/ September 23, 1970
* TO: R. L. Asher/Zone-Boca Raton (P) R. E. Dunham/Zono-Miimeapolis Office W. G. Gray/Zono-Dearborn L. P. Hollis/Zono-High Point J. A. McEachem/Zono-St. Louis C. R. Lowe/Zono-Atlanta (V) C. H. Wendel/Zono-Los Angeles Office
WRG 000364
K. W. Harrison R. W. Sterrett B. R. Williams J. N. Beveridge
Gentlemen:
-*
On Friday, September 18, we tested a blend floor deck and beam assembly protected with MK-4, non-asbestos fireproofing. The deck reached limiting temperature at two hours two minutes (122 minutes) but had drop off on the flat plate sections. The test ran for four hours, and the beam tem peratures appeared equal to or better than MK-3. This is encouraging, but we must wait for the UL engineers to complete the study of test data.
I recommend and urge a restrained attitude on our part. We will not have total equivalency from this test, but we may have enough to satisfy particular air pollution and code officials for particular projects
Our research team is continuing their efforts for the best product that will get total UL equivalency.
I will be in touch on or about October 1, to clarify our position, UL ratings, pricing and other pertinent data.
TFE/jac
Thomas F. Egan
25052981
rON'ST1*1^*mamscts wrr^ioN
CONFIDENTIAL
September 23, 1970
TO: R. L. Asher/Zono-Boca Raton (P) R. EJ Dunham/Zono-Minneapolis Office Vi. G. Gray/Zono-Dearborn L. P. Hollis/Zono-High Point ,j. A. McEachem/ZOno-St. Louis C. R. Lowe/Zono-Atlanta (V) C. H. Viendel/Zono-Los Angeles Office
T. F. E;
c"--lir'AT^Vining K. VI. Harrison R. W.. Sterrett
B. R. Williams J. N. Beveridge
v-
Gentlemen:
*
On Friday, September 18, we tested a blend floor deck and beam assembly protected with MK-4, non-asbestos fireproofing. The deck readied limiting temperature at two hours two minutes (122 minutes) but had drop off on the flat plate sections. The test ran for four hours, and the b&p tem peratures appeared equal to or better than MK-3. This is enrouraging, but we must wait for the UL engineers to complete the study of test data.
I recommend and urge a restrained attitude on our part. We will not have total equivalency from this test, but we may have enough to satisfy
Our research team is continuing their efforts for the best product that Will get total UL equivalency.
I will be in touch on or about October 1, to clarify our position, UL ratings, pricing and other pertinent data.
TFE/jac
Thomas F. Egan