Document RJngaZD2ReR8OQrj479rqyo5E
may receive a shock from energized electrical equipment via the water These units are not classified by a numeral because Class C fires are essentially either Class A or Class B, but also involve energized electrical wiring and equipment Therefore, the coverage of die extinguisher must be chosen for the burning fuel
Class D Extinguishers for fires in com bustible metals, such as magnesium, po tassium, powdered aluminum, zinc, sodium, titanium, zirconium, and lithium Persons working in areas where Class D fire hazards exist must be aware of the dangers in using Class A, B, or C extinguishers on a Class D fire, as well as the correct way to extinguish Class D fires These units are not classified by a numerical system and are intended for a special hazard protection only
The following recommendations are given in NFPA Standard No 10 as a guide m mark ing extinguishers, and/or extinguisher lo cations, to indicate the suitability of the ex tinguisher for a particular class of fire Ex tinguishers suitable for more than one class of fire may be identified by multiple symbols as described previously
Markings should be applied by decalcomanias, painting, or similar methods having at least equivalent legibility and durability
Where markings are applied to the extin guisher, they should be located on the front of the shell above or below the extinguisher name plate Markings should be of a size and form to give easy legibility at a distance of 3 ft
ordinary
i Extinguishers suitable
for Class A fires should be
identified by a triangle con
A taining the letter "A " If colored, the triangle shall be combustibles colored green
eELECTRICAL
EQUIPMENT
3 Extinguishers suitable for Class C fires should be identified by a circle con taining the letter "C " If colored, the circle shall be colored blue
COMBUSTIBLE METALS
4 Extinguishers suitable for fires involving metals should be identified by a five-pointed star containing the letter "D " If colored, the star shall be colored yellow
Where markings are applied to wall panels, etc , m the vicinity of extinguishers, they should be of a size and form to give easy legi bility at a distance of 25 ft
Extinguishers listed by Underwriters' Lab oratories, Inc, are rated after physical test ing These ratings, which are indicated by a numeral and a letter, define the extin guishing potential of an extinguisher be cause they specify the type and size or num ber that should be installed m a specific area
The numeral signifies the number of units of extinguishing potential and the letter(s), the' class(es) of fire on which the particular extinguisher is most effective for extinguish ment For example, a 4-A 16-B C rating signifies that the extinguisher is rated for 4 units of Class A fire-fighting potential, 16 units of Class B fire-fighting potential, and is safe to use on Class C fires in or near electrical equipment
Extinguishers labeled with pre-1956 clas sifications can be reclassified by using con version tables published m NFPA Standard No 10, Portable Fire Extinguishers
Location of units. The extinguisher must be located close to the likely hazards, but not so close that it would be damaged or cut off
FLAMMABLE LIQUIDS
2 Extinguishers suitable for Class B fires should be identified by a square con taining the letter "B " If colored, the square shall be colored red
"Note Recommended colors as described m the Federal Color Standard Number 595 are
Green -- No 14260 Red - No 11105 Blue - No 15102 Yellow -- No 13655
1093