1965 Guide And Data Book'
d. The figure of merit, Z -- cA/pK, involving the three parame ters previously dwcnwyjd, is used for describing the merit of a thermoelectric material and should be as laige as poadble. A similar concept in compressor performance is the volumetric efficient as affected by all three characteristics already dis cussed, i.e., pbton blovby and valve leakage, friction losses con tributing to gas superheating, and re-expansion losses.
(e) The maximum temperature difference, A7* -- `JZT1.*, that can be developed under no load conditions. This is similar in concept to the maximum pressure difference obtainable' in a compressor, also in an unloaded condition, and is dependent on the volumetric efficiency and the suction pressure.
ADVANTAGES AND APPLICATIONS OF
THERMOELECTRIC COOLING
The heating and cooling functions of the condenser and evaporator in a mechanical system can be interchanged by. reversing the direction of refrigerant flow. This cannot be achieved without considerable difficulty and expense. Since tiie motor and compressor involve rotary and reciprocating motion, wearing of parts and noise may also present a prob lem. The containing of the refrigerant requires a hermetic system which must be leakproof. A further inherent limitation of this system is that it cannot be readily made in miniating to economically provide a small amount of refrigeration.
The heating and cooling functions of a thermoelectric sys tem can easily be interchanged by reversing the polarity'of' the direct current applied to it. Since there are no moving parts, there is nothing to wear out and nothing- to generate noise. There is no refrigerant to contain, and the pressure^' tight tubing has been replaced by electrical wiring. Since thei cooling capacity of a single thermoelectric couple is very small, it is practical to make a system of very low refrigerating ca pacity. The thermoelectric system can also be made in large capacities by using many couples.
Capacity control in a thermoelectric system can be achieved by varying the voltage applied to the couples. The current flow is thus changed and the capacity changes'(see Fig. 6).
Another advantage is that a thermoelectric system will operate under zero gravity, or many times the force of earth gravity, and will operate in any position. This is important in considering cooling applications for use in space travel. A thermoelectric system also operates satisfactorily at high temperature levels up to 220 F.
Along with the advantages there are some disadvantages. One is that, at this time, a thermoelectric system requires more power than a compression system to produce a given cooling capacity. Fig. 5 gives an approximate comparison of tiie coefficients of performance of a compression system and thermoelectric systems using materials with various figures of merit. The current figure of merit is approximately 0.003 per C degree.
Since a thermoelectric system has no moving parts nothing to wear out, it might be expected to have an infinite
life. Individual couples and some devices have operated with out a noticeable change for a few years. However, there are some tilings that, if not controlled, may cause a degradation of performance. It is known that copper will diffuse into a thermoelectric material and adversely affect its thermoelec tric properties. The solders for joining thermoelectric material to copper straps must be carefully selected so that they do not diffuse into the thermoelectric material and eventually result in a joint failure. These effects can be minimised, and prob ably eliminated, by nickel plating the ends of the couple legs prior to soldering. The solders must also be selected with regard to the temperature range of operation of the system.
Thermal expansion and contraction of the materials on the1 opposite faces of a system will induce stresses. If the function
of a particular system is to alternately cool and
there
will be a reversal of these stresses. Materials must be selected to withstand this.
For many applications, the advantages of thermoelectric
cooling -will outweigh its .chief disadvantage of a relatively
low coefficient of performance. For some cooling requirements,a thermoelectric system is the only practical miming
Some of the applications of thermoelectric cooling are: air
conditioning and refrigerating systems for use on submarines,
temperature control of electronic components, cooling of scien
tific instrument components and small specialty appliances.
The U. S. Government has .sponsored the development of
many thermoelectric systems. Among these are: an 8500-Btuh
unit* for possible use as the refrigerating method for frozen
food storage rooms on nuclear submarines, a 9-ton air con
ditioner for a small submarine, prototypes of air conditioners
for submarines*, and temperature control of crystal oscillators
in frequency standards, to improve their life and sensitivity.
Thermoelectric applications in the scientific instrument field
include: immersion cooler.for cooling liquid in' a beaker, ther
mocouple reference junction at 32 F, instrument for measuring dew point, and microscope stage cooler.
There are also applications in commercial and appliance re frigeration. Some of these are: a drinking water cooler4 for use
on Diesel locomotives,''a small bottle-type water cooler for
offices, and a small ice maker for use in hotel rooms.
The latter unit was capable of freezing one tray of water
(approximately one pound) in 6 hours. Small portable re
frigerators with less than one cubic foot internal volume have
been marketed by two manufacturers. Both of these could be
operated from a 120-volt alternating-current source^ or from
a'12-volt direct-current automobile electrical system. A 2 cu
ft unit which can be used either as a refrigerator or a warming
oven has also been produced. The cabinet air temperature is 35 F on the cooling cycle and 160 F on warming
In tiie commercial and appliance areas, thermoelectric cooling is best suited to small specialty devices. The products
mentioned in tiie previous paragraph illustrate'this. Cur rently, thermoelectric cooling is economically practical in only low capacity systems.7 As the' capacity increases to
over 200 or 300 Btuh, a compression system will probably be the more economical. Ah' increase' in the figure of merit and a
decrease in the cost per couple will be necessary to change this
'relationship. Fig. 10 gives the maximum temperature differ
ence that has been achieved over the years. This can be con
verted to the figure of merit by using Equation 14. Based on
data currently available (1964), the maximum temperature
difference shown for 1961 has not been exceeded. There have,
however, been reductions in the cost of thermoelectric couples,
due to improved manufacturing techniques.
Fig. 10 .... Maximum Temperature Difference Achieved with a Thermoelectric Couple Over the Yean
Thermoelectric Cooling
,, ;__ J-^ctcr materials used for thermoelectric cooling cGuSeArTcurrently made from alloys of bismuth, tellurium,
and antimony for p-type, and of bismuth, tellurium, and selenium for n-type. Usually minute quantities of other ma terials are added to improve the thermoelectric properties. There has been a very great research effort to find improved materials and to develop a knowledge of the fundamental characteristics of these materials. While this knowledge has been increased, it is still not adequate to enable scientists to predict when higher figures of merit will be available or to estimate how high a figure of merit may be possible.
GUIDE TO THE DESIGN OF DEVICES
Information similar to that required for the desip of a
compression refrigerating system must also be established in
order to
a thermoelectric system. Some of the factors
to be considered are: ambient temperature, means of heat
removal from hot junctions, means of heat absorption at the
cold junctions, and the power available. Fig. 11 is a schematic
view of a thermoelectric assembly including couples and fins
for absorption and dissipation of heat.
A very important item in device design is heat transfer be
tween the thermoelectric junctions and the heat source or heat
cinlr For example, the temperature difference over which'a
couple operates is larger than the temperature difference be
tween ambient and tiie interior of a refrigerator. From Fig. 12,
it can be seen that, 'with a fixed current, a change in tempera
ture difference across the couple has an appreciable effect on
cooling capacity. The couple temperature difference must be
minimized to obtain tbe best performance.'
The couple-temperature difference in the assembly shown
in Fig. 11 equals tiie sum of these temperature differentials:
air temperature on hot side to air temperature on cold side,
hot ride fin base to ambient, hot junction to hot ride fin-base,
cold ride fin base to cold junction, cabinet air to cold side fin
base. The electrical insulation between the couples and the
fiii bases must be a good thermal conductor, to minimize
these temperature differences. A satisfactory material b diffi-
' cult to find, since most electrical insulators are relatively poor
thermal conductors. -Anodized aluminum, epoxy, coatings,
and others are bring used. The beat transfer surfaces can be
calculated by conventional means.
In designing the thermoelectric couples, the designer must
consider two basic, variables. These are current, /, and the
ratio of the cross-sectional area to tiie length of the couple legs,
A/L. There are an infinite number of combinations of these
two variables which yield the same total heat pumping.ca-
-------------- !
0.0 3J/0CG. C L *0.9 V 3I* K (no rj
27
10 19
. /-20 *1 9
t--ZSAKP /________
Fig. 12 .... Heat Pumping Capacity of a Thermoelectric Couple as a Function of Temperature Difference and Current
parity. There are'two limiting modes of operation, namely,
operation at maximum coefficient of performance and maxi
mum' heat pumping capacity, which are of special interest.
(See Fig. 6.) These two operating conditions fix I with respect
to A/L, but tiie choice'of A/L can still remain arbitrary;
more precisely, the choice of A remains arbitrary since L b gov
erned by. contact resistance considerations already, discussed.
As 'A/L b increased, the number of couples required de
creases, .since the heat pumping rate per couple b propor
tional to A/L. An increase in A/L increases the current re
quirements.
Once the temperature difference b established and a cur
rent b selected, it b possible to calculate the A/L to give
maximum cooling capacity pr maximum CP by differentiating
Equations 5 or,7 with respect to A/L, equating to zero, substi
tuting the proper values, and solving for A/L.
Another approach to the design of a thermoelectric unit b to
select thermoelectric modules that are .made by any one of
several manufacturers. A module b defined as an assembly of
thermoelectric couples. A typical eight couple module is shown
in Fig. 13.
,
. Fftch manufacturer has his own design and often provides
standard modules in different current ratings and different
numbers of couples. The manufacturer will provide per
formance data cimilftr to that shown in Figs. 6 and 12. It b /
fig. 11 .... Cross Section of Thermoelectric Module and Heat Transfer Surfaces-.!
- Fig. 13 .Typical Thermoelectric Module