Document RpYoV4Gm3nYvORnKy83N5J067

American Society of Heating and Ventilating Engineers Guide, 1932 520 and 545 Btu per cubic foot, with an average of 535. A given heat value may be maintained and yet leave considerable latitude in the com position so that as distributed the composition is not necessarily the same in different districts, nor at successive times in the same district. There are limits to the variation allowable, because the specific gravity of the gas depends on the composition, and too great a change in the specific Table 5. Representative Properties of Gaseous Fuels, Based on Gas at 60 F Gas Btu per Cu Ft High (Gross) Low (Net) Gravitt, Air = 1.00 FOR COMBUST- ' TION, (Cu Ft) Products of Combustion Cubic Feet Total COt H*0 with Nt Per Cent COt Dry Baas Theoretical Flame Tem perature, (deg Fahr) Natural gas-- Mid-Conti nental 967 873 0.57 9.17 0.97 1.92 10.2 11.7 3580 Natural gas-- Ohio 1130 1025 0.65 10.70 1.17 2.16 11.8 12.1 3600 Natural gas-- Pennsylvania 1232 1120 0.71 11.70 1.30 2.29 12.9 12.3 3620 Retort coal gas ,575 510 0.42 5.00 0.50 1.21 5.7 11.2 3665 Coke oven gas 588 521 0.42 5.19 0.51 1.25 5.9 11.0 3660 Carburetted water gas 536 496 0.65 4.37 0.74 0.75 5.0 17.2 3815 Blue water gas 308 281 0.53 2.26 0.46 0.51 2.8 22.3 3800 Anthracite pro ducer gas 134 124 0.85 1.05 0.33 019 1.9 19.0 3000 Bituminous producer gas 150 140 0.86 1.24 0.35 0.19 2.0 19.0 3160 Oil gas 575 510 0.35 4.91 0.47 1.21 5.6 10.7 3725 gravity necessitates a change in the adjustment of the burners of small appliances. , Combustion of Gaseous Fuels Table 5 shows that a large proportion of the products of combustion when gas is burned, may consist of water vapor, and that the greater the proportion of water vapor, the lower the maximum attainable CO2 by gas analysis. The table also shows that a low calorific value does not neces sarily mean a low flame temperature since, for example, natural gas has a theoretical flame temperature of 3600 F and blue water gas of 3800 F, although it has a calorific value less than one-third that of natural gas. The quantity of air given in Table 5 is that required for theoretical combustion, but with a properly designed and installed burner, the excess air can be kept low. The division of the air into primary and secondary is a matter of burner design and the pressure of gas available, and also of the type of flame desired. All the air can be made primary, and by proper pre-mixing of the gas and air the flame can be made short. 264 Chapter 16--Fuels Gas Heating Appliances For information on gas heating appliances, refer to Chapter 19. FUEL REQUIRED FOR HEATING1 An estimate of the fuel which will be required for a heating season requires a knowledge of the total heat requirements of the building and an assumption of the average efficiency of utilization of the fuel. The accuracy of the estimate will depend on the ability to predict these values and on the care taken in making allowances for factors of operation not covered by the general formula. The fuel requirements are given by the following general equation: P -- X 6 (a) X N (l - ta) X C X E where F = quality of fuel required for a heating season. N = number of hours of heating season corresponding to average temperature, <at -- inside temperature, degrees Fahrenheit. ' <a = average outside temperature, degrees Fahrenheit. la -- outside design temperature, degrees Fahrenheit. H = calculated heat loss of building based on outside temperature of to, Btu per hour. C = Calorific value of one unit of fuel, the unit being the same as that on which F is based. E = efficiency of utilization of fuel, per cent. Hourly Heat Loss, H The hourly heat loss (H) is equal to the sum of the transmission losses (7/t) and the infiltration losses (Hi) of the various rooms or spaces to be heated and the total equivalent heating surface required is equal to sq ft. In estimating the fuel consumption of a building of more than one room divided by walls or partitions, it is not correct to use the calculated heat loss of the building without making the proper allowance for the fact that the heating load at any time does not involve the sum of the infiltra tion losses of all of the heated spaces of the building but only part of the infiltration losses. This is explained in Chapter 4. It is sufficiently accurate in most cases to consider only half of the total infiltration losses of a building having interior walls and partitions, and the value of H in Equation 1 would, under these conditions, be equal to H' Ht + -py . If a building has no interior walls or partitions, whatever air enters through the cracks on the windward side must leave through the cracks on the leeward side, and only half of the total crack should be used in computing the infiltration for each side and end of the building. Under these conditions it is sufficiently accurate to use the total calculated heat loss (i7) for the building: *For further information on this subject see Estimating Fuel Consumption, by Paul D. Close, Heating, Piping and Air Conditioning, May; 1931. 265