Document Rj31xVL7owkOmr7vp2oxL6Mx8
756
CHAPTER 70
through the system before returning, at the risk of machine failure. Normally, however, the system should be designed, using pump dowD control or crankcase heaters, so that Liquid absorption in the crankcase is kept to a minimum.
2. In systems using flooded evaporators, where refrigerant bleed-off is necessary for oil removal from the evaporator. Oil separators used on these systems remove a substantial portion of the oil in the hot gas discharge line, and this makes it possible to operate with much less bleed-on from the flooded cooler than would otherwise be necessary to keep the oil concentration down in the cooler. For widely varying loads, or low tempera ture applications, they appear to be useful. For steady loads at air conditioning level they are seldom used.
3. In direct expansion systems using coils or tube bundles that require bottom feed for good liquid distribution and where re frigerant slop-over it essential from the top of the evaporator for proper.oit removal. In the same manner as in the preceding para graph, the use oif an oil separator'here wih suMtantiany'cut down on the amount of slop-over necessary from the evaporator in order to return oil.
4. In low temperature systems. It is advantageous to have as little oil as possible going through the low side, especially in Refrigerant 13 systems where the oil is not miscible with the refrigerant.
Potential problems. In applying oil separators in refrigera
tion systems there are certain potential hazards which must
be fully recognized and properly dealt with. 1. The main hazard to guard against in the use of oil sepa-`
rotors is their tendency to condense out liquid refrigerantduring compressor off cycles and on compressor start-up. This is true if the condenser is in a warm location, such as an evapora tive condenser and receiver on a roof.
During the off cycle, the oil separator cools down and acta as a condenser for liquid refrigerant that evaporates in warmerparts of the system. Thus, a cool oil separator will act-as a. liquid condenser during off cycles, and also upon compressor start-up until the separator has warmed up, and will auto matically drain this condensed liquid into the compressor crankcase. On start-up, then, there is excessive boiling in the crankcase because of the presence of a large amount of liquid refrigerant. Hus will result in poor lubrication and wear on the compressor, and may even end up in completely cleaning the' oil out of the crankcase as a result of this violent boiling action. Then, if not protected by an oil safety switch, compressor failure may result.
2. Oil separators are not 100 percent efficient and therefore, it is still necessary to design the complete system for oil return to the compressor.
3. The float valve is a mechanical device which may stick open or closed. If it sticks open, hot gas will be continuously bypassed to the compressor crankcase and this will cause the compressor to operate at an elevated temperature and will, of course, reduce capacity. If the valve sticks closed,'then, of course, no oil is returned to the compressor.
Precautions. Where oil separators are used, it is recom
mended that precautions be taken to prevent draining con
densed refrigerant into the crankcase. To minimize this possi
bility, the drain connection from the oil separator can be
connected into the suction line entering the compressor. In
this way, any liquid refrigerant returning from the separator
would go into the suction manifold rather than directly into
the crankcase. This drain line should be equipped with the
following: shut-off, hand throttling, and solenoid valves, and
sight glass. The throttling valve should be adjusted so that
the flow through this line is very small, in fact only a little
greater than would be normally expected for the return of oil
through the suction line. The use of the sight glass will help in
adjusting this flow. The solenoid valve should be wired so
that it is open only when the compressor is running; closed
when the compressor is off.
The above arrangement will prevent liquid draining down
into the compressor during an off cycle. When the compressor
starts up with liquid refrigerant in the oil separator, it will
also prevent this liquid from dumping directly into the crank
1962 Guide And Data Boot
case. It will show it to be bled slowly into the suction lin
where it can be taken care of in the normal manner ainiik
to oil returning from the system.
'
The hazard of draining condensed refrigerant into tk.
crankcase can also be minimized by insulating the oil arator and installing it ahead of a hot gas loop to the floor^!
that there will be a trap between it and any evaporative condenser installed above. Insulating the oil separator keen, it warm for a longer period after shutdown of the compress and cuts down on the amount of condensation in the shell during shutdown, unless it is for a prolonged period. One manufacturer returns oil from an oil separator through an oil reservoir which is heated, boiling off the refrigerant into the suction line.__
Surge Drums or Accumulators
The above names are alternately used to describe the same piece of equipment.
A surge drum is required on the suction side of
^
flooded evaporators to prevent liquid slop-over to the com.
pressor. The exceptions are shell-and-tube coolers and aimiinr
shell-type evaporators which provide ample surge space above
the liquid level, or contain eliminators for the separation of
gas and liquid. A horizontal surge drum is sometimes used where head room is limited.
Figs. 34 and 35 illustrate application* using a horizontal
surge drum.
The drum may be designed with baffles or eliminators to
separate liquid from the suction gas returning from the top
of the shell to the compressor. More often there is simply
allowed sufficient separation space above the liquid level
for this purpose. Such a design is usually of the vertical type
with a separation height above the liquid level of from 24 to
30 in. and with the shell diameter sized to keep the suction
gas velocity at a value low enough to allow the liquid droplets
to separate and not be entrained .with the. returning suction
gas off the top of the shell.
Since these vessels are also oil traps it is necesary to pro
vide oil bleed arrangements (Figs. 34 and 35), to keep a mini
mum oil concentration in the surge drum and flooded evap
orator, and continuously return oil to the compressor.
Compressor Flood-Back Protection
In most air conditioning and refrigeration systems it is possible to control the refrigerant feed so that liquid refrig erant does not return to the compressor during operation.
Some systems, by reason of poor expansion valve opera tion, sudden changes in loading, etc., periodically return liquid refrigerant to the compressor, although not in sufficient quantities to do real damage.
There are certain systems, however, which by their very design will periodically flood the compressor with excessive amounts of liquid refrigerant. Principally, these are systems in which there is a periodic reversal of the refrigerant cycle to: (a) provide hot gas defrosting of an evaporator, (6) furnish heat for release purposes in ice-making apparatus, or (c)
change from cooling to heating cycle, or vice versa, in heat pump systems.
These systems are almost identical in operation and effect on the compressor. Consider an air source beat pump for a typical analysis of what happens. The flood-back occurs when reversing the cycle, in either direction. During the cooling cycle the outdoor coils act as condensers and have warm liquid continually draining from them. Also the lines to which the thermal expansion valve bulbs are strapped are now hot
' '^ Waerant Piping Systems for Refrigerants 12, 22 and 500
757
U '.ilgpes and are hot. When the cycle reverses to a heating ^\the outdoor coils change from condensers to evaporators.
liquid that has been draining from them, during the conScte! cycle, is now dumped into the suction line. Of even SSer significance, the thermal expansion valves also open fEls the result of their bulbs being on warm lines (those rSwere previously hot gas lines). These valves will there-
Zijlbod through until control is re-established at the bulbs. ^ total of thoftp two effects constitutes a substantial liquid
^jjiack through the suction line. --When there is no way to control the hazard- of periodic <uod-back of substantial proportions through the suction fag-jt is necessary to t*lf<> measures to protect the compressor
^inst it. Otherwise compressor life will be materially
Aortened.
"
most satisfactory method appears to be a trap arrange-
catches the liquid flood-back and may do one ofthe
following: (1) meter it slowly into the suction line when it is duaned up with a liquid-suction heat interehanger, (2) evapo-
jsiej the liquid 100 percent in the trap itself and auto
matically return oil to the suction line; or (3) return it to the
ttoover or one of the evaporators: (The latter is used in am
monia systems only because of the no-oil-return feature.)
- Fig. 39 illustrates an arrangement which will handle mod-
gate liquid flood-backs, getting rid of the liquid by a com
bination of boiling off in the exchanger plus a limited bleed-off
into the suction line. This device, however, would not have
p.ffirwnt trapping volume for most heat pump jobs or hot gas
(frfrofit systems employing reversal of the refrigerant cycle.
For heavier periodic flood-backs a larger volume is re
quired in the trap. The arrangement shown in Fig. 41 has been
employed successfully in reverse cycle type heat pump jobs
fang: Refrigerants 12 and 500. It consists of a suction line
fiH-nmnlfttnr with sufficient volume to hold the maximum
apected flood-back and of large enough diameter to effect
liquid separation from the suction gas. The trapped liquid is
dmriy bled off through a controlled drain line into the suc
tion line, where it is boiled off in a liquid-suction heat inter-
changer, between cycle reversals. A proprietary derice is available for preventing liquid slugs
from returning to the compressor. Liquid returning in the suction line is trapped out in the upper part of the shell, while the gas returns to the compressor through the outlet connec tion at the top. The liquid, together with any oil that is mixed with it, falls by gravity through the inner tube of the heat exchanger section below the separator plate. This inner tube is orificed and sized so the refrigerant passing through it will be 100 percent vaporized before returning to the suc tion line. The design also requires that the refrigerant gas velocity through this heat exchanger tube be sufficiently high to entrain oil and return it to the suction line. Warm liquid from the condenser is routed through the lower part of the shell to provide the source of heat for vaporizing any liquid in the heat exchanger tube.
Refrigerant Driers'
The effect of moisture in refrigeration systems is discussed in Chapters 59 and 61 of the 1961 Guide And Data Book.
The use of a permanent refrigerant drier is recommended on most systems using Refrigerants 12, 22, and 500. It is a must on all low temperature systems, including those using Refrigerant 13.
The decision of whether or not to use a permanent drier on the higher temperature systems is one of judgment. In the case of package type air conditioners and water chiilere it may not be necessary if proper dehydration techniques have been followed at the factory, no refrigerant connections are broken in the field,and anyrefrigerant added is ata sufficiently low moisture content If there is any doubt that the system is initially free of moisture, or that the system can be main tained dry in operation, then a drier is indicated for protec tion of the compressor and to prevent freezing at the liquid
feed device. In the cfl-yi of hermetic compressors there is an additional
reason for keeping moisture out of the system. The motor windings are exposed to the refrigerant gas and excessive moisture can cause breakdown of the motor sanding insula tion possibly resulting both in bum-out of the motor and the distribution of the products of decomposition throughout the refrigeration system,
A full flow drier is usually recommended in hermetic com pressor systems to keep the system dry and to prevent the products of decomposition from getting into the evaporator in the event of a motor bum-out.
Side outlet driers are preferred Bince the drying element can be replaced without breaking any refrigerant connections. The drier is usually located in the liquid line near the liquid receiver. It may be mounted horizontally or vertically with the flange at the bottom, but should never be mounted ver tically with the flange on top since any loose material would then fall into the line when the drying element is removed.
A three-valve bypass is usually used as shown in Fig. 42 to provide a mpana for isolating the drier for servicing and to allow only partial refrigerant flow through the drier, in many
yging open type compressors, to reduce pressure drop and allow smaHpr drier selection in those cases. In systems using hermetic compressors, it is preferable to have all re frigerant going through the drier at all times for the reasons
given previously. The refrigerant charging connection should be located be
tween the receiver outlet valve and the liquid line drier so that all refrigerant added to the system will pass through the
drier. Reliable moisture indicators are now on the market for in
stallation in refrigerant liquid lines. These devices will in-