Fig. 33. Top and Bottom Opposite End Radiatoe Connections
Fig. 34. Connections to Radiator Hung on Wall
Steam Heating Systems and Piping
453
of pipes. To take care of expansion in long risers, either expansion points of commercial construction or pipe swing joints are used: Anchoring of pipes between expansion joints is desirable.
Two satisfactory methods of making runouts for one-pipe systems for either the up-feed or the down-feed type are shown in'Fig. 31. Where the vertical distance is limited and the runouts must run above the floor, the radiator may be set on pedestals or raised by means of high legs. Two methods of connecting a unit heater to a one-pipe steam heating system are illustrated in Fig. 2 and also in Fig. 5 of Chapter 26.
Typical two-pipe radiator or convector connections are shown in Figs. 32, 33 and :34. While the top is the preferred location for the' control valve, it-may'be located'at the bottom.1 Short'radiators may be5 top supply and bottom return5 on same end. With convectors the control
Fig. 35. Typical Pipe Coil Connections
Flc
i Connectins
Indirect Radiators with ; Wet Returns
Fig. 37. Typical Piping Connections
to Indirect RadiatorsTwith
Dry Returns "
.,
i
Fig. 38. Typical Piping for Atmospheric and'Vacuum Systems with Thermostatic Control (Central Fan System)
valve is sometimes omitted and a damper in outlet grille.used for heat control. The typical method of connecting pipe coils is shown in Fig. 35 and is suitable for atmospheric, vapor, vacuum, sub-atmospheric, and orifice systems.
Typical pipe connections for.indirect.radiators and tempering or heating stacks are shown in Figs. 36, 37, 38, 39, 40, 41, and 42.
Where a building is served by. a vacuum system or a sub-atmospheric .system the stacks should be piped in the usual manner and traps of large capacity, preferably of the combination float and thermostatic type, should be used.' In the orifice and closed two-pipe systems, traps should .be used on the returns so that a pressure above that of the atmosphere may be secured on the heaters.
Each stack should have a separate steam and return connection and trap. Wide stacks are more evenly heated if divided and supplied with two steam connections, one at each end, and a return connection for each