804 CHAPTER 31 1958 Guide Table 5. Ratio of Pressure Loss to Branch Velocity Pressure Take-off Angle 90-deg 60-deg 45-deg Ratio op Velocity in Branch to Velocity in Main Duct 0.4 0.6 0.8 1.0 1.5 2.0 3.0 6.5 3.1 2.0 1.5 0.95 0.74 0.62 5.0 2.2 1.3 0.77 0.47 0.47 0.58 3.5 1.3 0.64 0.43 0.40 0.45 0.54 LOSSES DUE TO AREA CHANGES Area changes in ducts, generally unavoidable, are necessitated frequently by the building construction or changes in the volume of air carried. Ex perimental investigations12-131415 of pressure changes, and pressure losses at changes of the area of duct cross sections, indicate that the excess pres sure loss over the normal friction loss is a dynamic loss due to a faster stream expanding into a slower stream, as determined by the actual areas occupied by the flow rather than the areas of the duct. No perceptible dynamic loss is due.to the converging of the air stream itself where the flow is contracted, but the air stream continues to converge beyond the edge of the contraction and. reaches a minimum at the vena contractu. For contraction, therefore, the dynamic loss is caused by expansion from the vena contracta to the full area following the contraction. Abrupt contraction in area may therefore be considered as a special condition of. abrupt enlargement. Fig. 11 illus trates (a) abrupt enlargement and (b) abrupt contraction. For a sudden symmetrical enlargement, a. theoretical expression for the loss is B, (8) where Ha = pressure loss due to sudden enlargement, based on standard air, inches of water. ' Ti = velocity of standard air in the inlet duct, feet per minute. Ft = velocity of standard air in the outlet duct, feet per minute. Ai -- area of the inlet duct, square feet. A z = area of the outlet duct, square feet. Ci = loss coefficient based on area Ai . C2 = loss coefficient based on area Ai . For a gradual symmetrical enlargement, Equation 8 changes to M2 4005/ (9) At A, _JS^== ... * f-AC s VENA 1 A* 1 Fig. 11. Aib Flow at Abrupt Enlargement or -Contraction of Air Stream Air Duct Design 805 where - ! = pressure loss due to gradual enlargement, inches of water. C, = coefficient of loss, as ratio of loss to loss for abrupt expansion,, dependent upon the total angle included between the sides of the duct. The loss for a sudden symmetrical contraction can be expressed as .'\4005/ \4005/ = \-i005/ .. . (10) where Hc = pressure loss due to sudden contraction (Fig. 10b). Co = loss coefficient based on orifice area A o. Vo = velocity of air through oyifice, feet per minute. The loss for a gradual symmetrical contraction can be similarly expressed - c-(ss)' where the coefficient of loss, Ct, depends on the included angle of the sides of the duct and the sharpness of the edges at the junction of taper to follow ing duct section. DUCT DESIGN The following discussion refers to ducts for commercial and industrial heating, ventilating, and air conditioning systems of the central station .type. The design procedures given yield the static pressure required to. overcome the resistance of the ductwork, including the supply outlets and return intakes. The fan selected for the duct system must not only pro duce this pressure but also the additional pressure required by the central equipment such as washers or spray chambers, heating or cooling Coils, and filters. Pressure losses of these components should, be obtained from, the manufacturers' catalogs. Special duct design procedures for heating ducts used in residences can be found.in Chapter i9, Warm Air Heating Systems. The design of ducts in industrial exhaust systems is discussed in Chapter 45. General rules which should be followed in tbe design are; , 1- The air should be conveyed as directly as possible at the permissible.velocities to obtain the desired results with minimum noise and greatest economy of power, material and space. sudd u<^en changes in the direction or velocity of the air should be avoided. When uaden .changes are necessary at bends; turning vanes.should be used to minimize the pressure loss. diverging transition pieces should be made as gradual as practicable. As ther^f m *"e setion on area changes, losses in abrupt enlargements are high and en, elore such transitions should be avoided. The included angle of divergence for .lu/jment should not exceed 20 deg. Losses in contractions are low but the in- ea angle, of convergence should not be greater than,60 deg. rectarY?1'6 the greatest air carrying capacity per square foot of sheet metal is desired, "gular ducts should be made as nearly square as possible. Aspect ratios (ratio