Document VJD36614gNkb0a88z4Z7Mx9Kq
COLUMBIA ACOUSTICS mi FIREPROOFING Campanxj-
(CANADA) Limited ^ Montreal, Canada
Exclusive Canadian Distributors
E. T. SAMPSON and COMPANY
Limited
Aonfreat HU 1-0183
Toronto HU 7-2141
1960
54
CAFCO* BLAZE-SHIELD, designed for fireproofing beams, girders, columns, decks and ceilings, is a scien tifically proportioned blend of virgin asbestos fibers, refined white mineral fibers, and 100% inorganic bind ers. Mechanically applied with patented, CAFCOdesigned equipment, it forms a lightweight,' fissured, continuous blanket without seams, joints or cracks.
APPLICATION
CAFCO BLAZE-SHIELD is applied direct to most types of clean surfaces without the use of supplementary bases, such as metal lath, for mechanical key. Upon job application of CAFCO ADHESIVE to the base surface, ONE application of BLAZESHIELD by ONE trade In ONE coat, followed by light tamp ing results is a tightly bonded, compressible coating.
ADVANTAGES
CAFCO BLAZE-SHIELD offers the architect, engineer and contractor these major advantages--
labor savings Specially designed equipment provides maxi
mum production from a small rolling scaffold. An experienced crew can apply up to 7,000 board feet per machine-day.
material savings In many cases savings can be effected
through elimination of clips, hangers, rods, channels, spacers, and kith.
weight savings CAFCO BLAZE-SHIELD applied 1' thick
to cellular deck weighs less than 1 pound-pc -square foot. It is lighter than 'lightweight** fireproofing materials.
Spoce savings Direct application to structural elements
reduces the volume of normally wasted space.
permanence Permanence of protection is assured because
inorganic BLAZE-SHIELD is rot-proof, vermin-proof, and rust-proof. Normal structural movement is absorbed without surface cracking and spalling.
Clean application Patented, CAFCO-designed equipment
incorporating a special Dust Control system permits other trades to work during fireproofing application.
high tight reflection BLAZE-SHIELD has a higher light
reflection than wet mix plasters. In many cases, the fireproofing medium may be used as the reflective surface above luminous ceilings.
high OCOUSflCof absorpf/on When tested by Hiverbank
Laboratories, CAFCO BLAZE-SHIELD applied direct to deck and beams for three hour retardancy provided an NBC of .90. The fireproofing fiber can replace the sound absorbent pad in perforated metal pan systems or may be used as a finished acoustical ceiling.
high thermat insulation A K-factor of .26 allows ef
fective insulation of spandrel members and roof undersides.
Winter app/iccf/on With simple precautions, application
is possible onder many temperature conditions which delay the use of other fireproofing materials. Schedules are main tained; job heating costs are reduced.
corrosion preventive CAFCO ADHESIVE applied di
rectly to steel leaves no space in which corrosion can take place. Job prime coating may often be eliminated.
T.M. Beg. U.S. Pat. Off.
Union Carbide Building New York City Architects Skidmore, Owing* ond Merrill General Contractor: George A. Fuller Company
The IX million square foot cellular steel floor system on this 52 story skyscraper is protected for S hour fire retardancy by CAFCO BLAZE-SHIELD.
fire tests prove efficiency
CAFCO BLAZE-SHIELD is a highly efficient fireproofing mate rial, tested and proved by Underwriters' Laboratories Inc. and Factory Mutual Engineering Division and accepted by Build ing Departments. Test data are filed with Insurance Rating Bureaus throughout the United States and Canada. Data on the facing page show fire test results.
cafco test facilities
Columbia Acoustics and Fireproofing Company maintains a test furnace for evaluating CAFCO BLAZE-SHIELD applied to existing and new construction systems. (lew uses and systems are constantly under study. Test results can be correlated with those obtained at Underwriters* Laboratories, Inc.
cafco engineering service An engineering and service staff is available to assist the build ing industry. Years of research and development have estab lished an enviable reputation which is reflected in every appli.cation of CAFCO products.
FIRE RETARDANT RATINGS
FLOORS and CEILINGS
description
CAFCO
rating thickness
J. authority
2*4" Carter***
\CAFCO
CAFCO applied directly to cellular steel floor units.
2 hrs. 3 hrs. 4 hrs.
% EXTR. BMS-92 V U.L TEST #CR193-2
1* EXTR. BMS-92
2*4" Concrete
1
xTTTZT
JL CAFCO applied directly to cellular
steel floor units. "ivi"
2 hrs. 3 hrs. 4 hrs.
CAFCO
,2*4" Concrete
SEAMS
` CAFCO
JL CAFCO opplied directly to fluted
steel floor units.
}W`
2 hrs. 3 hrs. 4 hrs.
CAFCO applied directly to beam.
1 hr. 2 hrs. 3 hrs. 4 hrs.
CAFCO
Vi" U.L TEST #CR193-3 Hi" U.L TEST #R3749-3
EXTR. BMS-92
EXTR. BMS-92 U.L TEST#R3749-3 1" EXTR. BMS-92
H"
IV' 2%"
EXTR. BMS-92 U.L TEST #CR193-3 U.L TEST #CR 193-2 U.L TEST dR3749-3
CAFCO
COLUMNS
6 go. llo-wiro 24" ox.
CAFCO applied to contact wrap ped beam.
H" rib loth 3.4*
1 hr. 2 hrs. 3 hrs. 4 hrs.
CAFCO
CAFCO applied directly to column surfaces above hung ceiling.
2 hrs. 3 hrs. 4 hrs. 5 hrs.
note: Toil* conducted in accordance with ASTM -119. Extrapolation! bod on formula* contained in Notional Bureau of Standord! teport SMS-92.
%" ly*"
i %"
EXTR. BMS-92 EXTR. BMS-92 EXTR. BMS-92 U.L. TEST df R3749-3
IV'
2%"
2%"
U.L TEST #CR 193-3 U.L TEST #CR 193-2
U.L. TEST #R3749-3 U.L TEST if R3749-4
3-HOUR ACOUSTICAL CEILING
description
open i*b jarg! ZC +t.
JH'&**** CenMtre**)ten*
authority
Informotion
A rated acoustical system providing 3-hour protection to openweb ioists. CAFCO SOUND-SHIELD, applied S" thick to gyp sum lath, provides an NRC of .60 and. reduces sound transmis sion over ceiling high partition systems.
Underwriters' Laboratories, Inc. R3749-5.
Refer to CAFCO SOUND-SHIELD Bulletin S-10, AIA File No. 39-B-l, Sweets Architectural File 12e/Co, or call your CAFCO technical representative.
90 go. reinforcing wifeV CAFCO SOUND-SNIEID7 * tl ge. nil* taddl->d
da^fcU headed annular noil
COLUMBIA ACOUSTICS and FIREPROOFING CcwfiGHV
j BLAZE-SHIELD SPECIFICATIONS
` NOTE: To permit a comparison of quotations on-fire proofing, we recommend this work be awarded a separate section in the specifications. This will permit immediate analysis without breaking down possible combination bids. Delete irrelevant paragraphs.
FIBROUS FIREPROOFING
GENERAL.
scope
This section shall include all materials, equipment and labor necessary for the application of fibrous fireproofing to areas indicated on drawings or specified in this section.
product qualifications
The manufacturer of the fireproofing material shall have the ap proval for the application specified. Such approvals are to in clude those of the pertinent municipal authorities and insurance rating boards, including (list code municipal and insurance authorities). The manufacturer shall provide acceptable labora tory test data to these authorities for approval.
contractors qualifications
The Contractor shall be franchised for this type of work by the manufacturer of the materials; he shall use materials and ap plication and Dust Control equipment approved by the manu facturer; he shall make the application or this work under the supervision of a manufacturer trained or approved foreman; he shall execute the work in strict accordance to manufacturers specifications and instructions.
samples
The Contractor shall submit two samples to the architect prior to commencement of work.
examination of existing work
The Contractor shall examine all work prepared by others which is to receive the work of this section. Commencement of work constitutes acceptance of all surface bases and preparations for his work.
work by others
Surfaces for application of fireproofing and base attachments for the suspension of pipes, ducts, lights, acoustical ceilings and other mechanical devices shall be installed by others prior to commencement of work covered by this section.
MATERIALS
bonding adhesive
Shall be milky white, latex-type water emulsion which shall be unaffected by water, water vapor, condensation, aging, or freez ing once it has set up. Bonaing adhesive to be CAFCO AD HESIVE as supplied by Columbia Acoustics and Fireproofing Company, Stanhope, N. J., or approved equal
fiber
The fiber shall be a factory quality-controlled and formulated mix consisting of inorganic virgin Crysotile asbestos fibers and small pellet, white mineral fiber, combined with inorganic binders. The materials shall have the approvals required in "product quali fications'* above. The fiber shall have a thermal conductivity (k) factor of not greater than 0.26; shall have a Noise Reduction Co efficient of 0.90 when applied in thicknesses of 7/16" and 1-7/16" to a test assembly composed of cellular steel deck and steel beams, respectively, as tested by Riverbank Acoustical Laboratories. Fiber shall be CAFCO BLAZE-SHIELD as manufactured by Co lumbia Acoustics and Freproofing Company, or approved equal, and shall be supplied to the job site in sealed paper bags, properly marked and labeled to show the approval of Underwriters' Labo ratories, Inc.
transparent overspray
Shall be CAFCO SEALER or approved equal; shall be trans parent and unaffected by moisture.
INSTALLATION
job conditions
Application shall be started only after the contractor is satisfied surface and weather conditions are acceptable. Surfaces shall be reasonably clean and free of dirt, grease, oil, loose plaster, rust, paint, or other conditions which would tend to prevent good adhesion. Freezing weather application shall follow the manufacturer's recommendations.
procedure
All surfaces to be covered shall be primed with bonding ad hesive. Fiber shall be applied to required thickness, and then tamped and oversprayed with sealer.
CAFCO FOR ACOUSTICS AND INSULATION
While CAFCO BLAZE-SHIELD has valuable acoustical and insulating properties, it has been designed primarily for efficient, economical fireproofing. Technical infor mation covering CAFCO SOUND-SHIELD, for acoustical absorption, and CAFCO HEAT-SHIELD, for thermal insulation, can be found in Sweets Architectural lla/Co and Plant Engineering 6a/Co Files, respectively.
Air Terminal Bldg., Uplands Airport, Ottawa, OnL Dept, ef Transport, W.A. Romsoy, Chief Architect General Contractor: Perinl ltd., Ottawa Architects: Gitlelond end Strvtt, Ottawa
COLUMBIA ACOUSTICS
and FIREPROOFING Company
(Canada) Limited, Montreal, Canada
Exclusive Canadian Distributors
E. T. SAMPSON and COMPANY, LTD.
Montreal
Toronto
PtlNTEO IN U.S.A.
Sun life Assurance Company of Co node, limited, Toronto Architects and Engineers: John B. Parkin Associates Consulting Architect: A-A.C. Porkin, PPKAIC General Contractor: Perinl, ltd.