Document V3kv2599XJQk26Bwy4ZJVZ7eo

668 CHAPTER 31 ;,1953 Guide Since 55 effective diameters are equal to 30 ft as required. 1 effective, diameter 30/55 = 0.545 ft or 6.56.in.,. . . . On Fig. 3 vertically, below intersection of 6.56 in. effective diameter line, and equivalent round opening line,' read 8.5 in. in lower margin.' " '' Example 4- A jet of air issues from a pipe or from air orifice having a well-rounded .AirDistribution 669 imed.andipimditpjbe.betjyeen 14 and 25 deg. The,angle will.depend on the type of approach, type .of outlet-and velocity. The effect of vertical bars placed in the face of the outlet to increase the spread, may also be deduced from the momentum theory. '-Assuming that there are, no horizontal deflecting bars, and that the air spreads vertically !through a total .angle of 14: deg; that a unifprm velocity exists at any sec tion of the air'stream; and that'the conservation of momentum principle rappjies down.to^ajyelocityof.60 fpm; the following approximate equations ,for throw are to be substituted for Equation 4:2 . . .. For a spread of 15 deg on each horizontal side L -- 0.55 Qi_VAi (8) For a spread of 30 deg on each horizontal side L -- 0.37 --7= v Ai For a spread of 45 deg o-n each horizontal Bide L: = ,0.28 Qi VT7A==l'. 0) (10) SLOT WIOTH OS ORIFICE OtAMETER- INCHES Fig. 3. Effective Diameters for Round and Rectangular Openings (Plenum Approach) ,, entrance (coefficient of discharge = 1.0) and delivers air with the same velocities'and with the same throw as in Example S. What is the required diameter? In this case since the coefficient of discharge is unity, the effective diameter of the jet is the actual diameter of the pipe or orifice, or 6.56 in., as obtained in Example S. Spread The induction effect results in the spreading of the air stream. The totTa*;'(l' angle included by the air stream from straight flow outlets has beenmeas- Fig. 4. Spread of Air Stream with Various Vanes Guide Vanes Vanes should have a depth of one to two times the spacing between the vanes. If the ratio of vane depth to spacing is less than one, effective control 'by means of the vanes cannot be obtained. Little improvement is ob tained by increasing.the-ratio beyond two. The effect of various types of varies is given in following paragraphs. Straight Vanes. As mentioned previously, the included angle between both planes will be in the neighborhood 6514 deg, for a straight setting of the vanes as shown in Fig. 4. Diverging Vanes. Such vanes set for an angular spread will have a marked effect on the direction and distance of travel of an air stream. An outlet having vertical vanes set straight forward in the center, with uniformly increasing angular deflection to a maximum at each end of 45 deg, will produce an air stream with a horizontal included angle of approximately 60 deg as shown in Fig. 4. The throw will be re duced one-half for such a vane setting. Increasing the divergence of the vanes reduces the air quantity handled by an outlet, for a given duct static pressure. The primary function of the vanes is to spread the air horizontally. Spreading the air vertically entails the risk of hitting beams or other obstructions,, or of blowing pri mary air at excessive velocities into the occupied zone. Converging Vanes. The blow of an outlet may be somewhat increased by converg ing the vanes of an outlet as illustrated in Fig. 4. Even with converging vanes, the resultant angle of spread of an air stream will not be less than 14 deg. The air con verges for a few feet in front of the outlet, and then diverges more than if the vanes had been set straight. . ., Bothithe,horizontal and .vertical vanes of,an outlet are important. After an installation has been marie, many conditions of; draftiness or stuffiness