32--Cold Forming of Metals
Fic 32-9 --Presses must also be made safe for electricians, millwrights, pipe fitters, and others who must
maintain them in a safe condition Automotive companies have requirements similar to the following for
electrical installations on equipment
1 All motor starters, relays, etc, required for each machine must be built into a single oil-tight (NEMA Type XII) control panel, with externally operated main power disconnect mechanically in terlocked with the enclosure doors so that no door can be opened until after the disconnect has been opened
2 The disconnect operating handle must be permanently attached to the disconnecting device and must be located not more than 6'/* ft and not less than 3 ft above the floor The handle must be arranged so that it can be locked only in the off posi tion with a minimum of three locks
3 Enclosure doors must be hinged vertically, be not more than 36 in wide, and be painted "safety orange" on the inside so that an open door will be readily seen
4 The inside of the enclosure should be painted with white enamel to increase visibility for main tenance and large panels must have interior lights
5 The control circuit voltage must be 115 or 120, obtained from a transformer with isolated primary and secondary windings
6 Equipment on the control panel must be located at least 18 in above the floor and not more than 84 m above the floor Devices carrying line voltage must be grouped above or to the side and be segregated from devices such as relays and timers carrying only the control voltage Nothing may be mounted above the mam disconnect
7 All wires must be color coded as follows for easy identification of their voltage level a) AC and DC power circuits (line voltage)--Black, h) AC 115/120 v control circuits --Red, c.) DC control circuits --Blue, d) 115/120 v circuits still energized when main dis
connect is open, such as enclosure lighting cir cuit--Yellow, e) Equipment grounding conductors --Green, f) Current-carrying grounded conductors--White
that are turned on by door switches