Document Vn0VvRKYQ0zg9Eep4Ym49z9q
Monsanto
DIVISION
0 reran ic
INSTRUMENT FUNCTION OUTLINE
w. plant G. Krummrich
8LDG/DEPT
AUTH NO.
811.00
2417
CED LOOP NO.
.
FIC-307-1
.
ISSUED BY
0. J.
REV. BY
Hans'
DATE
PLANT LOOP NO.
7/19/71
DATE
REV
SHEET
OF
3.0 OPERATION
3.1 NORMAL OPERATION
Typical flow control loop.
3.1.1 Startup
3.2 INTERLOCKS
None.
3.3 ABNORMAL OPERATION
_ _
'
3.3.1 Air Failures
' .
.
.
Air failure to the loop will cause the furnace to shutdown.
3,3.2. Power Failure
.
Power- failure to the loop will cause the control valves to close
shutting down the furnace.
.
PCB-ARCH-EXT0374136
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant Wo G. Krummrich
BLDG/DEPT
AUTH NO.
811.00
2417
CED LOOP NO.
FIC-307-1
ISSUED BY
DATE
C. J. Hans' 7/19/71
REV. 8Y
DATE
PLANT LOOP NO.
1REV
SHEET OF
1.0 FURNACE FUEL FLOW CONTROLLER
The fuel flow and thus the furnace firing level serves as the basis
of the column vapor through-put. This is the primary instrument
concerned with .column capacity.
.
1.1.1 Function
The function of this loop is to control the flow of fuel gas or fuel oil to the reboiler furnace. .
1.1.2 System Performance Required
.1.1.3 Accomplishment of Function
...
The fuel gas flow is controlled by measuring the rate of flow in
the line via an orifice plate and differential pressure transmitter.
The D/P transmitter sends'-a 3-15 psig signal to the indicating
controller. The controller compares this signal with a set point
and sends a carving 3-15 psig signal to the fuel- gas control
valvesto compensate for variation from the set point.
When using fuel- oil the measurement is made using an integral orifice. D/P transmitter, a switch on the field panel, selects either fuel gas or fuel oil operation and at the same time selects the D/P transmitter for that service, and either the' fuel gas or fuel oil control valves1. One, two or three burners can be 'used. Each one having its on control valve which can be selected from the field panel.
PCB-ARCH-EXT0374137
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
rLAN I W. G. Krummrich
bldg/dept
811.00
AUTH NO.
2417
CEO LOOP NO.
'
ISSUED BY
C. J.
REV. BY
FTC-349-1 DATE
Hans- 7/19/71
DATE
PLANT LOOP NO.
1REV
SHEET
OF
1.0 NO. 5 ABSORBER FEED FLOW CONTROLLER
This controller regulates the feed rate through and thus the AP across No. 5 absorber to allow the (exist) 538 feed pump to operate within its head-volume capability.
1.1..DESCRIPTION
.
' 1.1.1 Function
'
.
The function of this' loop is to measure arid control the flow by .feed to No. 5 absorber and to provide an alarm on low flow.
1.1.2 System Performance Required
_
113 Accomplishment of Function
The feed flow is controlled by measuring the rate of flow with an integral orifice differential pressure transmitter. The D/P transmitter sends a 3-15 psig signal to the indicating controller. This signal is compared to a set point and the controller sends a varying 3-15 .psig signal to the control valve FV-349-1 to compen sate for variation from the setpoint.
A pressure switch activates an alarm on low flow.
PCB-ARCH-EXT0374138
Monsanto
INSTRUMENT FUNCTION OUTLINE
DIVISION
Orcranic `
w. plant O. Krummrich
BLDG/DEPT
AUTH NO.
'
811.00
2417
CED LOOP NO.
ISSUED BY
C. J. Hans
REV. BY
FIC-349-1
DATE
' 7/19/71
DATE
.
PLANT LOOP NO.
REV
SHEET
OF
3.0 OPERATION
3.1 MANUAL OPERATION
Typical flow loop.
3.2 INTERLOCKS
.
' None.
3.3 ABNORMAL OPERATION
,
'
`
.. .
3.3.1 Air Failures
`
'
Upon air failure to the loop the valve will close and the alarm will sound.
3.3.2 Power Failure
\
Upon power failure the alarm will be inoperative.
PCB-ARCH-EXT0374139
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
W. G. Krummrich
PLANT
. BLDG/DEPT
AUTH NO.
811.00
'2417
CEO LOOP NO.
ISSUED BY
C. J; Hans
REV. BY
PICA 301- 5 7/l9/71 PLANT LOOP NO.
DATE
REV
1 SHEET OF
1.0 COLUMN PRESSURE CONTROLLER
The column head pressure needs to be controlled (40 mm for 1016;
360 mm for "mono") to limit the still pot liquid temperature to a
maximum of 300C at 140 mm. The still pressure is set by the
approximate 100 mm overall column AP for both operation.
.
1.1 DESCRIPTION OF LOOP
,
l-l.l Function
.
! "
.
.The function of this loop is to indicate and control the column's
absolute pressure and active an alarm in the control room on high
pressure.
.
1.1.2 System Performance Required
.
1.1.3 Accomplishment of Function '
.
The column pressure is sensed at the top of the column by an absolute
pressure type pneumatic transmitter. The transmitter sends a 3-15
psig signal to a local indication, a pressure switch in the field
cabinet for the alarm function, and to an indicating controller
mounted on the panel in the control room. The controller compares
the signal with the set point and sends a compensating signal to
'
the control valve. The control valve bleeds air into the vacuum
system.
.
The pressure switch activates an alarm when it senses an abnormally
N high input signal.
PCB-ARCH-EXT0374141
Monsanto
DIVISION
Organic
IMSTRUfilENT FUNCTION OUTLINE
plant w* G' Krummrich
BLDG/OEPT
811.00
AUTH NO.
2417
CEO LOOP NO.
ISSUED BY
C. J. Hans.
REV. BY
PICA 301-5
OATE
PLANT LOOP NO.
7/19/71
DATE
REV
SHEET OF
3.0 OPERATION OF LOOP
'
3.1 NORMAL OPERATION
--
" .'
-
, -.
Same as for a typical pressure loop.
'
'
'
'
-
f
-
.
' .
-
3.2 INTERLOCKS
)
.
.
.
None.
_
3.3 ABNORMAL OPERATIONS
. ;' -
' '
' -'
-
- 3.3.1 Air Failure
'
Upon instrument air failure to- controller, the valve will close, preventing air from being bled into the vacuum system. This would take all control of the vacuum system away from the controller. The vacuum system would lower'the column down to its inherent limits.
3.3.2 Power Failure
'
Upon electrical power failure only the alarm would be inoperative.
PCB-ARCH-EXT0374142
Monsanto
INSTRUMENT FUNCTION OUTLINE
DIVISION
Organic '
plant W. G. Krummrich
BLOG/DEPT
AUTH NO.
811.00
2417
1.0 STILL POT LEVEL CONTROLLER
CEO LOOP NO.
,
LRC-305-3
ISSUED BY
C J . Hans
REV. BY
DATE
PLANT LOOP NO.
7/19/71
DATE
REV
1 SHEET OF
.This instrument serves two needs: a) level recording for 1016A and "mono"; and b) level control of still pot feed during 1016 semi-continuous operation and the chain feed part of the "mono" operation. This instrument allows a volume of crude feed to enter the still equal to the distillate volume drawn off via FIC 303-1.
1.1' DESCRIPTION
-
1.1.1 Function
.
a. To indicate, record the level of liquid in .the still pot.
b. To control the level of liquid during semi-continuous operation.
c. To activate and alarm on high or low liquid level.
.
1.1.2 System Performance Required
.
.
1.1.3 Accomplishment of Function
A displacer type level transmitter senses the level and senses a
3-15 psig signal to the level indicating controller and also to the
recorder. The controller compares this signal with a set point and
send a 3-15 psig signal to control valve FV-305-3 to compensate for
variations from the set point.
.
Two pressure switches mounted in the field cabinet also receive this
. signal and sound`an alarm in the control room upon high or low
' level.
PCB-ARCH-EXT0374143
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant W. G. Krummrich
BLDG/DEPT
AUTH NO.
811.00
2417
CED LOOP NO.
LRC-305-3
ISSUED BY
DATE
PLANT LOOP NO.
C. J. Hans . 7/19/71
REV. BY
DATE
rev
sheet
0?
3.0 OPERATION
Typical flow loop.
'
.
3.2 INTERLOCKS
.
'
-----None.
' -
. *. ............... ...
'
'
;
3.3 ABNORMAL OPERATIONS
=' . '
.
.
3.3.1 Air Failure
Upon air failure to the loop the valve will close and the alarm will
sound.
'
3.3.2 Power Failure
Upon power failure the alarm will be inoperative.
PCB-ARCH-EXT0374144
Monsanto
DIVISION
Organic
INSTRUfrlENT FUNCTION OUTLINE
plant w* G* Krummrich
BLDG/DEPT
811.00
AUTH NO.
2417
CEO LOOP NO.
,
1 FTC--349- ________________________
ISSUED BY
DATE
PLANT LOOP NO.
C. J. 'Hans- 7/19/71
REV. BY
DATE
1REV
SHEET OF
1.0 NO. 5 ABSORBER FEED FLOW CONTROLLER
.
This controller regulates the feed rate through and thus the AP
across No. 5 absorber to allow the (exist) 538 feed pump to
operate within its head-volume capability.
1.1,.DESCRIPTION
.
.
l-l-l Function
The function of this loop is to measure and control the flow by .feed to No. 5 absorber and to provide an alarm on low flow.
1.1.2 System Performance Required
_
1.1.3 Accomplishment of Function
The feed flow is controlled by measuring the rate of flow with an integral orifice differential pressure transmitter. The d/P transmitter sends a 3-15 psig signal to the indicating controller. This signal 'is compared to a set point and the controller sends a varying 3-15 psig signal to the control valve FV-349-1 to compen' sate for variation from the setpoint.
A pressure switch activates an alarm on low flow.
PCB-ARCH-EXT0374145
Monsanto
INSTRUMENT FUNCTION OUTLINE
DIVISION
Organic
w. plant 0. Krummrich
BLDG/DEPT
- AUTK NO.
811.00
2417
3.0 OPERATION
CED LOOP NO.
FIC-349-1 .
ISSUED BY
DATE
C. J. Hans ' 7/19/71
REV. BY
DATE
PLANT LOOP NO.
REV
SHEET
CF
3.1 MANUAL OPERATION
;
-
Typical flow loop.
_3.2. INTERLOCKS
.
' None.
3.3 ABNORMAL OPERATION
3.3.1 Air Failures
Upon air failure to the loop the valve will close and the alarm
will sound.
3.3.2 Power Failure
\
.. Upon power failure the alarm will be inoperative.
PCB-ARCH-EXT0374146
Monsanto
INSTRUMENT FUNCTION OUTLINE
DIVISION ,
Organic
W. plant G. Krummrich
BLDG/OEPT
AUTH NO.
246
2417
1.0 COLUMN TOP-PRODUCT DIVERTOR .
CED LOOP NO.
XCV 303-1 &.-XGrV^30.3r 25
ISSUED BY
DATE
PLANT LOOP NO.
C. ,T. Wan s 7/19/71
REV. BY
DATE
REV
SHEET
1 1 O'1
These valves are needed to divert top product from the column (Item 301) to various locations depending on the product specifications
1.1 DESCRIPTION OF LOOP
.
L. 1.1 Function
These valves enable the operator, at his discretion, to divert all
product flow either to the MCS 1016 product receiver (Item 542,
.
.#4 product tank), to the light ends receiver (Item 328) or back
to the column (Item 301).
1.1.2 System Performance Required
.
1.1.3 Accomplishment of Function .
. \
Placing panel switch SS-5 in the "light ends" position opens valve
.. XCV 303-2 and closes XCV 303-1.
'
.
All column top product then flows to the light ends receiver (item
328). Placing the switch in the "closed" position closes XCV 303-1
and XCV 303-2 and diverts all top product, as reflux, back to the
column (Item 301). Placing the switch in the "product" position
opens XCV' 303-1 and closes XCV 303-2. This diverts all product
to the #4 product tank (Item' 542).
PCB-ARCH-EXT0374147
Monsanto
DIVISION
\.:.J Organic
INSTRUMENT FUNCTION OUTLINE
W. plant G. Krummrich
BLDG/DEPT
AUTH NO.
246
2417
CED LOOP NO.
.
XCV 303-1 &
ISSUED BY
DATE
PLANT LOOP NO.
C. J. Hans ` 7/19/71
REV. BY
DATE
1REV
SHEET
2 OF
3.0 OPERATION OF LOOP
3.1 NORMAL OPERATION
'
.' '
'
; Typical.
3.2- INTERLOCKS
.
.
None.
..
`
.
.
'
3.3 ABNORMAL OPERATION "
'
"
3.3.1 Air Failure
Air failure to the valves will-cause both valves to close which puts column on total reflux.
3.3.2 Power Failure
\
.
Same as air failure.
.
PCB-ARCH-EXT0374148