CHAPTER 30
1965 Guide And Data Book
This type of installation affects all factors previously dis cussed. Since the air stream entrains air on both its upper and lower surfaces, a higher rate of induction is obtained and results in a throw shortened by about i- Air loadings for these outlets can therefore be increased. Air drop from ceiling diffusers is increased by installation on exposed ducts, be cause there is no surface effect, and temperature differentials in summer air-conditioning systems must be restricted to a
to distribute air in various portions of the room in proportion to the heat gain or loss in those areas.
4. Select proper outlet size from manufacturers' ratings ac cording to the air quantities, discharge velocities, distribution patterns, sound levels, etc. Note manufacturers' recommenda tions with regard to use, method of installation, minimum ve locities, munmiim temperature differentials and any air distri bution characteristics which may limit the performance of the outlet.
range of 25 to 28 F deg. Air streams from slot diffusers and Noise Control
grilles may exhibit a marked tendency to drop because of the
lack of tiie surface effect.
The sound level of an outlet is comprised of the sound
Smudging is a problem frequently encountered with ceiling-' - generation of the outlet, which is a function of the discharge and slot diffusers. It occurs when the diffuser is mounted ' velocity, and the transmission or systemic noise, which is a
against the ceiling surface. For.diffusers, mounted flush with . function of the size of the outlet. Higher frequency sounds can
the ceiling, smudging is greatly minimized..The-dirt,suspen- ' be.the result of.'excessive outlet velocity but may also result
sion in the room air is subjected to turbulence at the outlet from sounds generated'in the duct by the moving air stream.
face, due, to induction, and is primarily regpo.nsrble for the Lower pitched sounds are generally the result of transmission
marked areas, ofblack and white that characterize smijdging: of mechanical,equipment noisfr through the duct.system and,
Smudging, can be expected' in areas which have a high- dirt' - outlet.. The cause: oi higher, frequency sounds can be pin
content in the room air, such, as areas of high 'pedestrian1/ pointed, as outlet or systemic, sounds by- removing the outlet
-traffic (lobbies, stores,, etc:). When ceiling diffusers are in-' during operation. A reduction in sound fevel indicates that the
stalled on smooth ceilings (plaster, mineral* tilei metal pan,-* outlet is causing noise..If the sound level remains essentially
etc.), smudging is in the form of a narrow band of discolora unchanged, then the system is at fault.
tion around the diffuser. Anti-smudge rings are quite effective
High pressure air distribution systems pose severe systemic
in preventing this type of- smudging. On- highly- textured- Bound problems, and these conditions must be treated sepa
ceiling surfaces such as rough plaster or sprayed-on compo rately. Special'attenuation devices are generally used'in con
sition, smudging;can be expected, to occur over a more exten junction with these systems. (See section on Equipment For
sive area. In,such cases anti-smudge, rings ace less effective,'. All-Air High-Pressure-Systems, this chapter.).
Refer to Chapter 14- on Sound Control, for more complete
PROCEDURE fQR OUTLET LOCATION' . AND. SELECTION,
information-on-design criteria, acoustic treatment,, selection procedures,,etc,
The following-procedure is generally used in selecting outlet locations and-'types of outlets:-
1., Determine the amount of, air to be supplied,to each room. Refer tp Chapters 26 &nd-27; for determination of- air quantities
for heating and'cooling.)* Determine.the-amounbof outdoor air to be introduced,accordmg- to .ventilation requirements of, state.or, local coda.
2. Select the- type of outlet arid, quantity`of' outlets for'each rpom, considering-`such' factors, as- air- quantity required;; dis-
tarice avaflablc'for-throw or radius.of: diffusion,.structural charr octeristics,apd. architectural-,concepts. Table. 1 iaibased.on ex
perience and typical, ratings of. various types of outlets. It.may
qe.used.as a general'guide to the types of outlets which may. or may. not be applicable1 for me-with various room, air loadings.1 Special conditionssuch as ceiling heights greaterl than-the.normal
8-12 ft, expo9ed;du.ct;mounting,,etc.,a8,well aaproduct modifier tionsjiwd, unusual conditions.of, roqm occupancy can.all modify
this table. Manufacturers' rating, data .should- be consulted; for
final determination of'the-suitabmty-of-the-types of, outletsito.be
used.
.
i i. - . . ,
- 3.- Ijpcatp-outletS'in the rooip;to distribute the.air as uniformly
as possible throughout the rqom. Outlets,may be sized and.located
. Table 1:.General'Guide-to Use-of Various1 Outlet-Types
Air toadag/CFM/^fl'ff ot'Roor Ane.i
1 to 1.5 1.5 to 3.Q
Dp* of Oufitf Grille
i * itwrngR.Banns . Vcfocttyr ' ,
25^35' 35^70``
GRILLE OUTLETS
Adjustable barprifc,.Thuris'the'most.common type of grille
used; as supply, outlet.: The:single deflection) grille consists oft
a frame enclosing a set of vertical or horizontal vanes. Vertical
vanes deflect the air.stream in.the horizontal plane and hori
zontal vanes definetthe airstream in-the-vertical plane. The
double, deflection, grille- has a,second set, of. vanes, installed
behindland..at rightangles.to the face vanes. This.grille con
trols the air stream .in both the horizontal and vertical planes..
The opening,between-twadjacentbars mustnot exceed the
depth-of; the.vanes for, effective control of, the direction of. the
air stream discharged from adjustable bar grilles..
Fixed^bargrille. This grille type is similar, to the single-de
flection grille/,except*,that, the-vanes are not adjustable. .The
vanes .may be..straightor.sefc at a.certain angle..The.angleat
which, the air ia,discharged from this-.grille.depends on .the
type of deflection vanes.
Stomped,gnUegr(sometimes referred.to as perforated,grilles).
These grilles are made; from, a single sheet of. metal which is
stamped out to,form.a.fretwork through which aircan.pass-
Various designs,are used, varying.from,square or. rectangular,
holes to intricate ornamental designs..This.typeof,outlet offers
no directional.contrail
.. ..
.The.air. handling capacity, of- stamped! grilles.varies.widely
with-their, design,, buttin general,, stamped: grille,have com
sderahly less capacity than; vane.type grilles..Their, main ad
vantage is structural strength, and pleasing appearance..
1.5 to 2:5.' ; 2.5 to 4.0
1 Sot
. 20-35 ; ' 3^55 ...
2.5to 3'.5' ' 1
3.5to5:0-
Diffuser:
' 5.0'to 6i5u
. ..
25-35
35r50; 50-5..
Applications
Properly'selected grilles-* operate satisfactorily.-from: high sidewall locations and from perimeter locations in the-sill,' curb, or floor. Ceiling mounted: grilles.whicli'discharge the air stream downward; are generally, not acceptable" in comfort
Air-Diffusina Equipment
555
air-conditioning installations in Interior cones, and may cause
complaints of draft in perimeter applications. High sidewall location generally presents two problems in
distributing the air properly in the space; (1) how to spread the discharged air properly in a horizontal plane in order to diffuse it over the entire area"being served by the outlet, and (2), how to prevent stratification of hot air, or premature drop into the occupied zone of cold air. Therefore, use of a double-
defleetion grille generally provides the most satisfactory, solution. The vertical face louvers of a well-designed grille will deflect the air approximately 50.deg to either side and
thus provide ample coverage of the conditioned space. Its rear louvers deflect the air at least 15 deg in the vertical
piflne, which is ample to control the elevation of the discharge
pattern. In perimeter installations, the grille must be selected to fit
the specific job. When small grilles must be used, adjustable vane grilles improve the coverage of--perimeter, surfaces., Where the perimeter surface can be covered with long grilles,; the fixed vane grille is satisfactory. Where grilles are located, more than 8 in. from the perimeter surface, it is usually de sirable to deflect the air stream towards the perimeter wall. This can be done with adjustable or fixed deflecting vane
grilles. Stamped outlet grilles should not be used as supply outlets
because of their restricted capacity and their lack of pattern
control.They may find some use, however, in perimeter instaT
lations as covers for supplementary heating openings, or for
the discharge of extremely
amounts of supply air.
Accessory Devices
Various accessory devices, designed to improve the per
formance of grille outlets, are available as standard equip
ment.
. ,v
Opposed-blade dampers can be attached to the back of grilles,,
(the combination of a grille and a damper is called a register),
or they may be installed as separate units in the duct. See
Fig. 1 (A). Adjacent blades of this damper rotate in opposite
direction, and therefore may receive air from any direction,
discharging it in a series of jets without adversely deflecting
the air stream to one side of the duct.
Multi-shutter dampers have a series of gang-operated blades
which rotate in the same direction. See Fig. 1 (B). This uni
form rotation deflects the air stream when the damper is par
tially open. Most dampers sue operated by removable keys, or by fixed
or removable levers.
Gang-operated turning vanes are used for installation in
collar connections to branch ducts. The device shown in Fig.
1 (C) has vanes which pivot and remain parallel to the duct
air flow regardless of the setting. The second device. Tig.
1 (D), has a set of fixed vanes. Both devices restrict the area of
the duct in which they are ingtAlWl- They should only be used
when the duct is sufficiently wide to allow the device to open to its ma-rimnm position without causing undue restriction
ofair flow in the duct which might limit downstream air flow.
IndunduaUy adjusted turning vanes are used in the device
shown in Fig. l (E). Two pairs of vanes are used. The down
stream set of vanes equalizes flow across the collar, while the
upstream vanes act as turning vanes. They can also be'ad
justed at various angles to act as a damper. However, it is not
practicable to use this device as a damper, because its balanc
ing requires removal of the. grille,to gain access, and reinstalla-
tion to measure air flow. This is a tim/w-nrumming procedure.
Other miscellaneous accessories which are available as stand-
ard equipment are fusible-link attachments to close dampere in-case of fire, remote control devices to operate the dampersfrom locations other than the grille face, maximum-minimum stops to limit damper travel, etc. -
Special Construction Features
Materials end Finishes. Grilles' are made of aluminum, brass, and bronze. Most commercially available finishes, such as paint, enamel, lacquer, electroplating, anodizing, and polishing are used in their manufacture.
Special Features. Hand-hole doors in grilles for perimeter unite, insect screens, reinforcements for grilles for added strongth,tamper-proof installation devices, protective screens or grids over outlets, and special frame shapes and widths,
are made to order.
SLOT DIFFUSER OUTLETS
The slot diffuser is an elongated outlet consisting of a single or a multiple number of slots. It is usually installed in long continuous lengths, and is well suited to the present-day architectural trend toward straight, clean lines and unob trusive appearance. Outlets with dimensional aspect ratios of 25 to' 1 or greater, and a maximum height of approximately 3 in., generally meet the performance criteria for slot dif fusers discussed in the section Supply Air Outlets.
' Two hasic types of slot diffusere are perpendicular flow slot diffusers, and parallel flow slot diffusers. :
Perpendicular Flow Slot Diffusers. The air discharge direc tion is perpendicular to the surface of the diffuser. The use of bars, vanes,' or internal deflection devices, may permit deflec tion of the air up to 30 deg from the perpendicular flow path. '' Parallel Flow Slot Diffusers. The air is discharged parallel with the surface of tire diffuser. Bars,' vanes, or internal de flection devices are required to achieve this flow pattern.'
Applications
High Side-WqU Installation.,.The perpendicular-flow slot diffuser is best suited to high side-wall installations and perimeter, installations in sills, curbs and floors. The air diacharged.from a perpendicular diffuser will not drop, if the diffuser is located within &-12 in. from the ceiling, and is of
iWVfi .
i // /:/)
- FLOW : J -^1
BRANCH ' OUCT
I OUTLET 1 COLLAR
6RANCH DUCT
Tlow--------
0UCT
-- OUTLET
1 COLLAR
OUTLET COLLAR
Fig. 1____Accessory Control Device, for. Grille and Register Outlets