Document VGjZxr3qzOR6QMmByG4q785Xq

260 Chapter 14 1945 Guide Column C; rBdiatorrunouts afid undrippedTiser ruriouts from ColumrfX; -up-feed risers from Column J; the main riser on a down-feed system from Column C (it will be noted that if Column H is used the drop would exceed the jimit ofMi lb); the dry return from Column R; and the wet return from Column Q. With a J^-lb drop the sizing would be the same as for Mi lb except that the steam main and dripped runouts would be sized from Column B, the main riser on a down-feed system from Column B, the dry return from Column 0, and the wet return from Column N. Notes on Gravity One-Pip Air-Vent Systems X. Pitch of mains should not be less than M in. in 10 ft. 2. Pitch of horizontal runouts to risers and radiators should not be less than M in. in 10 ft. Where this pitch cannot be obtained runouts over 8 ft in length should be one size larger than called for in the table. Table 6. Pipe Sizes foe One-Pipe Up-Feed System Shown in Fig. 7 Part of Ststeh Section or Pipe Branches to radiators.. Branches to radiators.. Riser.. a to b Riser.. b toe Riser________ ______ ctod Riser....... ... d toe Riser.. .... etof Branch to riser._____ _ Supply main / tog gtoh Branch to supply main h toj JL>ry return main_____ /to k Wet return main_____ ktom Wet return main m to n Wet return main ntop Radiation Supplied EDR Sq Ft Thboreticai Pipe size (INCHR8) Practical Pipe htwb (Inches) 100 2 2 50 200 1M 2 1M 2 300 2M 2M 400 2M 2M' 500 3 3 600 3 3 600 m. SH 600 3 3 600 2M 3 600 l M 2 600 l 2 600 1 2 600 l 2 Fig. 7. Riser, Supply Main and Return Main of One-Pipe System *2"^ 3. In general, it is, not desirable to have a main less than 2 in. The diameter of the far end of the supply main should not be less than half its diameter at its largest part. 4. Supply mains, branches to risers, or risers, should be dripped where necessary. 5. Where supply mains are decreased in size they should be dripped, or be provided with eccentric couplings, flush on bottom. Example 4. Size the one-pipe gravity steam system shown in Fig. 7 assuming that this is all there is to the system or that the riser and run shown involve the longest run on the system. Solution. The total length of run actually shown is 215 ft. If the equivalent length of run is taken at double this, it will amount to 430 ft, and with a total drop of \4 lb the drop per 100 ft will be slightly less than Me lb- It would be well in this case to use Mi lb, and this would result in the theoretical sizes indicated in Table 6. These theo retical sizes, however, should be modified by not using a wet return less than 2 in. while the main supply, g-h, if from the uptake of a boiler, should be made the full size of the ims amina,doer23inin. . Also the portion of the main k-m should be made 2 in. if the wet return - Steam Heating Systems and Piping_______ ;_________________________ ' ~ ' 261 ---------~-------------------ONE-PIPE VAPOR SYSTEM-------------------- The one-pipe vapor system operates under pressures at or near atmos pheric and returns its condensation to the boiler by gravity. In this system the automatic air valves are of special design to permit the ready release of air and prevent its ready return after it is expelled. The steam radiator valves are a type which, when opened, give a free and unob structed passageway for water. The piping is the same as for the one-pipe gravity system but sized so as to permit operation at a few ounces pressure. TWO-PIPE VAPOR SYSTEM A two-pipe up-feed vapor system using separate supply and return pipes is shown in Fig. 8. The radiators discharge their condensation Fig. 8. Typical Up-Feed System with Automatic Return Trap3 Proper piping connections are essential with special appliances for pressureequalizing and air elimination. through thermostatic traps to the dry return pipe. These systems operate at a few ounces pressure and above, but those with mechanical condensate return devices may operate at pressures upward of 10 lb. The simplest method of venting the system consists of a j^-in. pipe with a check valve opening outward. Most systems employ various forms of vent valves, designed to allow the air to readily pass out of the system and to prevent its return. These systems permit control of the heat in the radiator by varying the opening of the graduated radiator valves. The boiler pressure is maintained at substantially constant pressure slightly above atmos pheric pressure. These systems may be classified as (1) closed systems, consisting of those which have a device to prevent the return of. air after it has once been expelled from the system, and which can, operate at both super and subatmospheric pressures for a period of four to eight hours depending upon the tightness of the system and rate of firing, and (2) open systems, com prising those which have the return line constantly open to the atmos phere without a check or other means to prevent the return of air. The