American Society of Heating and Ventilating Engineers Gun,
the quantity of air introduced, or with valves or dampers which
' the heat output from local heaters such as radiators. Usually thV^ ttrrooll iiss aa combination of both volume control arid of air tempera control.
hirgj
In installations for auditoriums and theaters the requirement '
different from those in factories, since there must be a conside g*
volume of air circulated in order to provide ventilation and cooling
mois__tu_r_e__c_o--nte_n_t of this aanir mmuuosLt buee rreellaattiivveellyy ccoonnssttaanntt,, bbuutt iittss tteermn ri 'v| ture must be variable. A satisfactory solution of this oprohbllpeTMm hla,,s nPt6*1*33'difficult, but special systems of control are now in general use
pe..r..m.. i.t the t.e..mluppeuraatiuurice aannud nhuuimniiadiittyy ooif tthheeaatteerrss ttoo bbee ccoonnttrroolllleeddIjnJiHpll pendently and at the same time, to be immediatelvy reessrpwo-mnsive to ch. amnQo('Ms-
in occupancy. Some of these arrangements are successful in operatm^
without the use of any external heat whatever,
n
REFRIGERATING MACHINES
The refrigerating machine with which the heat is removed from the air consists of three essential parts, the evaporator, the compressor and the! condenser. There are, of course, many valves, accessories and device; each peculiar to the several different types of machines and necessary $ their proper operation.
In the evaporator, or cooler, a pressure is maintained which causes thfl refrigerant to evaporate or boil at a sufficiently low temperature to absorb! heat from the water, air or other medium in contact with the coolingf surface. Various devices such as separators, accumulators and eliminators^
are required to remove any entrainment of liquid from the gas leaving the cooler. Liquid refrigerant must be fed to the cooler at the same rate atji
which it is evaporated so as to maintain an approximately constant level.; Various manual and automatic valves are available for this purpose.
Many different types of coolers are available. Probably the earliest^ design was the open Baudelot which consisted of a number of super-
imposed pipes over which the water to be cooled flowed from a carefully leveled flooding trough carried just above the uppermost pipe. Drip strips
were required to prevent an unnecessary loss by splashing from the pipes. For extremely small tonnages such a cooling surface might be submerged,
but with a submerged cgil the rate of heat transfer will vary over a wide if
range, depending upon the agitatiqn of the water.
v
.Where proper protection against freeze-ups can be provided enclosed " coolers of either the shell and coil or the shell and tube type may be used to simplify water handling problems. Ifi many cases the loss of consider able static head can be avoided by the use of a closed cooler.
Good practice calls for a drop in water temperature ranging from the minimum of about 6 deg to a maximum of 10 deg, the lesser change in
water temperature requiring a correspondingly greater volume to be pumped and carried through pipes. A mean difference between water temperature and refrigerant temperature of 7.5 to 15 deg is satisfactory'. The temperature at which heat must be received by the refrigerant is therefore determined by the mean water temperature and the mean effec tive temperature difference.
464
Chapter 29--Air Conditioning of Buildings
h as the latent heat per pound of refrigerant is approximately
jPu
the narrow range of temperature which is utilized in
and the volume of gas per pound of refrigerant increases
^^ Mlv as the temperature and pressure is reduced, the temperature iif^'^efrigerant determines the volume of gas which must be handled
^aS'emnpSfierogrsinsopre.rformed by the compressor is that of withdrawing the yhe Iuefrj,,erant from the cooler and delivering it to the condenser at
P^iv^nressure that its heat can be absorbed by water at ordinary temand tflPgas recondensed into a liquid ready to be returned to
PfEp!1| yf]e construction of condensers follows along the same general jjj'at 0f coolers. The atmospheric type in which the latent heat of
-^risiderable amount of evaporation is added to the sensible heat abJ^tion ky the water is almost identical with the Baudelot. Shell and fPhe condensers are almost identical with the coolers. The double pipe ^tenser in which the cooling water is passed through the inner of two HSceiitric pipes with the refrigerant in the annular space is quite comHfnlv used. It is important in designing and locating condensers to mlltfadequate provision not only for cleaning but also for the removal
(^replacement of the tubes or complete sections. The condenser water must receive and carry away all of the heat abs&rfed in the cooler, plus the heat equivalent of the power used in driving Uie Compressor, with slight corrections for radiation direct from the com pressor and from gas transmission lines between the compressor and the
c"^oTndweonsteor.three gallons of water per minute per ton of refrigeration will rise approximately 15 to 10 deg in passing through the condenser. Good practiceTcalls for a condensing temperature not more than from 3 to 8 deg above the final temperature of the condenser water. The power required to drive the compressor is approximately proportional to the difference be-
Itryeen the condensing temperature and the evaporating temperature so fhat it is obvious that by increasing the investment in cooling and con-
,&dising surface the operating cost may be reduced. [There are two types of compressors in use in large plants, the positive-
"iteplacemeni type and the centrifugal. Of the former there are two general
Jypes' the reciprocating and the rotary. SK5
SYSTEMS OF AIR DISTRIBUTION
.In systems of air conditioning, the method of air distribution, as well
vas the practical details of design are of utmost importance. ^In an installation where exact relative humidity control is required, uniform temperature conditions are very important, because a variation 'in relative humidity will be caused by any variation in temperature. .^Moreover, the air is usually admitted, especially in summer, at tem.peratures lower than that of the room in order to effect the necessary [cboling. Therefore, the air must be distributed uniformly, not with jespect to floor space but with respect to the amount of heat to be absorbed in the various portions of the room. Thus it is necessary for the air
.conditioning engineer to have fairly exact information as to the distribu--
465