FORMATION OF PCDFs UNOER "OPTIMIZED" COMBUSTION CONDITIONS FROM LOW-LEVEL PCB OIELECTR1C FLUIDS
Mitchell 0. Erickson, Christopher J, Colt, Jtirus 0, Flora, Jr., Paul Q Goroan, Clarence L. Haile, Gary 0. Hinshaw, Fred C. Hopkins, Stephen E. Swanson
Midwest Research Institute 425 Volker Boulevard
Kansas City, Missouri 64110
Daniel T. Heggem U.S. Environmental protection Agency
Office of Toxic Substances Field Studies Brench, TS 798
401 M Street, S,V. Washington, 0C 20460
The Environmental Protection Agency {EPA) issued a final rule on August 25, 1982, authorizing indefinite use of certain electrical transformers containing poly chlorinated biphenyls {PCBs). This rule is known as the PCB Electrical Use Rule. At that time, information available to the EPA indicated that fires involving electrical transformers were rare, isolated Incidents. However, several recent transformer fires in buildings have brought into question EPA1 * earlier assump tion. The Agency has therefore issued an Advance Notice of Proposed Rulemaking (ANPR) (USEPA 1984a) and proposed rule (USEPA 1984b) to gather data on the spe cific risks posed by fires involving electrical transformers that contain PCBs and also on mechanisms for mitigating or eliminating these risks. Oepending upon the results of EPA's analysis of these data, the Agency may propose further control measures on the use of this equipment.
This abstract describes the methods and results of a study, conducted in support of EPA's data gathering activities under the ANPR, of the potential for forma tion of polychlorinated dibentofurans (PCDFs) and polychlorinated dibenzo-gdioxins (PCDOs) from uncontrolled fires involving PCB-containing dielectric fluids.
At high temperatures, such as those in transformer fires, polychlorinated bi phenyls (PCBs) react to form polychlorinated dibenzofurans (PCOFs) and other toxic by-products. The purpose of this study was to optimize conditions for PC0F formation in order to examine the potential for formation of PCDFs and poly chlorinated dibenzodioxins (PCODs) from combustion of selected PC8-containing dielectric fluids.
The study was conducted in three phases. In Phase 1, a bench-scale thermal de struction system, developed by MRI, was refitted with specific components in stalled to accommodate this study as shown In Figure 1. Then, a few test runs
HONS 213723
were made under preliminary temperature and oxygen conditions to ensure an ac* ceptaole system Plank. The concentrations of CO, C02, and 02 in the effluent were monitored continuously. The entire effluent from the thermal destruction system was passed through an XAO-2 trap to collect PCDFs and other semi volatile organics, The XAO-2 trap and a rinse of connective tubing were Soxhlet-extracted and cleaned using column chromatography to isolate the PCDFs and PCDOs. All sam ples were analyzed for PCDFs (and PCDOs In Phase 3), using high resolution (capillary) gas chromatography/electron impact mass spectrometry (HRGC/EIMS) in the selected ion monitoring (SIM) mode. Mo PCBs or PCDFs were detected in the Phase 1 samples.
The Phase 2 experiments were conducted to determine the optimum temperature, oxygen, and residence time conditions for PCOF formation. The feed into the system was mineral oil spiked with three individual PCS congeners which form PCDFs by the four known reaction mechanisms, A statistical analysis of the re sults for 33 runs indicates that both temperature and oxygen have significant effects on the PCOF yield and that the interaction between temperature and oxy gen is synergistic. The results indicate that the optimum values are a tempera ture of 675C and an excess oxygen concentration of 8X. The residence time did not significantly affect the yield in the range of 0.3 to 1.5 s, although lower times appeared to yield less PCOFs. Since residence time does not appear to significantly affect the PCDF formation, 0.B s was chosen as convenient for the Phase 3 runs.
In Phase 3, duplicate test runs were conducted with mineral oil and silicone oil dielectric fluids containing PCBs (Aroclor 1254) at concentrations of 0, 5, 50 and 500 ppm. A PCB askarel containing 70% Aroclor 1260 and a non-PCB askarel, containing mostly trichlorobenzene with some tetrachlorobenzene, were also tested in duplicate. PCOFs were found in all samples, except blanks, as shown In Figure 2. PCDOs were found in the samples from the trichlorobenzene runs and occasion ally at low levels in some of the other samples. Up to 5,700 ng total PCOFs/mL of spiked feed oil or 4% conversion efficiency (PCBs to PCOFs) was observed for the mineral oil and silicone oil runs. The PCB destruction efficiencies calcu lated for the 5, 50, and 500 ppm runs ranged from 79 to > 99%. Up to 19,000,000 ng total PCOFs/mL feed oil (19 mg/mL) or 3% conversion efficiency was observed for the askarel fluid. Statistical analysis showed a linear relationship for PCOFs formed versus the amount of PCBs (Figure 3). Although not statistically different, about twice the quantity of PCOFs was formed from PC8s in silicone oil than from the corresponding mineral oil samples. All eight PCDF homologs wert detected in the askarel runs with a maximum at the pentaCOF (Figure 4). With a few exceptions, only tri- through hexaCDFs were observed in the lower level runs, with a maximum generally at the triCDF homolog.
PCOFs and, to a lesser extent, PCDOs are formed from the trichlorobenzene di electric fluid under the optimum PCS-to*PCOF conversion conditions. Up to > 110,000 ng total PCOFs/mL feed oil (> 0.004% yield) and 1,900 ng total PCOO/mL feed oil (0.0001% yield) were observed for the trichlorobenzene runs. The homolog distribution of PCOFs is similar to that found from feeding PCBs. The amount of PCOFs formed is one to two orders of magnitude lower than for the askarel, but substantially higher than that for dielectric fluid containing 500 ppm or less PCBs.
The results of this work indicate that the optimum conditions for PCOF formation from PCBs are near S75C for O.B s or longer, with 8% excess oxygen. Under these
HONS 213724
conditions, PCDFs are formed fro mineral oil or silicone oil contaminated with PCBs at 5 ppm or greater. PCDFs are also formed from a trichlorobenzene di electric fluid which contained no detectable PCBs.
Further work is focusing on identification and quantitation of other products from combustion of these samples, and on running samples of other dielectric fluids, including paraffinic hydrocarbons, ester hydrocarbons, and tetrachloroethylene.
The work was supported by the U.S. Environmental Protection Agency under Con tract No. 68-02*3938. A more detailed report was published as EPA Report No 56^5-84-009.
REFERENCES
JSEPA. 1984a. Polychlorinated biphenyls (PCBs); aianufacture, processing, distribution in commerce and use prohibitions; use in electrical transformers. Advanced notice of proposed rulemaking, (49 FR 11070-11083).
USEPA. 1984b. Polychlorinated biphenyls (PCBs); sianufacture, processing, distribution in commerce and use prohibitions; use in electrical transformers. Proposed rule. (49 FR 39966-39989),
THERMAL COMBUSTION SYSTEM TO MODEL PCS FIRE CONDITIONS
inmtiwuMW iwllin
(fFItMM Qm Oj, CO], CO
ni Tw--fm. w*wtrt, wW I
W.WW
Figure 1
HONS 213725
PCOF FORMATION VERSUS FC8 CONCENTRATION
TETRA CDF*
Figure 3
PC8ASKAREL (70% Aradof 1200, 30% TiWitonKNflWiw)
rco> kxwiw< hk rc* wmii
Figure 4
Figure 2. Tetrachlorodlbenzofurans formed from various matrices. Note similar isomer distribu tion for the TCDFs formed from PCBs. Consistent patterns were noted for the other homologs.
HONS 213726