Document RwZqEB1OmggjK5EdrVabwNdk
446
CHAPTER 23
1948 Guide
CONDENSATE RETURN PUMPS
Condensate return pumps are used for gravity systems when die local conditions do not permit the condensate to return to the boiler under the existing static head. The return of the condensate permits the water to repeatedly go through the cycle of vaporization, with subsequent condensation and return to the boiler. During such repeated cycles any incrustants or other substances in solution are precipitated and the water de-activated to a considerable extent so that corrosion of a serious nature is seldom ever encountered where the condensate is repeatedly used. Serious corrosion is more frequently found in systems in which the con densate is wasted and fresh make-up water is continually being intro duced.
The most generally accepted condensate pump unit for low pressure heating systems consists of a motor-driven centrifugal pump with receiver and automatic float control. Other types in use include rotary, screw, turbine and reciprocating pumps with steam turbine or motor drive, and direct-acting steam reciprocating pumps.
The receiver capacities of these automatic units should be sized so as not to cause too great a fluctuation of the boiler water line if fed directly to the boiler and at the same time not so small as to cause too frequent operation of the unit. The usual unit provides storage capacity between stops in the receiver of approximately 1.5 times the amount of condensate returned per minute and the pump generally has a delivery rate of 3 to 4 times the normal flow. This relation of receiver and pump size to heating system condensing capacity takes account of the peak condensation rate.
A typical installation of a motor driven automatic condensate unit is illustrated in Fig. 9.
VACUUM HEATING PUMPS
On vacuum systems, where the returns are under a vacuum, and subatmospheric systems, where the supply piping, radiation and the returns are under a vacuum, it is necessary to use a vacuum pump to discharge the air and non-condensable gases to atmosphere and to dispose of the condensate. Direct-acting steam-driven reciprocating vacuum pumps are sometimes used where high pressure steam is available or where the exhaust steam from the pump can be utilized. In general, however, these have been replaced by the automatic motor-driven return line heating pump especially developed for this service. Steam turbine drive is also frequently used where steam at suitable pressures is available, the steam being used afterward for building heating. The usual vacuum pump unit consists of a compact assembly of exhausting unit for withdrawing the air-vapor mixture and discharging the air to atmosphere and a water removal unit which discharges the condensate to the boiler. They are furnished complete with receiver, separating tank and automatic controls mounted as an integrated unit on one base. There are also special steam turbine driven units which are operated by passing the steam to be used in heating the building through the turbine with only a 2 to 3 psi drop across the turbine required for its operation. . Under special conditions such as installations where it is .necessary to return the condensate to a high pressure boiler, auxiliary water pumps may be supplied. In some instances separate air and water pumps may be used.
For rating purposes8 vacuum pumps are classified as low vacuum and high vacuum. Low vacuum pumps are those rated for maintaining 5^ in.
Steam Heating Systems and Piping
447
Hg vacuum on the system, and high vacuum pumps are those rated to
maintain vacuums above 5J4 in.
Manufacturers of vacuum pumps specify that the standard capacity of pumps shall be 0.3 to 0.5 cfm of air removal and 0.5 gpm of water per 1000 EDE served. This capacity is at 5M in. of vacuum and with con densate at 160 F. The larger air capacity is for smaller systems and the smaller capacity for the larger systems.
Some manufacturers, however, specify more air capacity than standard where higher vacuums are desired and where air leakage is suspected.
The vacuum that can be maintained on a system depends upon the relationship of the air leakage rate into the system to the operating air capacity of the hydraulic evacuator when operating at any given return line temperature. The hotter the returns, the lower will be the possible vacuum for a given air leakage rate into the system; It is particularly essential on high vacuum installations to see that the entire system is tight in order to reduce the amount of inward air leakage and, further-
Fig. 21.
Method of Discharging High-Pressure Apparatus into Low-Pressure Heating Mains and Vacuum Return Mains through a Low-Pressure Trap
more, to see that relatively higher temperature steam is prevented from
entering the vacuum return lines through leaky traps, high pressure
drips, etc. It is for this reason that the condensate from equipment using
steam at high pressures should not be connected directly to a vacuum
return line, but should drain to a receiver through a high pressure trap.
The receiver should have an equalizing connection to a low pressure steam
main and drain through a low pressure trap to the vacuum return main as
indicated in Fig. 21.
'
Vacuum Pump Controls
- In the ordinary vacuum system;'the vacuum pump is controlled by a vacuum regulator which cuts in when the vacuum drops to the lowest point desired and cuts out when it has been increased to the highest point, these points being varied to suit the particular system or operating conditions. In addition to this vacuum control, a float control is included which will start the pump whenever sufficient condensate accumulates in the receiver, regardless of the vacuum on the system. -A selector switch is usually provided to allow operation at night as a Condensate pump only, also to give manual or continuous operation when desired.