American Society of Heating and Ventilating Engineers Guide, 1930
Table 1. Commercial Standard Fuel Oil Specifications A. Detailed Requirements for Domestic Fuel Oils
Grade of Oil
Approx. B.t.u. per Gal.
Flash Point, Min. Max.
Water AND
Sediment, Maximum
a Pour Point, Maximum
Distillation Test
Viscosity Maximum
No. 1 Light Domestic
Fuel Oil A light distillate
oil for use in burners requir ing a high grade fuel.
139,000 110F 165F or legal
0.05%
15F
10% point, End point, maximum maximum
420 F
600F
No. 2 Medium Domestic
Fuel Oil A medium distil
late oil for use in burners re quiring a high grade fuel.
141.000
125F 190 F or legal
0.05%
15F
10% point, 90% point, maximum maximum
440F
` 620F
No. 3 Heavy Domestic
Fuel Oil A distillate fuel
oil for use in burners where a low viscosity oil is required.
143.400 150F 200F or legal
0.1%
15F
10% point, 90% point, Saybolt
maximum maximum Universal
at 100F
460F
675F 55 seconds
aLower or higher pour points may be specified whenever required by conditions of storage and use. However, these specifications shall not require' a pour point less than 0 deg. fahr. under any conditions.
B. Detailed Requirements for Industrial Fuel Oils
Grade of Oil
Approx. B.t.u.
per Gal.
Flash Point, Min. Max.
Water and
Sediment, Maximum
Pour Point, Maximum
Viscosity, Maximum
No. 4. Light Industrial Fuel Oil
An oil known to the trade as a light fuel oil for use in burners where a low vis cosity industrial fuel oil is required.
144,500
150F. See Note b
1.0%
See Note c
Saybolt Universal at 100F
125 seconds
No. 5 Medium Industrial Fuel Oil
Same as Federal Specifications Board Specification for Bunker Oil "B" for burners adapted to the use of indus trial fuel oil of medium viscosity.
146,000
150F
1.0%
Saybolt Furol
at 122F 100 seconds
No. 6 Heavy Industrial Fuel Oil
Same as Federal Specifications Board 150,000 Specification for Bunker Oil "C" for burners adapted to oil of high viscosity.
150F
Water sediment
1.75% . 0.25%
Saybolt Furol
at 122F
300 seconds
bWhenever required, as for example in burners with automatic ignition, a maximum flash point may be specified. However, these specifications shall not require a flash point less than 250 deg. fahr. under any conditions.
cpour point may be specified whenever required by conditions of storage and use. However, these specifications shall not require a pour point less than 15 deg. fahr. under any conditions.
232
Chapter 12--Heating by Oil
will depend entirely upon the individual installation, but it is reasonable to assume an increase in efficiency of 10 to 15 per cent over coal.
The chart (Fig. 2) can be used for estimating the cost per 1,000,000 B.t.u. for various heat contents per gallon (see Fig. 1), and costs per gallon and is based on an overall efficiency of 60 per cent. The cost in