Document R9eRe9ZeB5mzwn3JqGzJjnE7
S7*0 V
Iff/Cf COPTHE DOW CHEMICAL COMPAN KISTtlCTI
8H2.1-1-191(1
PHMwm imniiMf
IACCT:
InIeOmliKsta,n
HVUnaiT
,r *"r--a----------------------- -------------- pn-------------------
Cfrfl^al, Biology Research
banuarv 24. 19*
fa^G. &llvartein
19088860
EVALUATION OF CANOPY HOOD IN THE TRADES TRAINING DEPARTMENT, 294 BUILDING
INFORMATIVE SUMMARY WITH CONCLUSIONS Work by: L. G. Silverstein R. W. Bohl
A canopy hood over tha work tabla uaad by studants in Tradas Training is inadequate to control vapors ganaratad in layup of Derakane rasins and is probably inadaquata to control
rm asbastos axposura in tha coursa of studant aetivitiaa. Tha axhaust fan capacity could ba put to battar usa by modification ! of tha hood to provida slot vantilation positionad elosa to the
sourca of contamination. A recommendation is made to this affect.
DOto f%y/>
%/4/
REVIEWED BY
^[**+-r0* 1-1-Z -1
jmd
F. G. Kania, Tradas Training Department, 294 Building
R. M. Johnson, Tradas Training Department. 294 Building
B. B. Holder, M.D., Medical Department, 607 Building
M. Kalyman, Safety Department, 400 Building
R. R. Langner, Industrial Hygiene Services, 607 Building
Central Report Index, 566 Building
?? Bet/tfkAAjoeA, T&Abes
SO
3
1
ji u u u u J J J
DOW 06205
2 PROBLEM Supervision requested evslustion of s recently installed canopy hood in terms of its ability to control fumes generated by student activities with Derakaneand epoxy resins and asbestos.
CONCLUSIONS & RECOMMENDATIONS 1. The present canopy hood installation is not adequate to pro
tect persons working at the'bench from fumes generated in Derakane resin work or from inhalation exposure produced by work with asbestos.
2. The exhaust system should be modified to provide a slot ventilation exhaust approximately 3" by 12" at each of the four work stations on the bench.
3. Because of the high toxicity and atringent regulations associated with the use of asbestos, it is strongly recom mended that a substitute be found for this work.
00W 06206
3
4. Materials usad in this activity are noted skin irritants and - some are known skin sensitizers; therefore, the indoctrination of students in this activity should emphasize the need for minimizing skin contact and unusually good personal hygiene * to avoid skin irritation or skin sensitization*.
DISCUSSION
Supervision requested evaluation of a recently installed canopy hood over the work bench used by students in the Ts rades Training Skill Area, second floor of 294 Building. The exhaust rate of this canopy hood was found to be about 1300 cubic feet of air per minute, using an Alnor thermoanemometer. This exhaust rate could provide much improved exhaust ventilation if it is directed through four slot ventilators at the four work positions at the bench. Calculations show that four slots 3" wide by 12" long would produce an air velocity at the face of the slot of approximately 1200 linear feet per minute. This face velocity at the slot should provide good control of vapors produced within 6" to 10" of the slot. It would certainly be better than the
c
i . n f\ n a *r
DOW 06207
l^ n n n n i c
4
present canopy arrangement and past axparianea would indicate that it should ba adequate to control the vapor* produced in Derakane layup work.
Air movement in the breathing zone of persons at the work bench, with the canopy hood on. were observed by generating visible smoke at the work positions. The observers stood at the bench and performed moderate arm and body movements to simulate student activities. The direction of air movement was random and visible smoke reached the observers' breathing cones. The canopy hood exerted no detectable influence on air movement at breathing zone height. Air velocity at the work bench was quite low and variable, ranging from less than 20 to about SO fpn (linear feet per minute). The low air velocities and high degree of fluctuation at the work bench, plus the lack of definite direction of air flow shown by the smoke tubes, lead to the conclusion that the canopy hood is ineffective as presently used.
During the survey, it was pointed out that asbestos is used as a filler in the operation. Asbestos has been shown to be a severely hazardous material by inhalation exposure. As a result, the federal Occupational Safety & Health Administration
oout
6?08
c i O O n o * **
5
has promulgated stringent requirements for control of exposure, medical surveillance and a number of other related factors as part of the OSHA (Occupational Safety 6 Health Act) regulations. A copy of the asbestos regulations under OSHA is appended in Appendix Z of this report.
Because of the potential hazard and the extreme con trol and surveillance requirements related to asbestos, it is recommended strongly that a less hazardous substitute be found immediately for use as a filler. If this cannot be done, imme diate steps should be taken to monitor the exposure of students while using asbestos and to comply with the other requirements of the regulations in Appendix I.
Oerakane resins and epoxy resins and hardeners are known to cause skin irritation (dermatitis) and some components of epoxy resin systems are known to be skin sensitizers. The practices observed and described during this survey are necessary to prevent skin contact because of the consequences of excessive skin contact. It is urged, hereby, that the course include a specific section on potential skin hazards and the safety pre cautions required to avoid dermatitis or sensitization.
DO^
6 Appendix zz is a chapter from a book on the subject of safe handling of epoxy resin systems. This chapter has been condensed into a verbal slide talk using the illustrations shown in Appendix ZZ and is available for use by Trades Training either with or without the author, just so long as you don't misquote him!
DOW 06210