Flammable and Combustible Liquids
FlC 34-6 -- Bonding and grounding ol a flammable liquid tank truck and loading rack
a flammable liquid tank truck and loading rack
In areas where flammable liquids are stored or used, hose nozzles on steam lines used for cleaning should be bonded to the surface of the vessel or object being cleaned
Moving belts are sources of static electricity unless they are made of a conductive material or are coated with a conductive belt-dressing compound designed to prevent static charges from being built up
Nonconductive materials, such as fabric, rubber, or plastic sheeting passing through or over rolls will also create charges of static electncitv Static from these materials as well as from the belts can be discharged with grounded metal combs or tinsel collectors Radioactive substances and static neutralizers using electrical discharges are also employed for this purpose
Bonding and grounding systems should be checked regularly for good order, especially electrically Preferably before each fill, the
exposed part of the bonding and grounding system should be inspected for parts which have deteriorated because of corrosion or have otherwise been damaged Many com panies specify that bonds and grounds be con structed of bare braided flexible wire because it facilitates inspection and prevents broken wires from being concealed, as discussed earlier
Electncal equipment
Electricity becomes a source of ignition where flammable vapors exist if the proper tvpe of electrical equipment for these atmos pheres either has not been installed or has not been maintained The NFPA Standards and their National Electrical Code should be consulted m al! cases
Spark-resistant tools
Although the hazard of ignition of flamma ble vapors or gases by sparks may at times be overemphasized, it must be recognized