HEATING VENTILATING AIR CONDITIONING GUIDE 1943
(dollars) -j- 13,000 (Btu) X 2000 (lb) X 0.55 (efficiency) => $0,804. The total cost of heat lost per year = 0.804 X 181.6 (thousand Btu) = $146.00. (A closely approximate solution of such a problem may be made quickly by the use of the estimating chart given in Fig. 1.)
Table 3. Heat Loss from Bright Copper Pipe Given One . .Thin Coat of Clear Lacquer
Expressed in Btu per hour per linear fool per degree Fahrenheit between the pipe and surrounding still air at 70 F
Nominal.' Pipe Size
(Inches)
M
Y
1
lM
m
2.
m.
3
3M 4
4H 5 6 8
Hot Water (Type K Copper Tube)
, Steam (Standard Pipe Size Pipe)
120 P
150 F
180 F
210 F
227.1 F (5 Lb)
297.7 F (50 Lb)
337.9 F (100 Lb)
Temperature Difference
SO F
80 F
110 F
-
140 F
157.1 F
227.7 F
267.9 F
0.240 0.320 0.390 0.470 0.540 .
0.690 0.840 0.960
1.100 1.241
0.265
0.356 0.437
0.537 0.612 0.762
0.937 1.025
1.250 1.400
1.480 1.700 2.200
1.685 1.936 2.500
0.282 0.373 0.463 0.554 0.645 0.818 0.991 1.135 1.318 1.480
1.790 2.052 2.630
0.307 0.414 0.507 0.614 0.714 0.892 1.085 .1.270 1.442 1.556
1.965 2.272 2.854
0.401 0.477
0.598 0.700 0.830 1.005 1.178
1.400 1.580 1.750 1.910
2.130 2.450 3.120
0.461 0.571 0.681 0.812
0.966 1.164 1.361 1.625 1.845 2.040
2.240 2.415 2.810
3.425
0.478 0.578 0.710 0.840 .0.990
1.201 1..420 1.700
1.905 2.130 2.350 2.610 2.990
3.730
Table 4. Heat Loss from Horizontal Tarnished Copper Pipe
Expressed in Btu per hour per linear foot per degree Fahrenheit ' between the pipe and surrounding sttll air at 70 F
Nominal Pipe Size
(Inches)
Hot Water (Type K Copper Tube)
Steam (Standard Pipe Size Pipe) '
120 F . 150 F
180 F
210 F
227.1 F
(5 Lb)
297.7 F (50 Lb)
337.9 F .(100 Lb)
Temperature Difference
H M
l
-m m
2
2K 3
3H A AH
5'
6 8
. 50 F
. 0.250 0.340 . 0.440
. 0.500 0.580.
0.730 . 0.880
1.040' 1.180 1.460
1.600 1.840 2.400
80 F
0.2870.381 0.475 0.559 0.656 0.825
1.000 .
1.175 1.350 1.500
1.812 2.125 . 2.685
HOF
0.300 0.409 0.509 0.618 0.710 0.890 1.091 1.272 1.454 1:635
1.980 2.270 2.910
140 F
6.321 0.429 0.536 0.622 0.750 0.957 1.143 1.343 1.535 1.715
. 2.071 2.430 3.110
157.1 F
0.433 0.533 0.636 0.764 0.904 1.101 1.305 1.560 1.750 1 .941:. 2.131 2.387. 2.740 3.310
227.7 F
0.500 0.543 0.746 0.878 1.053 1.273 1.490 1.800 2.020 2.240 2.465 2.770 3.210 4.050
267.9 F
0.530 0.654 0.803 0.934 1.120 1.364 1.605 1.940 2.170 2.430 2.650 2.990 3.440 4.370
.
778
CHAPTER 43. PIPE AND DUCT HEAT LOSSES
HEAT LOSSES FROM INSULATED PIPES
The conductivities of various materials used for insulating steam and hot water systems are given in Table 8. They are given as functions of the mean temperatures or the mean of the inner and outer surface tem-
Table 5. Radiating Surface per Linear Foot of Pipe
Nominal P(iIpnechSeisz)e
Ye
1
m
Surface Area (Sq Ft)
0.22 0.275 0.344 0.435 0.498
Nominal Pipe Sue (Inches)
2
2H.
3 3H 4
Surface Area (So Ft)
0.622 0.753 0.917 1.047 1.178
Nominal Pipe Size (Inches)
5 6 8 10 . 12
Surface Area (Sq Ft)
1.456 11734 2.257 2.817 3.338
Table 6. Radiating Surface per Linear Foot of Copper Tubing Outside diameter Yz in. greater than nominal size
Tube Size (Inches)
J4 . 1
mm
Surface Area (Sq Ft)
0.164 - 0.229
0.295 0.360 0.426
Tube Size (Inches)
22H
3 3H 4
Surface Area (Sq Ft)
0.556 0.687 0.818 0.949 1.080
Tube Size (Inches)
5 6 8
Surface Area (Sq Ft)
1.342 1.604 2.128
A Table 7. Areas of Flanged Fittings, Square Feet3
Nominal , Pipe Size
(Inches)
i
m ni 2' 2H 3 3H 4
5 6 8 10 12
Flanged Coupling
90 Dkg Ell
LongERlta, dius
Tee
Cross
Standard
Extra Heavy
Standard
Extra Heavy
Standard
Extra Heavy
Standard
Extra .Heavy
Standard
Extra Heavy
0.320 0.383 0.477 0.672 0.841 0.945 1.122 1.344 1.474 1.622 1.82 2.41 3.43 4.41
0.438 0.795 1:015 0.892 1.083 1.235 1.575 1.622 2.07 0.510 0.957 1.098 1.084 1.340 1.481 1.925 1.943 2.53 0.727 . 1.174 1.332 1.337 1.874 1.815 2.68 2.38 3.54 0.848 1.65 2.01 1.84 2.16 2.54 3.09 3.32 4.06 1.107 2.09 2.57 2.32 2.76 3.21 4.05 4.19 5.17 1.484 2.38 3.49 2.68 3.74 3.66 5.33 4.77 6.95 1.644 2.98 3.96 3.28 4.28 4.48 6.04 5.83 7.89 1.914 3.53 4.64 3.96 4.99 5.41 7.07 7.03 9.24 2.04 3.95 5.02 4.43 5.46 6.07 7.72 7.87 10.07 2.18 4.44 5.47 5.00 6.02 6.81 8.52 8.82 10.97 2.78 5.13 6.99 5.99 7.76 7.84 10.64 10.08 13.75 3.77 6.98 9.76 8.56 11.09 10.55 14.74 13.44 18.97 5.20 10.18 13.58 12.35 15.60 15.41 20.41 19.58 26.26 6.7i 13.08 17.73 16.35 18.76 19.67 26.65 24.87 34.11
Including areas of a<xompanying flanges bolted to the 'fitting. .
peratures of the insulations. It should be emphasized that they are the average values obtained from a number of tests made on each type of material, also that all variables due to differences in thickness, pipe sizes, and air conditions are eliminated. Individual manufacturer's materials will, of course, vary in conductivity to some extent from these vailues.