Document X3qQRK8GY33b4m9OmVQMoE0w

.1*3 S TRLiMuNT FUNCTION OUTLINE UEPAiu.u...^ Emu ,.. ' TITLE REBOILER FURNACE' -'307 - SHUTDOWN LOOP NUMBER 307-1 SHEET 1 . WRITTEN BY OF ' 2 CLASSIFICATION B-307-1 , DATEREV. BY.DATE_________________________ REV. NO. 1.0 ,. : ' NEED FOR LOOP The purpose of this description is to define the furnace shutdown system (interlock ). The purpose of the system is to protect the personnel and plant against abnormal operating conditions. 11 Description of Loop . .' The shutdown loop is composed of: a. 8 interlocks that will close all 3 ACV's in the fuel lines and sound an alarm. ' b. 4 other interlocks will close on the one ACV in the fuel line affected and sound an alarm. . The first 8.are: ' ... . 1.1.1 Power Failure ' ' . 1.1.2 Main power switch in the furnace field cabinet. 1.1.3 Pushbutton on the panel board in the control room. 1 1.4 1.1.5 1.1.6 Switch on the panel board in the control room that . is used to dead-head the jet. High furnace stack temperature of-500C. The thermocouple is located in the stack and the monitor (indicator) is located in'the field cabinet, upper right-side. If this interlock is in (tripped) a faint red glow will come from the light behind the small door and the reset must be pushed. Normal .. temperature when making 1016 is 400C.'' - ' ' j High Aroclor temperature from the furnace coil will trip -the interlock at 330C. The thermocouple is located in the coil outlet line under the furnace'. The temperature is recorded and the interlock, is on (TJRIA-300) In the control room, point #5. V . 117 Low flow from the furnace coil Is set at 420 GPM. The alarm contact Is in FI 307, located at the bottom of the furnace, north side. See IFO FIC-307-5.- (r PCB-ARCH-EXT0373561 -# . 'instrument function outline TITLE REBOILER FURNACE - 107 - EHUTPOWN SHEET 2 .OF 2________________________ JRITTEN. BY_, DATEREV. BY DEPARTMENT 2^ LOOP NUMBER- 3g7^1 CLASSIFICATION B-307-1 DATE REV.NO. 1.0 NEED EOR LOOP (cont'd.) 11 Description of Loop . 1.1.8 High temperature of vapor from the vent cooler, . ' on top of the column,- will alarm at 55GC and the Interlock will come in at 100C. The thermocouple is. located in the vacuum line by the dead-head valve. . ' The recorder is ^n the control room. #7 point brings in the alarm (55 C), #16 point is the interlock . ' (100C). Both points read from the same thermocouple. All the above interlocks will close the 3 ACV's in the fuel lines, gas or oil, to the furnace burners. They must all be satisfied before the furnace can be lighted. All the interlocks will sound an alarm in the control room and the tel-alarm window "furnace shutdown" will light. The alarm in the field cabinet will also sound. The second four interlocks for individual burners are: 1.2. 1 Pilot flame .failure (purple peeper). 1.2.2 On-off switch in the. field panel. 1.2.3 Individual stop .buttons in the field panel. 1.2,4. A) Each burner has 2 pressure .switches for gas pressure. High pressure Is set for 40#. Low . pressure is set for 10#. The normal pressure at at the regulator gauge Is 3.3#-. The pressure switches are mercolds located before the ACV's. , . B) Each burner has 2 pressure switches when using . fuel oil. One (l) is for low fuel oil pressure . and is set for 25-30#* The other is for low atomizing steam pressure and is set for 50#. In all the above cases, if one burner goes down, the alarm will sound in the control room and the tel-alarm window - '"furnace shut down" will light. BUT if another burner goes : down there will NOT be another alarm on the tel-alarm. There Is an alarm in the field cabinet. It will sound each time a burner goes down. . ' . 1-3. ' Also see drawings 2417, E5 and e6 and IPO. FI307-5.. . PCB-ARCH-EXT0373562