Document R4daZNXZkyd67p7MReBZBpxv

A Study Determining Asbestos Fiber Release During the Removal of Valve Packing James R. Millette and Michael 0. Mount MVA, Inc, 5500 Oakbnook Parkway, Suite 200, Norcross, Georgia 30093 Asbestos packing material used in valves is generally considered to be a nonfriable material unless cut or torn. In a controlled, contained area within a steam power plant, personal and area air samples were collected be fore and during removal of asbestos packing material from valves that had been used at the plant. The results of this study show asbestos fibers can be released into the air during the generally used procedures for the removal of asbestos packing material. Air concentrations were measured by phase contrast microscopy in the range of 0.2 to 1.3 fibers/cc and by transmission electron micros copy in the range of 1.3 to 4.2 fibers/cc for all diameter fibers greater than 5 pm in length. Millette; JR: Mount MO: A Study Determining Asbestos Fiber Release During the Removal ol Valve Racking. AppL Occup. Environ. Hyg. 8<9):790-7S3; 1933. Introduction Most piping systems use valves to regulate the flow of fluids or gases within them. The valves, especially in indus trial facilities, may contain asbestos packing material that acts as a seal to prevent fluid or gas leakage as the valve is turned. Periodically, the values must be repaired or rou tinely maintained by removing the packing and replacing it with new packing In some steam plants, it is common practice to perform the removal and repackingofa number of valves at one time This effort may involve:several workers and take a number ofdays to complete A literature search showed only one published study reporting on the release of asbestos fibers from packing material. Asbestos Packing Material ' According to the li& Environmental Protection Agency (ERA) asbestos packing means an asbestos-containing product intended for use as a mechanical seal in circum stances involving rotary, reciprocating and helical motions, and which are intending to restrict fluid or gas leakage be tween moving and stationary surfaces. In a valve, the packing is compressed against the bore of the box by a gland that is tightened down on the packing (Figure 1) The packing is forced against the throat of the valve box and the packing conforms to the vaive shaft surface, forminga tight seal. Compression packings are manufactured from various types of fibers, such as vegetable, animal, mineral (asbes tos) or synthetic, and twisted or braided with binders and lubricants. One of the most commonly used types of compression packing in valves is a graphite impregnated packing material that has the appearance of shiny, stiff rope Packings are not considered friable asbestos-containing materials (ACM) because they are not easily crumbled into fine or dusty material by hand pressure; However, the EPA states that products such as packing may release asbestos dust if cut or tom.*0 Study Design Asbestos-containing materials are common in industrial steam plants, and because a maintenance activity often in volves the disturbance of more than one material, it is diffi cult to assess the contribution, ifany ofa particular ACM to the overall airborne asbestos concentration. Valve packing removal, for instance, may involve the removal or at least disturbance of asbestos-containing pipe insulation or fit ting *mud." Therefore, to determine the possible contribu tion of valve packing only special precautions were taken to isolate this material from other activities that might have contributed airborne asbestos from other sources Study Site The study was conducted in an unused steam power plant in Manchester, New Hampshire. The study team con ducted the valve packing removal tests after an asbestos abatement contractor had prepared a double containment area around two valves attached to the main power plant turbine Prior to the studies, the abatement contractor pre pared the valves by removing all pipe insulation from the valve area and thoroughlycleaning each valve In a separate area of the plant, the abatement contractor also prepared a third valve that had been disconnected from the steam plant piping system by similariy removing all the pipe insu- 790 I047-322X/93/0809-790S6.00/4 C 1993 AIH APPL OCCUP. CHV7R0H HYG. #9) SEPTEMBER 1993 VALVE SHAFT Study Procedures FIGURE 1. diagram of steam pipe valve containing packing. kuion and cleaning the valve thoroughly. This valve was truer moved into the containment for packing removal The containment barriers in tlie area consisted of layers of poly ethylene plastic sheets on a wooden frame and 2 layers of polyethylene plastic on the Boot A containment area (5 X 7 ft) around the valves was completely contained within a larger containment area (7HX11 ft) (Figure 2) The study area had two high efficiency particulate absolute air filtra tion devices (AFD) used to dean the air of particulate in cluding asbestos before each valve packing removal activ ity The inner area AFD was turned offduring each phase of testing The outer area AFD operated throughout the tests The study consisted of the collection of air samples be fore and during valve packing removal activities A retired steam plant maintenance worker&upervisor using his own tools performed the valve packing removal in the same way that he had in his previous years of work on industrial valves and as is often done in power plants today Although some lubricating oil was used to loosen the packing, the work was generally done in a dry manner. Three packing removal tests were performed. The first two packing re moval activities consisted of opening valves connected to 4- to 6-inch diameter pipes and reaching in with a variety of tools to pull out three to four rings of the old packing The third test utilized the same valve that had been opened in the second test and duplicated the packing removal activity. More packing was removed under the same conditions as the second test. Pieces of the removed [jacking were placed in plastic bags andstoredforanalysis.The packing removed from both valves appeared to be graphite impregnated packing material that had a shiny gray-black appearance Each packing removal activity occurred for approximately 30 minutes. The study site was cleaned between activities Prior to starting each part of the study four area air sam ples were collected to determine the background level of asbestos in the air ofthe studyarea. The sampling cassettes were located on the walls at the breathing zone, 5 feet from the fioot A volume of720 to 840 Lofair was passed through eachcassette atafiowrate of15 L/inin. Two area airsamples FIGURE 2. Diagram of enclosure for valve packing removal study. appl occup. ernmoK hy& m September 1993 791 TABLE II. Transmission Electron Microscopy Results on Personal Air Monitoring Samples During Packing Removal Asbestos Concentration (libers/cc) Sample Description All > 5/tfli PCM Equivalent* Tesi 2 Personal packing remover Personal packing remover 2.2 4.2 1.5 2.6 Test 3 Personal packing remover Personal packing remover 1.5 2.1 1.2 1.5 'Phase contras! mooscopy equivalent by transmission electron microscopy counting. Asbestos tides or bundles greater than or equal to ipat in length and at least 0.25<im in width (3:1 asoect rain). maining material was carbon. Similar looking unused as bestos packing found in the storeroom of the power plant was not friable In an additional test, a piece of the unused packing was subjected to heating at 400C for 1 hour in a . muffle furnace The packing became friable after the treat ment by heat Conclusions Asbestos packing, although not friable in original, un used condition, can become friable after use in valves and can release asbestos fibers into the air during valve packing removal operations The levels of asbestos detected in the air were similar to the levels reported previously for valve packing activities40 and in some instances involving gasket removal activities0' Recommendations The results of these tests suggest that asbestos packing material, although not identified as a friable ACM, should be considered as such during packing removal activities If possible, the packing should be wetted with water or oil before it is cut and torn with packing tools such as hooks during the procedures for removing old packing References 1. McKinnery, W.N.; Moore, R.W.: Evaluation of Airborne Asbestos Fiber Levels During Removal and Installation of Valve Caskets and Packing. Am. Ind. Hyg. Assoc. J. 53(8):531-532 (1992). 2. U.S. Environmental Protection Agency: Title 40, Code of Federal Regulations, Part 763. Asbestos: Manufacture, Importation, Pro cessing and Distribution'in Commerce Prohibitions; Final Rule. Fed. Reg. 54(132)(July 12, 1989). 3. Nelson, CA.: Millwrights and Mechanics Guide, p. 236. McMillan Publishing Co., London (1986). 4. U.S. Environmental Protection Agency: Asbestos Waste Manage ment Guidance. EPA-530/SW-85-007. Office of Solid Waste, Wash ington, DC (May 1985). 5. Carter, J.W.; Taylor, D.G.; Baron, PA.: Method 7400. In: NIOSH Manual ofAnalytical Methods, p. 7400-1 - 7400-8. National Institute for Occupational Safety and Health, Cincinnati, OH (1984). 6. Carter, J.W.; Baron, PA.; Taylor, D.G.: Method 7402. In: NIOSH Manual ofAnalytical Methods, p. 7402-1 -7402-7. National Institute for Occupational Safety and Health, Cincinnati, OH (1987). 7. Cheng, R.T.; McDermott, H.J.: Exposure to Asbestos from Asbestos Gaskets. Appl. Occup. Environ. Hyg.-6:568-591 (1991). Received 8/27/92 rtview decision 12/3/92 revision 11/19/92 accepted 01/28/93 APPL OCCUP. ENVIRON. HYG. 8(9) SEPTEMBER 1993 793