CHAPTER 9
1954 Guide
3. From G to D': Two paths, (a) through 2j in. of tie rod, and (6) through 2j in.
of insulation.
'
4. From D to E: Two paths, (a) through 1 in. of tie rod, and (b) through 1 in. of
'c'on5c.rFetreo.m E to F: One path through 3 in. of concrete. . . It will'be noted that items 2 and 4 are paths of similar flow, and could be treated > as,one. If equilibrium or steady state heat transfer is assumed, there will exist a , temperature difference between the metal tie rod and the concrete, and also between
the metal tie rod and the insulating material. The rate of heat transfer between these materials is dependent upon their conductivity values and the temperature difference. As the conductivity of the metal tie rods is considerably higher than that of the concrete or insulating materia], it cannot be assumed that the same rate of heat1 transfer takes place for all parallel paths. Likewise, an appreciable error would
be'niade by assuming that no heat transfer takes place between the metal tie.rod and , the surrounding materials. Although the pattern of the isotherms is unknown, the following method of calculation does partially take into;account the heat flow be
tween the metal tie rods and its bounding materials.
Parallel Flow. The conductances through the areas of parallel heat flow may be
determined as follows:
1. The area of each J-in. diameter tie rod is 0.00036 so ft, and as the tie rods are spaced 9 in. vertically, and 12 in. horizontally, there will be 0.00036 X t = 0.00048 sq ft of tie rod to each square foot of wall area. Then from plane B to plane G, the
conductance Ci is
0,00048 C, 1.0
0,99952 X|| = 0.192 + 11.994 = 12.186 1.0
2. For tie rod and insulation from plane C to plane D the conductance C, is
0.00048 400 0.99952 0.30 = 0.077 + 0.120 = 0.197 C' = ~TTXT5+ 1.0 2.5 3. For tie rod and concrete from plane D to plane E the conductance C, is
0.00048 W0 0.99952 C, "To_xio+ 1.0
12^ = 0.192 + 11.994 1-0
12.186
Series Flow. After the conductance values have been determined, the total re-
aistauce and \J value can be determined as follows:
l , *. , l
,1,2,1
+ k +c1 + c,+ c, + fe+/.
1 ,30 _i_ + JL + _I_ + H + --
Br ~ 1.65 + 12.0 + 12.186 0.197 12.186 12.0 6.0 Br = 0.606 + 0.250 + 0.0821 + 5.076 + 0.0821 + 0.250 + 0.167 = 6.513
= 0.153 Btu per (hr) (sq ft) (F deg).
The Hot Box test value, from University of Minnesota, for this wall, corrected for a 15 mph wind velocity, was U = 0.150 Btu per (hr) (sq ft) (F deg). The error between the calculated and test values would be
0.153 - 0.150 x 100 = 2 percent. 0150
If the effect of the tie rods were omitted from the calculations, the overr an U value would be 0.103. Although the percentage of area occupied by.
0.00048 X ioo = 0.048 percent* the1 tie rods per square foot of wall area is 1.0
Heat Transmission Coefficients of Building Materials
185
the error between the calculated and test values would be 0.150 - 0.103 X 100 = 31 percent. 0.150
In making the calculations for values of U shown in Tables 7 to 19, the following conditions have been assumed:
Equilibrium or steady-state heat transfer, eliminating effects of heat capacity. ' Surrounding surfaces at ambient air temperatures. Exterior wind velocity of 15 mph. Surface emissivity of ordinary building materials = 0.83. No correction for position or direction of heat flow. (Average coefficients used). Air spaces are | in. or more in width. Variation of conductivity with mean temperature neglected. Corrections for framing made on basis of parallel heat flow through 2 X 4 in. (nomi nal) studs, 16 in. on centers, the framing covering 15 percent of wall area. Actual thicknesses of lumber assumed to be as follows:
Nominal
1 in. (S-2-S)... in. (S-2-S)...
2 in. (S-2-S) 2i in. (S-2-S)...
Actual ........2| in.
Nominal
Actual
3 in. fS-2-S)................................ 2$ in. 4 in. (S-2-S)................................... . 3| in. Finish flooring, (maple or oak) . 1U in
Coefficients for frame construction are corrected for the effect of framing where such correction would increase the coefficients, but not where the correction would decrease the coefficients.11
It should be noted that the effects of poor workmanship in construction, and installation have an increasingly greater percentage effect on heat transmission as the coefficient becomes numerically smaller. Failure to meet design estimates may be caused by lack of proper attention to exact compliance with specifications. A factor of safety may be employed as a precaution when it is judged desirable. Some engineers do not use a 17value less than 0.10. n
Roof Coefficients
Computations for wood shingle roofs applied over wood stripping are based on 1 by 4 in. wood strips, spaced 2 in. apart. Values for roofs con taining Spanish and French clay roofing tile are assumed the same as for slate roofs. Values for pitched roofs in Table 17 apply where the roof is over a heated attic or top floor, so that the heat passes directly through the roof structure, including any interior finish material.
Combined Ceiling and Roof Coefficients
If the attic space between the ceiling and roof is unheated and not venti lated, the combined coefficient from room air below the ceiling to exterior air can be calculated from the followilig formula:
Rt
=
_L
U,,
+
_L
nU,
(4)
and
where U Rr
U = l/Rr
combined coefficient to be used with ceiling area, total resistance of ceiling and roof.
(5)