Document VrV5GGXy2Dy4QKJ7w1rZ2pEq

r7 HEATING VENTILATING AIR CONDITIONING CUIDE 1940 Table 11. Typical Calculation of Pipe Sizes on Up-Feed Riser with Flush Valve Water-Closets and Urinals (See Fig. S) Floor op Bldg. 8th 7th 6th 5th 4th 3rd 2nd 1st Fixtures on Floor 4 W. C. 2 U. 3 Lav. 4 W. C. 2 U. 3 Lav. 4 W. C. 2 U. 3 Lav. 4 W. C. 2 U. 3 Lav. 10 Lav. 1 S. S. I S. S. 1 S. S. Gpm PER Fixture 45 30 3 45 30 3 45 30 3 45 30 3 3 4 4 4 Maximum Gpm on Floor Maximum Gpm on Riser PROBABLE Use (per cent) Probable Demand Riser Gpm Allowable Drop Lb per 100 Ft 180 60 9 249 249 44 109 8.5 180 60 9 249 498 28 139 8.5 180 60 9 249 747 22 164 8.5 180 60 9 249 996 30 1026 18 179 18 185 8.5 8.5 4 1030 18 186 8.5 4 1034 18 187 8.5 4 1038 IS 188 8.5 Pipe Size In. m 2M 3 3 3 3 3 3 Table 12. Suggested Storage Tank Sizes for Homes and Apartments Art. Ybab Service j Service Dokino.Hbatino Season Based on Boiler Water at 180 F g Babes on Boiler Water at 215 F Tank Capacity 30 35 40 50 60 72 80 100 125 150 200 250 300 400 500 Piping Connection* Boiler, In. i 1X l\Xx iiXx 2 2 2 2 2 2H VA 3 3 Tank, In. X X X X l l l iX lX \X IX m lX 2 2 Number of Baths or Families i i 1-2 1-2 1-2 2-3 2-3 3-4 4-5 5-6 6-7 7-9 9-11 11-15 15-18 Tank Capacity 30 40 52 66 82 100 120 144 160 200 250 300 400 500 600 Piping Connections Boiler, In. i i i \x IX IX IiXx 2 2 2 2 2X 23 X Tank, In. X X X 1 1 1 1 1 ix ItiXxx 2 2 2X Number of Baths or Families i i i 1-2 2-3 3 4 5 6 6-7 7-9 9-11 11-15 15-18 18-21 756 CHAPTER 44. WATER SUPPLY PIPING AND WATER HEATING water demand can be heated during periods of light demand and stored up for use during the periods of heavy demand. The total water con sumption per person usually varies between 100 and 150 gal per day when laundry and culinary operations for the occupants are carried out on the same premises. The maximum hourly demand under these conditions will be found to be about one-tenth of the average daily consumption. If one-third of the total water used is hot water arid 125 gal per day is assumed as a fair average of consumption per person, it is apparent that each person uses about 40 gal of hot water per day. If one-tenth of this represents the peak hourly load', then 4 gph must be allowed per person for the heaviest demand. If the average occupancy of apartments is 3 persons, the peak hour demand per apartment will be about 12 gph. It is customary to allow 10 gph of heating capacity per apartment. Water in excess of this heating capacity drawn out during the peak hours is Vent II ' 1 + 1 J' 1 | " -<* 11 11 11 I 11?! t Q. 1 3& c3 >> ao.. 3 O9k V) y Vi j. Vi * o. 3 1 ^ 1 *^ 1 1// / oJ ''l? / /rST <o) (e> Fig. 7. Methods of Arranging Hot Water Circulation Lines provided for by storage in the hot water tank where this water is heated during hours when the demand is below the average. In single homes, hot water use averages 20 gal per day pier person. Table 12 gives sug gested storage tank sizes for homes and apartments based on the number of families or baths. HOT WATER HEATERS Various types of heaters are available for supplying the hot water for domestic service in buildings. In any hot water supply system the water should be heated to a temperature between 150 and 180 F. Where the hot water requirements include supplies for kitchens, laundries or process work, the higher temperatures are used. In buildings where steam is available throughout the year, the hot water supply is usually taken from this source. In smaller domestic installations the fuel-burning device is generally automatically arranged so that hot water is supplied the entire year and not merely when the boiler is used for heating purposes. 757