CHAPTER 25
1948 Guide
usual coils for conlfort installations, this does not occur unless the evapo
rating temperature at the coil outlet is about 20 to 25 F. The exact value
depends on the design of the coil and the amount of loading. Although it
is not. customary to choose coil. and condensing units to balance at low
temperatures at peak, loads, there is. .danger of this occurring when the
load decreases. This is further aggravated if a by-pass is used so that
less air is. passed through .the coil at light, loads. It may be .even worse if
the control is arranged for decrease of inside temperature with fall of that
outside.. Freezing can.be avoided by.making the full load balance a-.high
evaporating temperature and checking: the balance at the minimum
load.
,
i
Care should:be exercised in the design of humidity control to minimize the cycling of; the refrigerating compressor because of re-evaporation of moisture from the fins. It is sometimes necessary to by-pass air around a coil when the compressor is not-operating* ..
REFERENCES
*-A.'S.H.V.E. Code for Testing Radiator, (A.S.H.V.E. Tkxnsactions, VoL 33.1927, p. 18).
--A.S.H.V.E; Standard Code for Testing and Rating Concealed Gravity Type Radiation (Steam), (A.S.H.V.E. Transactions, Vol. 37. 1931, p. 367); (Hot Water), (A.S.H.V.E. Transactions. Vol. 39. 1933, p. 237). (See also A.S.H.V.E. Transactions, Vol. 41.1935, p. 38. and Vol. 42.1936, p. 29).
--A.S.H.V.E. Research Report No. 998--Factors Affecting the Heat Output of Convectors, by A. P. Kratz, M. K. Fahnestock, and E. L. Broderick (A.S.H.V.E. Transactions. VoL 40, 1934, p. 443).
--Factors Influencing the Heat Output of Radiators, by A. C. Davis, W. M. Sawdon and David Dropkin (A.S.H.V.E. Transactions. Vol. 42, 1942, p. 185) and Cornell University, Engineering Experiment Station Bulletin No. 29, April. -1942.
*--Heat Emission from Radiators, by K. F. Rubert (Cornell University, Engineering Experiment Station
Bulletin No. 24, 1937).:
v .t
--*C1* o3m* p*arative Tests of Radiator Finishes, by W. H. Severas (A.S.H.V.E. Transactions,, Vol. 33, 1927, p. 41).
7--Heat Loss from Direct'Radiation, by J. R. Allen (A.S.H.V.E. Transactions, Vol. 26.1920, pi 11).
--Heat Output of Concealed Radiators, by E. A. Allcut (University of Toronto, School ofEngineering, Research Bulletin No. 140, 1933).
--The Heating Effect of Radiators, by Charles Brabble (A.S.H.V.E. Transactions, Vol. 33. 1927,
P.33). .
.
.,
1 University of Illinois, Engineering,Experiment Station Bulletins Nos. 192 and 223. and Investigation of Heating Rooms with Direct Steam Radiators Equipped with Enclosures and Shields, by A. C. Willard, A. P. Kratz, M. K. Fahnestock and S. Konzo (A:S.H.V.E. Transactions, VoL 35,1929, p. 77).
*i--A.S.H.V.E. Research Report No. 962--The Application of the Eupatheoscope for Measuring the Performance of Direct Radiators and Convectors in Terms of Equivalent Temperature, by A. C. Willard, A. P. Kratz and M. K. Fahnestock (A.S.H.V.E. Transactions, Vol. 39,1933, p. 303).
. . 1 *"The Kata Thermometer--Its Value and Defects, by W. J. McConnell and C. P. Yagloglou. (Reprint No. 953 from U. S, Public Health Service Report, pp. 2293-2337, September 5, 1924).
> Thermo-Integrator--A New Instrument for the Observation of Thermal Interchanges, by C.-E. A. Winslow and Leonard.Greenburg (A.S.H.V.E..Transactions, Vol. 41, 1935, p. 149),
14--The Calibration of the Thermo-Integrator, by C.-E. A. Winslow, A. P. Gagge, Leonard Greenburg I. M. Moriyama and E. J. Rodee. (The American Journal ofHygiene, Vol. 22, No. 1, July, 1935. pp. 137-156)
**--The Globe Thermometer in Studies of Heating and Ventilation, by T. Bedford and C. G. Warner. (The Journal of Hygiene, Vol. 34, No. 4).
1 --A.S.H.V.E. Research Report No. 1067--The Cooling and Heating Rates of a Room with Different Types of Steam Radiators and Convectors, by A. P. Kratz. M. K. Fahnestock and E. L. Broderick (A.S.H.V.E. Transactions, Vol. 43, 1937, p. 389).
*7--University of Illinois, Engineering Experiment Station Bulletin No. 230, p. 20.
*--Reheating by Means of Refrigerant Compressor Discharge Gas, by S. F. Nicoll (A.S.H.V.E. Trans actions, Vol. 47, 1941, p. 239). .
Chapter 26
UNIT HEATERS, UNIT VENTILATORS, UNIT HUMIDIFIERS
Definitions; Unit Heaters: Classification, Application, Outlet Velocities, Ratings for Various Types, Temperature, Automatic Control, .Location, Piping Connections; Boiler Capacity for Steam
, Unit Heaters; Unit Ventilators: Ratings, Applications, Location, Exhaust Vents; Window Ventilators; Unit Humidifiers
DESCRIPTIONS of heating, cooling, ventilating, humidifying, arid dehumidifying systems are given in other chapters. This chapter deals with unit heaters, unit ventilators, and unit humidifiers. Cooling units, unit air conditioners, and attic fans are described in Chapter 36.
Definitions
The generally accepted meaning of the word unit in the terrris unit heaters, unit ventilators, and unit humidifiers is that of a factory made, encased assembly of the functional elements indicated by its name. Such units can be shipped' complete or in sections so that the only field work necessary is the assembling of the sections, providing proper sup ports and connecting the unit to sources of heat (or fuel), power and water supply, and, if necessary, to vent pipes for combustion gases.
The term unit heater denotes an assembly of elements whose principal function is heating. The essential elements of a unit heater are a fan and motor, a heater, a housing, and outlet vanes or diffusers,
The term unit ventilator denotes an assembly whose principal function is to ventilate.: It may serve to circulate air within the space,'or to intro duce air from without the space, or may accomplish both purposes. The essential elements of a unit . ventilator are a fan and motor, a heater, a set of dampers, a housing and outlet vanes or diffusers.
The term unit humidifier denotes an assembly of elements whose principal function is to humidify. The essential element of a unit humid ifier is an atomizer or evaporator. To this may be added'a fan, a heater, outlet vanes or diffusers, and a housing to enclose the various parts.
Classification
UNIT HEATERS
The various types of unit heaters which are at present available can usually.be classified according to one of the three following methods:
1. By type of heater. Under this classification there are three types of heating elements to be considered: (a). the steam or hot water type, (ft) the electric type, and (c) the direct fired type which may be gas, oil, or coal fired.
2. By type offan. Under this classification there are two types of fans to be considered: (a) the propeller type1 which may be equipped with a horizontal or vertical shaft, and (b) the centrifugal type which may be designed for horizontal or vertical blow. .
3. By arrangement of elements. Under this classification there are two types of heaters to be considered: (a) the draw-through type, in which the