TECHNICAL DATA SHEET MCS-1865 AND MCS-1866
TRANSFORMER FLUIDS
Mqsnz co^f
Mo. ic/i-'c' - ,j~7 (DA.TL: mo./yA)
Fluids for use in liquid-filled transformers should have high dielectric strength, wide operating temperature range, good heat transfer properties, chemical stability
* and be fire resistant. MCS-1865 and MCS-1866 were developed to provide such characteristics, and are suggested for evaluation as dielectric fluids for transformers.
MCS-1865 and MCS-1866 do not contain polychlorinated
biphenyl (PCB). nor--sili-cone --frJ.uids..^ Both MCS-1865 and
MCS-1866 are synthetic hydrocarbons combined with trichloro --
Jbenzene to give the desired viscosity level - These fluids
have a considerable degree of fire resistance, but are not
equivalent to askarels in this general characteristic.
Technical data on typical laboratory samples are to develop furTntv
given below. Additional studies are underwayAand
data,
--wil.3 bp supplied -lab&g? Samples are available for preliminary
evaluat ion._______ ____________ __
_____
standard
disclaimed
clause, C^oxe.o)
RESISTANCE 0 licLAiMt/i (6OXS0)
Monsanto (log-d^ Mic, ftpofiess line.
DSW 306271
STLCOPCB4069667
typical OATA ...........................
-18 6 5
ELECTRICAL PROPERTIES &
Dielectric strength (ASTM D877) 25C, 0.1 inch gap
>50 KV .
Impulse Strength
Power Factor, 100C, 60 Hz (ASTM D924)
>120, <160 KV
0.11%
Dielectric Constant, 100C, 60 Hz (ASTM D924)
2.56
Gassing Tendency (ASTM D2298)
9.5 ml/min.
MCS-1866
42.1 KV
0.01%
2.74 41.2, 31.7 ml/
min-
FIRE RELATED PROPERTIES & Flash Point (ASTM D92) Fire Point (ASTM D92) Auto Ignition Temp., (ASTM D2155) Oxygen Index
315F.(157C) None to b.p. OlO'Flioo'O) 750F(399C)
18.3
3 I O'F (1 s
None to b.p. 800F(42 7 C)
17.1
PHYSICAL PROPERTIES#
Specific Gravity @ -30C -15 C 0C 25C 50 C 100C 150C
Coefficient of Exp., ml/ml,C
1.027 1.016 1.005 0.987 0.970 0.933 0.895
0.000750
Viscosity, @ -40 C
-30C -15 C
0C 25 C 50C 100C 150C
cs.
DSW 306272
19,620 5, 119 1,040 306 69.5 24.4 6.44 2.88
1.088 1.076 1.065 1.045 1.026 0.988 0.948
0.000761
1830 426 140 37 14.7 4.50 2.18
*This data is based upon samples tested in the laboratory and is not cmaranteed for all samples.
STLCOPCB4069668
Pour Point (ASTM D97)
Temperature C at which Vapor Pressure is:
1 Torr 10 Torr 100 Torr 760 Torr
Specific Heat, @ 25F 50F 100 F 150 F
BTU/lb.
Thermal Conductivity BTU/ft., hr. @ 25F 50F 100 F 150F
MCS-1865 -50F(-45C)
MCS-1866 -50F(-45C)
58 104 169 248
49 96 161 240
0.412 0.430 0.466 0.501
0.390 0.406 0.438 0.470
0.0785 0.0771 0.0744 0.0716
0.0744 0.0729 0.0702 0.0675
MATERIALS COMPATIBILITY
Extensive compatibility testing has not been completed.
However, it is expected that those materials which are used with
askarel transformer fluids will also be compatible with MCS-1865
and MCS-1866. It is recommended that compatibility tests be conducted
between the fluids and samples of the specific material to be used
under conditions simulative of actual use. A good procedure for such
testing is ASTM 3255, Method for Investigating the Compatibility of
Transformer Insulation and Construction Materials in Askarels.
HAWBLI-M3 -tRECAtTIOWS-
DSW 306273
(A hailing prnnnt-inw<--ts--currctttly being piepaltiJ by the-Medieal
Bepartmcnt and will be addo4 to
bulletin bafmro it i3 printed).--------
Monsfinto