558 CHAPTER 30 1965 Guide And Data Book Blank-off Baffles. Blank-offbaffles are used for minor adjust ments of the air flow from a diffuser. These baffles blank off a sector of the diffuser, and prevent the supply-air.from striking an obstruction such as a column or partition or the wall of the conditioned space. * -V, . Blank-off baffles should be used only if absolutely neces sary. By blanking off the ares of the diffuser/ baffles, reduce the area and increase velocity of supply air. This must be taken into account when selecting diffuser.size.- ' ' Anti-ernudgerings are round or square-metal, frames, at tached to and extending.4,to -12 in. beyond the .outer edge, of the diffuser. Their purpose' is to-provent, or at least alleviate, ceiling smudging. A light-proof grille is used to transfer air to or from dark rooms. The tors of this type of grille form a labyrinth, and are jointed black. The bars may take-the form of several sets of V-bars, or they may be of some special interlocking louver design to provide the required labyrinth. Stamped grilles are also frequently used as return and exhaust intakes, particularly in rest rooms and utility areaal They are relatively inexpensive. Ceiling and Slot Diffusers. Ceiling and slot diffusers may also. be. used as return and exhaust intakes, .although their cost frequently-prevents such application. See manufacturers7 catalogs for performance-data. Applications , Special Construction Features Ceiling diffusers .are made.of steel or aluminum. A great variety of finishes, such as paint, enamel,. lacquer, electro plated and anodised, and polished, finishes are U3ed.in their manufacture. In general, the configuration of ceiling diffusers does not fend itself-to satisfactory,polishing operations. Modifications far Ceiling Systems. Because of. the large variety of ceiling suspension systems' which have come into common use in the past few years, many modifications of square and rectangular diffusers,are available which.meet contemporary architectural concepts. When diffuser size does not conform to tile increments, filler panels are available which do conform to tile sizes. Special adaptations are avail able for snap-in T-bar, lay-on T-bar, splined, t and radiant ceiling constructions. RETURN AND EXHAUST AIR INTAKES ; Return air intakes may be connected to a duct, or they may be simple vents which transfer sir from one- area to another. Exhaust air intakes remove air directly from a.building and, therefore, are always connected to a duct. Whatever the ar rangement, intake size and configuration determine velocity and pressure requirements for therequired air flow. See section Return and Exhaust Intakes in Chapter 29, for further dis cussion of these factors and of the effect of the location of the intake on the system. In general, the same type of equipment, grilles and registers, dot diffusers and ceiling diffusers which is' used for supplying air, may be used for air return and exhaust. Intakes do not require the deflection, flow equalizing, and turning devices which are necessary for supply outlets. Dampers, however, are necessary when it is desirable to balance the air flow in the return duct system. Return and exhaust intakes may be mounted'in practically any location: in ceilings, high or low in side wails, in floors and in doors. See section Return and Exhaust Intakes in Chapter 29 for their selection and location. i Accessory Devices * Dampers. The dampers shown in Fig. I are used in`conned tion with grille and register return and exhaust intakes. The damper type does not affect the performance of the intake. No other accessory devices are required. 'V EQUIPMENT. FOR ALL-AIR HIGHPRESSURE SYSTEMS . . . . In all-sir high-velocity, high-pressure air distribution sys^ terns the duct velocities-and static pressures are such that special control and acoustic equipment is required for proper introduction of the conditioned air into the space to be served! This chapter deals with control equipment for single-duct . and dual-duct air-conditioning systems; refer to Chapter 31' Air Duct Design, for design of high-vclocity ducts; and duct construction details. Relevant material on-sound control in air-conditioning systems, and sound rating methods for air outlets, will be found in Chapter 14, Sound ControL TYPES OF EQUIPMENT . Control equipment for all-air high-pressure systems may be classified as follows: (1) pressure reducing valves; (2) single-; duct terminal units; (3) dual-duct terminal units; and (4) high-capacity dual-duct units. They provide all or some'of these functions: pressure reduction, volume control; temperature modulation, air mixing, and soundattenuatioii.' Pressure-Reducing Valves GRILLES AND REGISTERS Adjustable bar grilles. The same grilles as used for air sup ply are used, particularly when it is desirable to match the de flection setting of the bars with that of .toe supply outlets. Fixed bar grilles. The same grilles as described in section Grille Outlets, are used. This grille type is the most common return air intake. Vanes are straight or set at a certain angle, the latter being preferred when appearance is important. The so-called V-Bar grille, with tors in the shape ofinverted vees stacked within the grille frame, has the advantage of being sight-proof. It can be viewed from any angle without detracting from its appearance. Door grilles are usually V-Bar grilles. The capacity of. the grille decreases with in creased sight tightness. .\ : Pressure-reducing or air valves consist of a series of gang- operated vane sections mounted within a rigid casing, and gasketed to reduce air leakage between valve and duct as much as possible. They are usually installed in rectangular ducts between a high-ptesure trunk duct and a low-pressure branch duct for manual, remote manual, pneumatic, or elec tric oontroL The amplest arrangement uses a pressure-reduc ing valve behind each sidewall diffuser. Pressure reduction is effected by partial closing o! the valve, and results in high-pressure drop through the valve. This action generates noise, which must be attenuated in the low-pressure discharge duct. The length of duct lining' depends upon toe amount of noise to be attenuated, and the frequency of the noise source which determine the efficiency of a given length of sound lining. Volume control is obtained by adjustment of the valve. Ait-Diffvsing. Equipment - ' ; - 559 'ther manually or. by a' pneumatic or electric control motor Actuated by a static pressure regulator or a thermostat.. p^jure-rcducing'valyes'we generally equal in size. to.toe low-pressure branch'; duct connected, to'the valve, discharge* This arrangement provides minimum pressure drop: with valves fully opened. Also;- with valves fully closed, there is little air leakage, even with high inlet static pressures. . Single-Duct Terminal Units The term high-pressure unit;awnmonly implies a unit with integrated Kiund.cbamber'to reduce, the npi9, generated in the u"fo- The.singlwiuct terminalunit generally, consists of a pressure^velocity- reducing- air valve-and a sound-attenuation chamber fined with heat and sound insulating material/ and equipped with baffles for sound reduction. Special sound attenuation in the air discharge ducts is generally not required with units of this type. Hie pressure-velocity reducing air valve or Hampering device of these units can be adjusted either manually or by means of a pneumatic or electric motor, actuated by a thermostat or volume regulator, depending upon the desired function of the unit. Well-designed valves or dampers should close tightly with less than 2 percent leak age of the design volume of toe unit at static pressures up to 8 in. wg. The minimum static pressure of the unit, with the dfimppr or valve wide open, should be less than 1 in. wg at rated unit volume. The unit casing should be nearly airtight for unit static pressures up to 1 in. wg. Air may be discharged through a single rectangular opening suitable for low-pressure rigid branch duct connection, or through a supply outlet connected directly to the unit. Sev eral outlets may be connected to the unit by means of flexible ducts. Dual-Duct Terminal Units The construction of this type of unit is essentially the same,, as that of the single-duct high-pressure unit, but these-unite have two pressure-velocity reducing air valves. The unite under control of toe room thermostat draw warm and cold air from warm- and cold-air supply ducts in accordance with the room requirements to obtain individual room control without zoning. When individual modulating dampers are used to regulate the amount of warm and cold air, it is common practice to vary the size of the damper opening to effect both pressure reduction and volume control with the same damper. When a single modulating damper is used to regulate the amount of both warm and cold air, a pressure-reducing damper is needed in the unit to reduce pressure and limit air flow. Well-designed modulating dampers should close tightly to limit leakage through the closed duct to less than 2 percent of the unit volume at static pressures up to 8 in. wg. The unit casing should be nearly airtight for unit static pressures up to 1.0 in. wg. Rapid mixing of warm and cold air in the unit is achieved by suitable construction of air baffle arrangement. A mixedair discharge with less than l F deg stratification for each 10 F deg inlet temperature difference between the air streams m tiie two ducts is desirable. Noise generated in the unite is generally attenuated by the sound absorption material and the sound baffles within the unit itself. Special sound treatment of the low-pressure dis charge duct should not generally be necessary. Air may be discharged through a single rectangular opening suitable for low-pressure rigid branch duct connection, or through a supply outlet connected directly to the unit. Several outlets may be connected to the unit by means of flexible ducts. Constant-Volume Gjnfrof The use of terminal unite incorporatmg-'a means of main taining constant- vohitne flow is increasing. The constant volume function .maty be. obtained- by means of a.mechanical rolume;cpni^deyip^itontjuned^witoin the unit whieh. is actu ated by static pressure in the primary duct system without an outside source of; power, or by a pneumatic volume regulator and selector devices whiph are actuated by outeide pneumatic pressure and,an intemaIcilibration pressure:drop. Static Pressure Control. - -. To prevent static pressure'unbalance in single-duct and dual-duct* highrpressure systems,' some control off static pres^ sure is necessary in systems operating with variable air flow. In single-duct systems, variations in static pressure can be limited by: (1) static-pressure controllers, operating dampers in the air-distribution system, (2) static-pressure controllers, operating inlet vane dampers on the fan, and (3) by zoning and changing air supply temperature in response to staticpressure changes. In dual-duct systems, the following methods of controlling static pressure are used: (1) by dampers operated by staticpressure regulators located at critical points in the air dis tribution system, (2) by static-pressure controllers, regulating warm and cold air temperatures in order to limit the variations in the air flow in individual ducts, and (3) by constant-volume regulators in each individual air-mixing valve or acoustic terminal device. High-Capacity Dual-Duct Units In high-capacity dual-duct unite, the functions of pressure reduction, volume control, temperature modulation, air mix ing, and sound control are achieved in connection with the use of a linp-d low-pressure duct. High-capacity unite have large pressure-velocity reducing air valves for warm and cold air operated by pneumatic or electric control motors. When a single modulating damper is used on both ducts, an additional control valve for pressure reduction and constant volume control is required; individual modulating dampers on both ducts effect temperature modulation, pressure reduction and constant volume control. Well-designed dampers should be capable of minimizing leakage in the closed duct; the unit caring should be essentially leak-proof. Air mixing is generally started in the high-capacity unit, but the mixing action continues in the fow-pressure distribu tion duct for a distance of 5 to 15 ft before the first outlet. A mired-air discharge with less than 1 F deg stratification for each 10 F deg inlet temperature difference between the air streams in the two ducts is desirable. - Sound attenuation is provided by insulating the low-pres sure duct connected to toe discharge end of the high-capacity unit on the inside. The length of duct lining depends upon the amount of noise to be attenuated, and the frequency of the noise source which determine the efficiency of a given length of sound lining. The duct lining attenuates the noise gener ated in toe high-capacity unit, which generally feeds two or more supply outlets, so that the recommended length of duct lining should be installed before the first outlet connection. BIBLIOGRAPHY Alfred Koestel, Philip Hermann, and G. L. Tuve: ASHVE Research Repobt No. 1404--Comparative study of ventilating jets from various types of outlets (ASHVE Transactions, Vol. 56, 1950, p. 459). D. W. Nelson and D. J. Stewart: ASHVE Research Report