIONS OF USE
-... iA1 *i Now aiktnl
..
C . '
D . f
. Aekarel in property* After normal oper Non-arced but built new or rebuilt ation; a eurvey of 60 allghtly contend-
Same aekarel aa in Column D ---
unite prior to uee. unite, moat 2-6 yro. natod aekarel In
altar refining.
old; aome 10.
improperly* built
unite, new or
slightly ueed.
'
'V
Heavily arced aakarul due to neglect and internal eloctrical malfunction.
InepoctUn Chock Nlnli Color
Light straw
Light straw
Light straw
Clarity
'
Moisture 25*C.
Clear, free from particle
30 ppm
Clear, practically free from pertidea
30 ppm
Clear, trace of particles
10-70 ppm all dissolved water
Dielectric Strength 25*C., 0.1' gap
Volume Reeiativity 100*C.. 600 Volta, DC., 0.1' gap
36 KV minimum
36-48 KV
100 X 10* ohm-cm. minimum . usually 600-1,600
20 X 10* ohm-cm. minimum usually at laaat
100 X 10*
36-46 KV
16-400 X 10* ohm-cm.
Can have foreign eltadee,. blue, green, red cast.
Clear, alight amount of particles
20-100 ppm all dissolved water
Foreign ahadee remain showing extraction of oil soluble color.
Clear, free from particles
30 ppm
30-42 KV
40-46 KV
about 6 X 10* okm-cm.
atlaaat 1,600 X 10* ohm-cm.
Black
.
Contain carbon particles
Hear 12Sppm ntmlion level -- plus pqoBible undiaaolvad water
5-16 KV
about 3 X 10* ohm-cm.
.
Power Factor: 100*C..60 cycle
1 26*C. 60 cyclee
2-6% 0.06-0.1%
10-26% 0.6-2%
10 to near 80% 0.6 to near 10%
30 to 100% about 7 to over 16%
2-6%
.
0.1-4.2%
A properly built tnneformer it defined at cm In which the materialeof cenetruction or* chemically and electrically compatible with aehand.
100% at least 26%
i , 1
..
^ -'
`
.
PRR 0 5 1 7 5 ?
HARTOLDMONOO11681
CLEANING ARCED TRANSFORMERS
If a unit has arced so that the askarel is no longer fit for use, a
thorough cleaning of the unit is necessary before re-filling with
new askarel insulation and returning it to service. Follow
procedure:
.
1. Drain out all dark, carbon-contaminated askarel. (Discard by dumping or burying where it will not contaminate a water supply.)
2. Wire brush carbon deposits from internal parts and insulation.
3. Flush thoroughly using new askarel (not an oil, not a cleaning solvent).
4. Wipe internal parts dry of askarel with lint free rags.
5. Flush a second time with fresh askarel; drain; then fill to the
proper level with new askarel.
.
6. Energize transformer to warm the fluid for 24 to 48 hours;
then circulate the askarel through a filter, returning it' to the
unit filtered and ready for use.
.
.'
':V-`
PRR 051759
.. ...............ft*.......... . HARTOLDMONOO11682
Thermal Cenductmtf
The thermal conductivity values of Pyranol 1470'at 27"C. and 58 *C.
are 26-2 and 25-8 x 10*4 calories centimeters*1, degrees centigrade*1,
second*1, respectively. Or, approximately 0.06 BTU per (hr.) (sq*.
ft.) (F.) per foot.
1`
Heat Capacity
__
Over the temperature range of 25" to 125C. the specific heat of transformer askarel is close to 0-30 calories per gram per degree.
Coefficient of Expanse*
~_-
_ . ,, JS2* *s
The average coefficient of expansion of transformer askarel over
the temperature range 20 to 100*0. is 0.0007 cc/cc./C. One gallon
would increase to 1.056 gallons on heating from 20 to 100C.
Fire Rasstancs
" ..
1
To use the generic name askarel the fluids must be approved by the
Underwriters* Laboratories as possessing adequate Are resistance
and freedom from forming explosive gases when arced- These
liquids do not have a burn point (ASTM D92-30) (Cleveland open
eup method) up to about 205*GM at which temperatures they begin
to boil. The significance of this is that they do not burn or support
combustion under conditions encountered in transformewoperation.
Thus the danger of secondary explosion (or fire) is eliminated.
-- --
1-60 -40 -20 -0
20 40
60 80
Efltoct et Tfc<nprftvrtt m
E>M*<Vi< Sbv&qtii
AiJrarai
'
fit 7 ^mjinn iffmlir hr im nuifiln
^ 67 KV
63KV 57 KV : & 55 KV 50 KV 60 KV 48 KV . 45 KV
-
PRR 051759
HARTOLDMONOO11683
Vapor ProTaore of Pyranot 1467 owd laertoon PPQ
Tetwpatotwo *C
40 60 80 100 120 140
Vopo* fmw4 go. Up.
1 49 9
35 60 90
Temperature't
-20 0
20 40 60 80 100
THo Vlo*Hy ond D*nity of Pyronof 1457 and tnertoen PPQ.Type AtfcqrW
Vttity
Cewriatefcea
WyPwtg
Unbe+nmi
600
. 42 17 74 4-5
2.9
2J3
. 2400 196 85 50 40 36 33
0*ay
m/ec.
--
1474 1-552 1429 1407 1.486
--
.Solubility of Air and- Nitrogen ' .in Traniformer Atkorel
.
. '
'
.
.
Parrot* of 0 By Vetmoo ewrntif to
' 23*C rtc mm
,
iwc.
0*C 740 wag
.
lire. ioax.
Air 64 5-5 8-8 54 . Nitrogen 6.0 ' 49 S-5 4.4
(When container of aekaral ip heated rapidly from 25 to 100*C, no appreciable
gaming isobeerired.)
'
1
;.
Approximate Vapor Prereure v*. Temperafura ** , . For Tranafarmor Atkorel
' fytmd 1447 and
*C limww PPO
Pyrene! 1470
40 60 . 80 ' ' 100
120
140 .
1 mm Hg. 5 mm Hg. 9 mm Hg. 30 mm Hg. 60 mm Hg. 90 mm Hg.
- 0.9 mm Hg. . 3J'aa Hg.
84 mm Hg.
18 atm Hg. 32 mm Hg. 53 mm Hg.
PRft 051760
HARTOLDMONOO11684
* r f
i
ift.
fi J
Analytical Ssrviws on Transformer Askarsl Availabla from Monsanto
Transformer usene not wishing to make their own fluid analysis can obtain these services from
Monaanto. Simply contact Monsanto and specify what tnaiyieo sure wanted. You will be sent the
pro peraampie container filled with fresh sskireL When you receive this, empty it and
carefully taka your aampie (follow procedure for eampiing in thia guide) and send the container
to Monsanto'l laboratory. Charges listed include aampie container, shipping, handling, and
laboratory costs.
_
TYPES OF ANALYSES AVAILABLE
ANALYSIS I)
b) tevrti KeAnemefS.
ROUTINE MAINTENANCE CHECK Total Charge: $20.00
To determine the general condition of the fluid and find whether flither analysis is necessary, (one-quart sample required)
frooortt-- Tw*
, Color and Condition ' Dielectric Strength
Moisture
You will be notified of the results of this . test. If further testing is indicated, and you want a complete analysis, you will be eent a five-pint aampie container. This sample will be used for the following series of tests:
ANALYSIS 2)
COMPLETE ANALYSIS ' . Total Charge: $50.00
(al To determine the extent of fluid contamicadon. (b) earth refinement to deter mine whet degree of restoration of electrical and insulating properties is possible, (c) check test Co see bow the fluid responded to earth treatment.
.
) C+mpl*h> Anafydu to determine the ex ' tent of contamination
presenter Tewed
.
Color and Condition
Specific Gravity
Refractive Index
. .
Water
_ ...
Free Chlorides
-. '.
Aridity
,, . .
, Dieiedtric Strength '
' Power Factor, Dielectric
.
Constant, and Resistivity
Consists of treatment for 2,5 hours at 506Q*C. with 0.1 to 0.2 percent by weight of properly conditioned Atiapulgus day and than filtration through dry filter paper.
<) Anetytie After laberetery Earth KaAnemetSt
PropartUe Tmt+4
Refractive Index
Water
Free Chlorides
Aridity.
Dielectric Strength
.
Power Factor, Dielectric
Constant, and Resistivity
You will ha notified of the results of this test' series on your sample. Then, after re fining your entire transformer fluid fill you can check on the results by requesting the following analysis:
ANALYSIS 3)
ANALYSIS AFTER EARTH
' REFINEMENT Total Chargs: 530.00
' '
(This charge will not apply when analyses. 1 and 2 have already bean
. mads.)
To detannin* whether the entire lot Of
aakarel fill responded to the ium extant as
the laboratory sample, (five-pint sample
required)
.
Ptoperrtet Teitsd '
,
' Color and Condition ' ; '
Refractive Index
''
Water
Free Chlorides
Aridity
'
Dielectric Strength
'
.
Power Factor, Dielectric.
Constant, and Resistivity .
To arrange far the tests described nbtm ante to the following address:
Paul G. Benignus Monsanto Chemical Company 800 North Lindbergh Blvd. St. Louis 66, Missouri
. '
Samples to be tested should be dearly marked (or identification and tent directly to:
Monsanto Chemical Company - W-,;h Krummrich Laboratory
Monsanto, Illinois Attention: R. Kuster
'
PRR 051761
.j xj
m
m
CO /
mr-- rar <r
rr ts.
{ ' ' A '
HARTOLDMONOO11685
!*!
/ -v-1 H-'i
"Vi Sff I !- >A-f-,*?
I
I
/
-y .
.I
9
\
ORQANIO'CHEMICALS DIVISION
,
` ST. LOUIS CS, MISSOURI .^
. .:
i?
.
^
.
,4
. xt
. ~
The information heroin regarding obtaining optimum results rom_ aakhrel iuids in your transformer iuu been accumulated by Mon&tuiur for over 30 years from the experience of makers end users of aakarei transformers end it ig believed will be helpful.
Nothing harem'eh&ll be construed *s applying to ether than eskarat '
Insulation. Oats and maintenance suggestions herein do opt apply
to the,other components of the transformer. All operating and main
tenance suggestions recommended by the manufacturer of the trans
former should also bo carefully followed.,
,
Because these maintenance directions apply only to the aakarei insula tion, Monsanto disclaims any liability for damage to property or injury to persons arising tram transformer operation.
)-.
J UMdU.U
X A
nail. .xX
PRR 051762
HARTOLDMON0011686
P'OO 4 O<A
GC at Ql
<!
i
ij
i 1
I
\
/
t ,v?**s _'
' . 1. ' ' _ ' '
-
v ` . * > .
?, .../.''-
, . --
wfZXytfryjwisl-n*ir?r
HARTOLDMONOO11687
ORIGINAL