Document RJjbVBMK14ngqQ359vaQyxm1v

HEATING VENTILATING AIR CONDITIONING GUIDE 1943 (dollars) -j- 13,000 (Btu) X 2000 (lb) X 0.55 (efficiency) => $0,804. The total cost of heat lost per year = 0.804 X 181.6 (thousand Btu) = $146.00. (A closely approximate solution of such a problem may be made quickly by the use of the estimating chart given in Fig. 1.) Table 3. Heat Loss from Bright Copper Pipe Given One . .Thin Coat of Clear Lacquer Expressed in Btu per hour per linear fool per degree Fahrenheit between the pipe and surrounding still air at 70 F Nominal.' Pipe Size (Inches) M Y 1 lM m 2. m. 3 3M 4 4H 5 6 8 Hot Water (Type K Copper Tube) , Steam (Standard Pipe Size Pipe) 120 P 150 F 180 F 210 F 227.1 F (5 Lb) 297.7 F (50 Lb) 337.9 F (100 Lb) Temperature Difference SO F 80 F 110 F - 140 F 157.1 F 227.7 F 267.9 F 0.240 0.320 0.390 0.470 0.540 . 0.690 0.840 0.960 1.100 1.241 0.265 0.356 0.437 0.537 0.612 0.762 0.937 1.025 1.250 1.400 1.480 1.700 2.200 1.685 1.936 2.500 0.282 0.373 0.463 0.554 0.645 0.818 0.991 1.135 1.318 1.480 1.790 2.052 2.630 0.307 0.414 0.507 0.614 0.714 0.892 1.085 .1.270 1.442 1.556 1.965 2.272 2.854 0.401 0.477 0.598 0.700 0.830 1.005 1.178 1.400 1.580 1.750 1.910 2.130 2.450 3.120 0.461 0.571 0.681 0.812 0.966 1.164 1.361 1.625 1.845 2.040 2.240 2.415 2.810 3.425 0.478 0.578 0.710 0.840 .0.990 1.201 1..420 1.700 1.905 2.130 2.350 2.610 2.990 3.730 Table 4. Heat Loss from Horizontal Tarnished Copper Pipe Expressed in Btu per hour per linear foot per degree Fahrenheit ' between the pipe and surrounding sttll air at 70 F Nominal Pipe Size (Inches) Hot Water (Type K Copper Tube) Steam (Standard Pipe Size Pipe) ' 120 F . 150 F 180 F 210 F 227.1 F (5 Lb) 297.7 F (50 Lb) 337.9 F .(100 Lb) Temperature Difference H M l -m m 2 2K 3 3H A AH 5' 6 8 . 50 F . 0.250 0.340 . 0.440 . 0.500 0.580. 0.730 . 0.880 1.040' 1.180 1.460 1.600 1.840 2.400 80 F 0.2870.381 0.475 0.559 0.656 0.825 1.000 . 1.175 1.350 1.500 1.812 2.125 . 2.685 HOF 0.300 0.409 0.509 0.618 0.710 0.890 1.091 1.272 1.454 1:635 1.980 2.270 2.910 140 F 6.321 0.429 0.536 0.622 0.750 0.957 1.143 1.343 1.535 1.715 . 2.071 2.430 3.110 157.1 F 0.433 0.533 0.636 0.764 0.904 1.101 1.305 1.560 1.750 1 .941:. 2.131 2.387. 2.740 3.310 227.7 F 0.500 0.543 0.746 0.878 1.053 1.273 1.490 1.800 2.020 2.240 2.465 2.770 3.210 4.050 267.9 F 0.530 0.654 0.803 0.934 1.120 1.364 1.605 1.940 2.170 2.430 2.650 2.990 3.440 4.370 . 778 CHAPTER 43. PIPE AND DUCT HEAT LOSSES HEAT LOSSES FROM INSULATED PIPES The conductivities of various materials used for insulating steam and hot water systems are given in Table 8. They are given as functions of the mean temperatures or the mean of the inner and outer surface tem- Table 5. Radiating Surface per Linear Foot of Pipe Nominal P(iIpnechSeisz)e Ye 1 m Surface Area (Sq Ft) 0.22 0.275 0.344 0.435 0.498 Nominal Pipe Sue (Inches) 2 2H. 3 3H 4 Surface Area (So Ft) 0.622 0.753 0.917 1.047 1.178 Nominal Pipe Size (Inches) 5 6 8 10 . 12 Surface Area (Sq Ft) 1.456 11734 2.257 2.817 3.338 Table 6. Radiating Surface per Linear Foot of Copper Tubing Outside diameter Yz in. greater than nominal size Tube Size (Inches) J4 . 1 mm Surface Area (Sq Ft) 0.164 - 0.229 0.295 0.360 0.426 Tube Size (Inches) 22H 3 3H 4 Surface Area (Sq Ft) 0.556 0.687 0.818 0.949 1.080 Tube Size (Inches) 5 6 8 Surface Area (Sq Ft) 1.342 1.604 2.128 A Table 7. Areas of Flanged Fittings, Square Feet3 Nominal , Pipe Size (Inches) i m ni 2' 2H 3 3H 4 5 6 8 10 12 Flanged Coupling 90 Dkg Ell LongERlta, dius Tee Cross Standard Extra Heavy Standard Extra Heavy Standard Extra Heavy Standard Extra .Heavy Standard Extra Heavy 0.320 0.383 0.477 0.672 0.841 0.945 1.122 1.344 1.474 1.622 1.82 2.41 3.43 4.41 0.438 0.795 1:015 0.892 1.083 1.235 1.575 1.622 2.07 0.510 0.957 1.098 1.084 1.340 1.481 1.925 1.943 2.53 0.727 . 1.174 1.332 1.337 1.874 1.815 2.68 2.38 3.54 0.848 1.65 2.01 1.84 2.16 2.54 3.09 3.32 4.06 1.107 2.09 2.57 2.32 2.76 3.21 4.05 4.19 5.17 1.484 2.38 3.49 2.68 3.74 3.66 5.33 4.77 6.95 1.644 2.98 3.96 3.28 4.28 4.48 6.04 5.83 7.89 1.914 3.53 4.64 3.96 4.99 5.41 7.07 7.03 9.24 2.04 3.95 5.02 4.43 5.46 6.07 7.72 7.87 10.07 2.18 4.44 5.47 5.00 6.02 6.81 8.52 8.82 10.97 2.78 5.13 6.99 5.99 7.76 7.84 10.64 10.08 13.75 3.77 6.98 9.76 8.56 11.09 10.55 14.74 13.44 18.97 5.20 10.18 13.58 12.35 15.60 15.41 20.41 19.58 26.26 6.7i 13.08 17.73 16.35 18.76 19.67 26.65 24.87 34.11 Including areas of a<xompanying flanges bolted to the 'fitting. . peratures of the insulations. It should be emphasized that they are the average values obtained from a number of tests made on each type of material, also that all variables due to differences in thickness, pipe sizes, and air conditions are eliminated. Individual manufacturer's materials will, of course, vary in conductivity to some extent from these vailues. 779