CHAPTER 20
1954 Guide
Table 3. Capacity Tables tor Warm Air and Return Air Branches*- b
FIRST STORY
For UNINSUL
ATED Metal Ducts
Actual Length (fbom Bonnet to boot! ok, u-kum Return Plenum to Boot) in I LET
1 to 7 ST.
Col. a
8 to 12 ST.
13 to 17 18 TO 24 ST. ST.
25 to 34 35 TO 44 ST.
45 TO 54 ST.
Col. e Col. c Col. d Col. e Col. e Col. g
Wabm Atw
Combi
nation
No.
Return Aib ; :
Combi- -
nation No.
Section A.
40 to 69 Equivalent Ft for Fittings and Register
7200 12500 16000 19100
25000 32000 80000
6700 11700 15000 18000
23400 30000 75000
6100 10800 14000 17000
21600 28000 70000
5600 9900 13000 16000
19800 26000 65000
4800 8500 11300 14200
17000 22600 56500
4100 7400 9900 12500
14800 19800 49500
3500 6400 8700 11000
12800 17400 43500
41 42 43 44
45* 46*
51 52 53 54
55 56 57*
Section B.
70 to 99 Equivalent Feet
5500 9900 13100 16300
19800 26200 65500
5100 9200 12300 15400
18400 24600 61500
4800 8600 11600 14500
17200 23200 58000
4500 8100 10900 13700
16200 21800 54500
3900 7100 9700 12200
14200 19400 48500
3400 6200 8500 10800
12400 17000 42500
3000 5400 7500 9500
10800 15000 37500
41 42 43 44
45* 46*
51 52 53 54
55 56 57*
Section C.
100 to 129 Equivalent Feet
4600 8500 11300 14300
17000 22600 56200
4300 7900 10600 13500
15800 21200 52600
4100 7400 10000 12700
14800 20000 50200
3800 6900 9400 11900
13800 18800 47300
3300 6100 8400 10500
12200 16800 42000
3000 5300 7400 9300
10600 14800 37000
2700 4700 6500 8300
-9400 13000 32400
41 42 43 44
45* 46*
51 52 53 54
55 56' 57*
Section D. 130 to 164
Equivalent Feet
Section E. 165 to 200
Equivalent Feet
4100 7300 9800 12300
14600 19600 49200
3800 6500 8800 11000
13000 17600 44100
3800 6900 9100 11700
13800 18200 45800
3500 6100 8200 10500
12200 16400 41500
3600 6400 8600 11000
12800 17200 41900
3300 5700 7700 9900
11400 15400 38800
3400 6000 8100 10300
12000 16200 40300
3100 5400 7200 9300
10800 14400 36000
2900 5300 7200 9100
10600 14400 36000
2700 4800 6400 8300
9600 12800 32000
2600 4700 6400 8100
9600 12800 3X800
2400 4300 5700 7300
8600 11400 28200
2300 4200 5600 7100
8400 11200 28100
2100 3800 5000 6400
7600 10000 24700
41 42 43 44
45* 46*
41 42 43 44
45* 46*
51 52 53 54
55 56 57*
51 52 53 54
55 56 57*
For INSULATED
Ducts
Col. a 1 to 9
Col. b
10 to 17 FT.
Col. c
18 to 24 FT.
25 TO 34 FT.
Col. e
35 to 64 ft.
For Ducts that abb COM PLETELY INSULATED
with i In. Thick Insul ation from Bonnet to Boot,. USE THESE CoLVUX HEADINGS.
* These tables are for use in sizing both the warm air and the return air branches.
,
b Frictional resistances and temperature drops in ducts have both been accounted for in these tables*
c Use these items only when the building construction, or capacity requirements, necessitate the
two adjoining stacks or door registers.
Forced Warm Air Systems
469
Table 4. Capacity Tables for Warm Air and Return Air Branches*- *>
SECOND STORY
Fob
UNINSU LATED Metal Ducts
Aw oah Length (fbom Bonnet to Boot) or, (from Return Plenum to Boot) in Feet
1 to 7 FT.
8 TO 12 FT.
13 to r FT.
18 TO 24 FT.
25 to 3 FT.
35 to s FT.
45 to & FT.
Col. a Col. b Col, c Col. d Col. e COL.F Col. o
Section A.
40 to 69 Equivalent Ft for Fittings
and Register
6300 10900 14000 17000
21800 28000 70000
5700 10000 13000 15900
20000 26000 65000
5200 9200 12100 14900
18400 24200 60500
4800 8500 11400 13900
17000 22400 57000
4100 7300 10000 12400
14600 20000 50000
3500 6400 8800 11100
3100 5600 7800 9900
12800 11200 17600 . 15600 44000 39000
Section B.
70 tu99 Equivalent Feet
5000 9000 11900 14800
4600
8200 11000 13900
18000 -16400 23900 22000 59500 55000
4300 7600 10300 13000
15200 20600 51500
4000 7100 9600 12200
14200 19200 48000
3400 6200 8400 10800
12400 16800 42000
3000 5400 7500 9600
2700 4700 6700 8500
10800. 9400 15000 13400 37500 33500
Section C.
100 to 129 Equivalent Feet
4200 7700 10400 13000
15400 21700 52200
3900 7200 9700 12100
14400 19400 48400
.3700 6700 9000 .11300
13400 18000 45300
3500 6200 8400 10600
12400 16800 42300
3000 5400 7400 9400
10800 14800 37000
2600 4700 6500 8300
9400 13000 32500
2400 4100 5800 7400
8200 11600 29000
Section D. 130 to 164
Equivalent Feet
Section E. 165 to 200
Equivalent Feet
3800 6800 9100 11400
13600 18200 45500
3500 6100 8200 10300
3500 6300 8400 10500
12600 16800 42000
3200 5700 7600 9500
3200 5800 7900 9800
11600 15800 39600
2900 5300 7100 8900
3000 5500 7400 9200
11000 14800 36800
2700 5000 6700 8300
2700 4800 6300 8100
960) 12600 32200
2500 4400 5700 7400
2300 4200 5700 7200
8400 11400 28200
2100 3900 5100 6500
2100 3700 5000 6400
7400 10800 25100
1900* 3400 4500 5800
12200 16400 41000
11400 15200 38300
10600
14200 35800
10000
13400 33400
8800
11400 29000
7800 10200 25800
6800 9000 22800
Warm Air
Combi
nation
41 42 43 44
45* 46*
41 42 43 44
45* 46*
41 ' 42 43 44
45" 46'
41 42 43 44
45* 46*
41 42 43 44
45* 46'
Retuhn Aib
Combi nation
No.
51 52 53 54
55 56 57*
51 52 53 54
55 56 57*
51 52 53 54
55 56 57*
51 52 53 54
55 56 57*
51 52 53 54
55 56 57*
Fob tNSULATED
Ducts
Col. a 1 to 8
Col. b
9 to 14 FT.
Col. c
15 to 20 FT.
Col. d
21 to 27 FT.
Col. e
28 to 42 FT.
Col. f Fob Ducts that are COM PLETELY INSULATED
43 to 54 WITH $ IN. THICK INSULATI ON FT. from Bonnet to Boot Use these Column Headings.
k -- bcpac ore ior use m sizing both the warm air and the return air branches. c frictional resistance and temperature drops in ducts have both been accounted for in these tables. twn .these items only when the* building construction, or capacity requirements, necessitate the use of 0 adjoining stacks or floor registers.