Document V3kv2599XJQk26Bwy4ZJVZ7eo
668
CHAPTER 31
;,1953 Guide
Since 55 effective diameters are equal to 30 ft as required. 1 effective, diameter
30/55 = 0.545 ft or 6.56.in.,. . .
.
On Fig. 3 vertically, below intersection of 6.56 in. effective diameter line, and
equivalent round opening line,' read 8.5 in. in lower margin.'
" ''
Example 4- A jet of air issues from a pipe or from air orifice having a well-rounded
.AirDistribution
669
imed.andipimditpjbe.betjyeen 14 and 25 deg. The,angle will.depend on the type of approach, type .of outlet-and velocity.
The effect of vertical bars placed in the face of the outlet to increase the
spread, may also be deduced from the momentum theory. '-Assuming that
there are, no horizontal deflecting bars, and that the air spreads vertically
!through a total .angle of 14: deg; that a unifprm velocity exists at any sec
tion of the air'stream; and that'the conservation of momentum principle
rappjies down.to^ajyelocityof.60 fpm; the following approximate equations
,for throw are to be substituted for Equation 4:2 .
. ..
For
a
spread
of
15
deg
on
each
horizontal
side
L
--
0.55
Qi_VAi
(8)
For a spread of 30 deg on each horizontal side L -- 0.37 --7= v Ai
For
a
spread
of
45
deg
o-n
each
horizontal
Bide
L:
=
,0.28
Qi VT7A==l'.
0) (10)
SLOT WIOTH OS ORIFICE OtAMETER- INCHES
Fig. 3. Effective Diameters for Round and Rectangular Openings
(Plenum Approach)
,,
entrance (coefficient of discharge = 1.0) and delivers air with the same velocities'and with the same throw as in Example S. What is the required diameter?
In this case since the coefficient of discharge is unity, the effective diameter of the jet is the actual diameter of the pipe or orifice, or 6.56 in., as obtained in Example S.
Spread
The induction effect results in the spreading of the air stream. The totTa*;'(l' angle included by the air stream from straight flow outlets has beenmeas-
Fig. 4. Spread of Air Stream with Various Vanes
Guide Vanes
Vanes should have a depth of one to two times the spacing between the vanes. If the ratio of vane depth to spacing is less than one, effective control 'by means of the vanes cannot be obtained. Little improvement is ob tained by increasing.the-ratio beyond two. The effect of various types of varies is given in following paragraphs.
Straight Vanes. As mentioned previously, the included angle between both planes
will be in the neighborhood 6514 deg, for a straight setting of the vanes as shown in
Fig. 4.
Diverging Vanes. Such vanes set for an angular spread will have a marked effect
on the direction and distance of travel of an air stream. An outlet having vertical
vanes set straight forward in the center, with uniformly increasing angular deflection
to a maximum at each end of 45 deg, will produce an air stream with a horizontal
included angle of approximately 60 deg as shown in Fig. 4. The throw will be re
duced one-half for such a vane setting. Increasing the divergence of the vanes
reduces the air quantity handled by an outlet, for a given duct static pressure. The
primary function of the vanes is to spread the air horizontally. Spreading the air
vertically entails the risk of hitting beams or other obstructions,, or of blowing pri
mary air at excessive velocities into the occupied zone.
Converging Vanes. The blow of an outlet may be somewhat increased by converg
ing the vanes of an outlet as illustrated in Fig. 4. Even with converging vanes, the
resultant angle of spread of an air stream will not be less than 14 deg. The air con
verges for a few feet in front of the outlet, and then diverges more than if the vanes
had been set straight.
. .,
Bothithe,horizontal and .vertical vanes of,an outlet are important. After an installation has been marie, many conditions of; draftiness or stuffiness