HEATINC VENTILATING AIR CONDITIONING GUIDE 1944 a scum of fine particles and grease accumulates on the surface of the water in all new boilers, while heavier particles may settle to the bottom of the boiler and form sludge. These impurities have a tendency to cause foaming, preventing the generation of steam and causing an unsteady water line. This unavoidable accumulation of oil and grease should be removed by blowing off the boiler as follows: If not already provided, install a surface blow connection of at least in. nominal pipe size with outlet extended to within 18 in. of the floor or to sewer, inserting a valve in line close to boiler. Bring the water line to center of outlet, raise steam pres sure and while fire is burning briskly open valve in blow-off line. When pressure recedes, close valve and repeat process adding water at intervals to maintain proper level. As a final operation bring the pressure in the boiler to about 10 lb, close blow-off, draw the fire or stop burner, and open drain valve. After boiler has cooled partly, fill and flush out several times before filling it to proper water level for normal service. The use of soda, or any alkali, vinegar or any acid is not recommended for cleaning heating boilers because of the difficulty of complete removal and the possibility of subsequent injury, after the cleaning process has been completed. Insoluble compounds have been developed which are effective, but special instructions on the proper cleaning compound and directions for its use in a boiler, as given by the boiler manufacturer, should be carefully followed. Care of Idle Heating Boilers Heating boilers are often seriously damaged during summer months due chiefly to corrosion resulting from the combination of sulphur from the fuel with the moisture in the cellar air. At the end of the heating season the following precautions should be taken: 1. All beating surfaces should be cleaned thoroughly of soot, ash and residue, and the heating surfaces of steel boilers should be given a coating of lubricating oil on.the fire side. _ __ 2. All machined surfaces should be coated with oil or grease. 3. Connections to the chimney should be cleaned and in case of small boilers the pipe should be placed in a dry place after cleaning. 4. If there is much moisture in the boiler room, it is desirable to drain the boiler to prevent atmospheric condensation on the heating surfaces of the boiler when they are below the dew-point temperature. Due to the hazard of some one inadvertently budding a fire in a dry boiler, however, it is safer to keep the boiler filled with water. A hot water system usually is left filled, to the expansion tank. 5. The grates and ashpit should be cleaned. 6. Clean and repack the gage glass if necessary. 7. Remove any rust or other deposit from exposed surfaces by scraping with a wire brush or sandpaper. After boiler is thoroughly cleaned, apply a coat of preservative paint where required to external parts normally painted. 8. Inspect all accessories of the boiler carefully to see that they are in good working order. In this connection, oil all door hinges, damper bearings and regulator parts. 250 CHAPTER 13 Radiators and Convectors Heat Emission of Radiators and Convectors, Types of Radi ators, Convectors, Radiator and Convector Ratings, Effect of Operating Conditions, Heating Effect, Heating Up the Radi ator and Convector, Enclosed Radiators THE accepted terms for heating units are: (1) radiators, for direct surface heating units, either exposed, enclosed, or shielded, which emit a large percentage of their heat by radiation; and (2) convectors, for heating units haying a large percentage of extended fin surface and which emit heat principally by convection. Convectors are dependent upon enclosures to provide the circulation by gravity of large volumes of air. HEAT EMISSION OF RADIATORS AND CONVECTORS Most heating units emit heat by radiation and convection. The re sultant heat from these processes depends upon whether or not the heating unit is exposed or enclosed and upon the contour and surface charac teristics of the material in the units. An exposed radiator emits roughly half of its heat by radiation, the amount depending upon the size and number of sections. When the radiator is enclosed or shielded, the proportion of radiation is further reduced. The balance of the emission is by conduction to the air in con tact with the heating surface, and the resulting circulation of the air warms by convection. A convector emits practically all of its heat by conduction to the air surrounding it and this heated air is in turn transmitted by convection to the rooms or spaces to be warmed, the heat emitted by radiation being negligible. The output of a radiator can be measured only by the heat it emits. The old standard of comparison used to be square feet of actual surface, but since the advance in radiator design and proportions, the surface area alone is not a true index of output. (The engineering unit of output is the Mbh or 1000 Btu per hour.) However, during the period of transition from the old to the new, radiators may be referred to in terms of equivalent square feet. For steam service this is based on an emission of 240 Btu per hour per square foot and for hot water service 150 Btu per hour per square foot. TYPES OF RADIATORS Present day radiators may be classified as tubular, wall, or window type and are generally made of cast-iron. Only the small-tube type of 251