CHAPTER 40
1950 Guide
<ft = 10 logio
(2)
where
I = the sound intensity in watts per square centimeter.
The reference intensity is. 10-16 watts per square centimeter, coinciding with the reference pressure of 0.0002 dynes per sq cm or 2 X 10""4 microbar. A microbar is. the unit of pressure commonly used in acoustics, one.microbar. being equal to one dyne per sq cm.
The relationship of the decibel scale to sound pressure and sound in tensity is shown in Table 1. A stated sound level in decibels, under standardized procedure, will thus be related to a threshold of 0.0002 dynes per square centimeter, or to a threshold of 10-15 watts per sq cm. The standardization upon terminology, procedures and reference levels may be found in Standards1 published by the American Standards Association..
APPARATUS FOR MEASURING SOUND
' The measurement of sound or noise is conventionally made by means of a
sound-level meter2 consisting of a microphone, an amplifier, a variable
attenuator, weighting networks, and an indicating meter which reads
' directly in decibels. The approved sound-level meter must comply with
the: specifications of the American Standard Sound Level Meters for
Measurement of Noise and Other Sounds, Z24 3-1944, approved and
published by the American Standards Association. The meter is designed
to indicate sound level above the standard reference level. Three measur
ing networks are generally provided: (1) flat response, (2) 70 db network
and (3) 40 db network. The various networks are approximations of the
equal-loudness contours relating intensity and frequency sensation response
of the normal human ear.1 Where there are no specific codes which specify
the particular network to be used, general practice would indicate use of
the 40 db network for sound levels up to about 55 db, the 70 db network
for sound levels from about'55 db.to 85 db, and the flat response network
for higher levels. When sound level measurements are stated, the specific
weighting network used, i.e., 40 db, 70 db or flat response, should always
be reported. Complexity in design and calibration, and variations in
component parts; of the sound level meter impose some deviation from
design' objective'response. Allowable , deviations inresponse or accept
able tolerations recognized in the Standard, vary from dfcZdb in the 1000
cycle, range to , 5 db, or more, below 100. cycles and above .1200 cycles
per second. . .
.
v . . .' -..
GENERAL PROBLEM OF SOUND CONTROL
The problem confronting the air conditioning .engineer is to design a system which will . .operate without increasing the noise level in the conchtioned space.., It is therefore necessary:
1.. To determine thelnoise levelexistingwithout.the equipment. ,
...
2. To.ascertain the noise level which would exist if the equipment were installed
without sound control..
:,,.
3. To provide as a part of the installation, sufficient sound control appliances and treatment to reduce the sound level due to the installation to a sound level at least three decibels/ and preferably five decibels; below that1 found in Item-1. .
. To. accomplish, this the engineer should have information of three kinds :
: -. 1; A knowledge of.the noise levels currently'considered acceptable in various rooms, in order that he may have a basis on which to proceed.
Sound Control
845
TABLE 1. DnCIBEI.ScALE VS. SotTND PbESSDKES AND SOUND INTENSITIES
Decibel'1
Pressure
Level
,. dynes per sq cra
Intensity watts-per sq cm-
Decibel Pressure
. Level, ;
> dynes per sq cm-
Intensity
*-
watts-per sq cm*,
0
0.000200
1.000 X 10-"
40 '
0.0200 1.000 X 10-"
1
0.000224
1.259 X 10""
50
0.0631
1.000 X 10-",
2
0.000252
1.585 X 10~"
60
0.200
1.000 X 10-"!
3
0.000282
2.000 X 10-"
70
0.631
i.ooo x ur*
4
0.000317
2.520 X 10-"
80-
2.00
1.000 X 10-
-6
0.000399
4.000 X 10-"
90
6.31
1.000-X 10-'
8
0.000503 - 6.310 X 10-" 100
. 20.0
i:ooo x io-
10
0.000631
1.000 X 10"" 110
63.1
1.000 X 10-*
20
0.00200
1.000 X 10-" 120
200.0
1.000 X 10-f
30
0.00631
1.000 X -io-"
2. A knowledge of the nature and intensity of the noise created by the various
parts of the equipment.
. : :;
'
3. A knowledge of how, when necessary, to vary and control the noise level between the equipment and the conditioned space.
In addition, the engineer should have sufficient information to predict the levels produced by noises which may be transmitted by the duct system from one conditioned .space to another, or from an outside space to the conditioned space: In either case; the designer must know the prob able noise level at the point where the noise originates. From this he can compute the attenuation or transmission loss required in order to bring this level down to that required in the. conditioned space.. If there is likelihood of direct transmission through a duct, the attenuation required may be computed as shown' in section Noise Transmitted Through Ducts. If the transmission is through dividing walls, it will be necessary to refer to published . data on losses through standard building . constructions.'
Information concerning the sound levels created by ventilating and air conditioning equipment such as fans, motors,, air washers and similar items, has not- yet been1'completely! established: \However7':'humerous manufacturers are in a position to supply such- data upon many, of their products.; Additional information .is' being . collected; Uniformity ;in method of test and presentation of sound measurement data for fans, has been standardized in the Sound Measurement Test Code for Centrifugal and Axial Fans, developed by the National Association of Fan Manufac turers. The Code prescribes that the sound level shall be measured by the flat response network of the sound-level meter. Readings on the 40 db and 70 db networks may also be taken and reported, but theflat response reading :is required to comply with the Code requirement. General .prac tice is to use the slow or damped needle reading of the meter. The fast' or undamped needle of the indicating; meter 'generally reads one to two db lower, ithan the slow or damped meter needle. The same Code prescribes a method of determining- the sound level reading at each of seven stations, spaced at 5 ft from the outside of the fah housing,, and located in a hori zontal plane passing through the fan shaft;. The sound level of the fan is. the average of the seven readings. . The level so determined is valuable primarily for-comparative purposes rather than absolute values:; Of more value to the design engineer would be the sound-level at the fan outlet' and at the beginning of the distribution duct system. ..
The technique of sound measurement in.a moving air stream of ap-