HEATING VENTILATING AIR CONDITIONING GUIDE 1943
room thermostat regulates: the supply of steam to.the unit through a control valve in the steam supply line and the unit heater motor operation is manually controlled.
Unit heaters equipped with dampers arranged for by-passing air around the heating coils are controlled by room thermostats operating modu lating damper mptors attached to these dampers so that as the tempera tures rise, a decreasing amount of air is heated. When the by-pass is wide open the heating effect is so much reduced that control of the steam supplied to the coil is not generally important. If valve control is added, the throttling of the steam may be concurrent with, or subsequent to, the opening of the by-pass.
Cooling. Units
The recommended form of temperature control for a cooling unit con
templates the continuous operation of the fan, with automatic regulation
of the compressor or cooling coil, or both, as determined by a thermostat
in the room, or in the return air to the cooling unit. Such operation
insures continuous circulation of air in the room, and in addition to
providing the cooling effect of moving air, overcomes the tendency of the
air to stratify. . As the temperature begins to rise, the controller opens the
valve, to a cold water cooling coil, or for direct expansion coils, opens a
valve in the refrigerant line, closes a by-pass around the coil or starts
a compressor.
'
Cooling units may also be controlled by arranging.the room thermostats to start and stop the fan motors or by a combination of motor and refrigerant control.-
Unit Ventilators
There are various types of unit ventilators available but in general all types are designed to draw air from the outside or to mix outside and recirculated air, heat it and introduce it into the room under control of a thermostat.
The design of unit ventilators has to an extent been based on the
requirements for automatic temperature control and the cycles of control have been developed to include other heating devices in the rooms with unit ventilators. Unit ventilators are frequently used in schools and other types of buildings where many states have laws or regulations
governing the minimum amount of ventilation to be provided. The con
trol of the amount of; outdoor and recirculated air is designed to conform
to the various laws. Usually the device circulates a constant amount of
air and the amount automatically taken in from outdoors is controlled
in one of these ways: .
.
1. Full recirculation until the room temperature reaches a certain point, generally two degrees, below the desired room temperature; then a minimum amount of outdoor air for ventilation while the temperature is maintained by throttling steam; and if the room temperature rises with all steam shut off, the gradual increase in amount of out door air up to 100 per cent.
2. Full recirculation until the room reaches a set point below room temperature, after which all air is taken from outside.
3. Gravity recirculation while the fan motor is not running, with full outside air as soon as the fan starts, obtained by a relay in the motor circuit.
662
CHAPTER 34i ; AUTOMATIC CONTROL
4., Full recirculation or all outdoorair as determined by a manual switch which can be operated at any time whether or not the fan is running. .All the unit ventilators in a single building may be operated by one or many switches.
With arrangements 1 or . 2, it is desirable to include a relay to prevent the intake dampers from opening while the fan is not running, regardless
of room temperatures. With a dual system of control this is essential to prevent the thermostat keeping the outside damper-open until the tem perature falls to the reduced setting.
. The intake and recirculated air quantities are determined by a single damper or by a pair of dampers working together, and operated by a damper motor. Although this affects the temperature of the air delivered, the main heat control comes froth the throttling of the steam supplied to the heating coil, with or without by-pass damper control. To prevent air being delivered at too low a temperature,'a low limit thermostat is commonly installed in the air stream and set at some point between 55 and 70 F. The lower settings may cause discomfort, the higher ones overheating, depending on circumstances. The air stream thermostat can be used to turn on steam, reduce the amount of outside air, or both.
Rooms with unit ventilators frequently have auxiliary heating devices,
such as direct radiators, convectors or unit heaters, all under control of a
single room thermostat. A common control cycle for such rooms is com
posed of the following functions, assuming that 72 F is the desired
temperature:
*
1. Below 70 F the unit ventilator intake damper is in full recirculating position and all heat is turned on.
2. At 70 F the intake damper moves to a position that will admit a predetermined minimum amount of air from outdoors.
3. At 71 F the auxiliary heating devices are shut off.
4. From 71 to 72.5 F, the heating effect of the unit ventilator is throttled..
5. From 72.5 to 74 F, the intake damper is gradually moved to increase the amount of outside air from the set minimum to 100 per cent.
.6. If the room thermostat calls for too much cooling, the air'stream thermostat holds the delivery temperature at a proper minimum.
Other similar cycles may.be used. One additional feature is.the use-of an air stream thermostat that has its control point reset by the room thermostat.. Then as. the room temperature rises, the delivery tempera ture is gradually reduced from a maximum to a minimum.
All Year Conditioning Units
. It is desirable to provide for automatic change-over between the heating and. cooling!cycles in the control system for all year conditioning units because of; the probable necessity of a change several times a year. In the fall season a period requiring cooling often fallows one requiring heating, and the reverse: is true in the spring. The automatic change-over is especially valuable where a large number of units is used.;
A control system for;an all year conditioning unit providing for the automatic change-over is shown in Fig. 7. Operation .of the control equipment is as follows:
1. During the Heating Cycle. Combination controller T\ measures the temperature in the space being conditioned and opens control valve V3
~ 663 .