Document VdnzQZ2y8Y9gZgem11L87brq
ABD00110033
VCM Tankfarm HAZOP
Critical Rank:
4 , Marginal Risk II = High Consequence C = Possible Occurrence
Deviation : High Temperature or Pressure
Equipment Number: DM-061
Equipment Description: Sphere vapor line knock-out pot.
Cause: 1. External Heat 2 . Blocked or plugged line during recovery. 3 . Closed or blocked valve during recovery.
Consequence:
1. Fire/Explosion. 2. Lift relief valve. 3. Rupture line. 4. Lift relief valve on DM-061. 5. VCM release.
Suggested Mitigation: Install deluge over DM-061. Tie into new deluge line.
Resolution:
Comments:
12