Document RJbMdV5OK7ONOeRwoV5q47vrE

HEATINC VENTILATING AIR CONDITIONING GUIDE 1944 In spite of this, a small size fuel requires a larger opening of the door slots; for a certain size for each fuel no slot opening is required, and for larger sizes too much excess air gets through the fuel bed. It is impossible to establish a single rule for the correct slot opening for all types and sizes of fuels and for all rates of burning. Furthermore, the effect of slot opening is dependent on whether the ashpit damper is open or closed. Bituminous coals require a large amount of secondary air during the period subsequent to a firing in order to consume the gases and to reduce the smoke. The smoke produced is a good indicator, and that opening is best which reduces the smoke to a minimum. Too much secondary air will cool the gases below the ignition point, and prove harmful instead of beneficial. Secondary air that enters the combustion chamber too far removed from the zone of combustion will also be harmful, for the oxygen in the secondary air will not react with any unhurried gases unless the mixture is subjected to high temperatures. The air requirements of oil and gas burners are discussed in Chapter 10, Automatic Fuel Burning Equipment. DRAFT REQUIREMENTS The draft required to effect a given rate of burning the fuel is dependent on the following factors: 1. Kind and size of fuel. 2. Grate area. 3. Thickness of fuel bed. 4. Type and amount of ash and clinker accumulation. 5. Amount of excess air present in the gases. 6. Resistance offered by the boiler passes to the flow of the gases. 7. Accumulation of soot in the passes. '' Insufficient draft will necessitate additional manipulation of the fuel bed and more frequent cleanings to keep its resistance down. Insufficient draft also restricts the control that can be accomplished by adjustment of the dampers. The quantity of excess air present has a marked effect on the draft required to produce a given rate of burning. If the excess is caused by holes in the fuel bed, or an extremely thin fuel bed, it is often possible to produce a higher rate of burning by increasing the thickness of the bed. The thickness of the fuel bed should not, however, be increased too much because the increased draft resistance will reduce the rate of primary, air supply and the rate of burning. For amount of draft required see Chapter 9, Chimneys and Draft Calculations. DRAFT REGULATION Because of the varying heating load demands present in most instal lations it is necessary to vary the rate of fuel burning. The maintenance 172 Mar.;... CHAPTER 8. COMBUSTION AND FUELS of the proper air supply for the various rates of burning is accomplished by regulation of the drafts. Correct and incorrect methods of draft regulation are shown in Fig. 3. The air enters through the ashpit draft door, firing door and by leaks in the setting, whereas the gases leave only through the uptake. By throttling the gases with the damper in the uptake all the air entering by each of the three intakes is reduced in the same proportion. If the ashpit draft door is closed the air admitted through the ashpit is reduced and increased through the other two intake openings. Fig. 3. Correct and Incorrect Methods of Draft Regulation in A Hand-Fired Furnace Methods of control of . draft conditions when burning oil or gas are noted in Chapter 10, Automatic Fuel Burning Equipment. CLASSIFICATION OF COALS The complex composition of coal makes it difficult to classify it into clear-cut types. Its chemical composition is some indication but coals having the same chemical analysis may have distinctly different burning characteristics. Users are mainly interested in the available heat per pound of coal, in the handling and storing properties, and in the burning characteristics. A description of the relationship between the qualities of coals and these characteristics requires considerable space: a treatment applicable to heating boilers is given in a Bureau of Mines Bulletin*. Coal composition may be expressed by either an ultimate or proximate analysis. In the ultimate analysis the proportions of carbon, hydrogen, oxygen, nitrogen, sulphur, and ash are determined. This form of analysis is difficult to make and is used only for extremely close studies. The proximate analysis is more easily made and is satisfactory for most purposes. In this analysis, the proportions of moisture, volatile matter, fixed carbon, and ash are determined. Moisture is obtained by noting the loss of weight of a sample of coal when dried at about 220 F. To determine volatile matter, the dried sample is heated to about 1750 F in a closed crucible, and the loss of weight is noted. The sample is then burned in an open crucible, and the accompanying loss of weight repre- 'Five Hundred Tests of Various Coals in Househeating Boilers (U. S. Bureau of Mines Bulletin No. 276). 173