Document R2G4Ky0y0O674EJkorEZNZoX
48
CHAPTER 3
1962 Guide And Data Book
sorption over the spectrum is proportional to that of a perfect
black body. The combined radiation and convection coeffi
cient in the normal temperature ranges has a value of slightly
less than 2.0. In the usual installation, the actual performance
is considerably greater due to transfer of high frequency radi
ation from die sun and lighting, which is practically inde
pendent of panel surface temperature. This mechanism was
investigated ui considerable detail by C. S. Leopold* who de
veloped the concept of Independent Radiant Transfer, IRT,
which he defined as follows:
(Panel Transfer -- Convection -f- Rad. due to\
to Panel
temp of other j100
room surfaces
%IRT----------------------------------------------------------------------------------- (5)
Energy of Source
When a method is available to evaluate the different mechanisms of radiation from luminaires. Equation 5 can be rewritten to eliminate the experimental error.
/Short Wave Radiation + Long Wave Radiation\
/ from lights absorbed absorbed by panel 1
l by panel (Light)
(Low temp from ylOO
\ fixture surfaces) /
%TKT-------------------------------------------------------------------------- (6)
Energy Input to Lights
This method of analysis estimates the additional perform ance gained from lighting which is suspended in a room. It is a function of the type of ceiling and panel construction, and, above all, of the type of lighting fixture used. Table 1 shows some empirical results obtained both by model and full scale prototype tests. These percentages represent the additional pickup in Btu per sq ft o! panel area as a percent of lighting input. For certain types of lighting, particularly incandescent, considerable improvement in performance may be obtained by using special copper phosphate heat absorbing paint on the panels.11 It should also be noted that for incandescent lighting, a certain amount of the radiant energy from the lighting source is stored in the building structure, and will not materi alize as a cooling load until a considerable time lag after the lights are turned on.u-"
ABSORPTION OF SOLAR RADIATION
Panels installed in the ceiling near large window areas will absorb quantities of energy from solar radiation, which are independent of panel surface temperature in the normal range, especially when a deflection device, such as a light colored Venetian blind, is used to reflect the radiation upward to the paneL The quantity will depend on such factors as general window construction, window type and configuration, type of glazing, mid type of shading device. Leopold reported an experiment with a model of exterior zone with 35 percent window strip of clear glass with white Venetian blind inside.u'u
With panels in the entire ceiling area, approximately 13 percent of the room load due to solar gain was absorbed by the panels as IRT, resulting in a fictitious h value of 2.77 for a panel temperature of 68.5 F with a room temperature of 78 F. A similar experiment using a panel area of 40 percent of the ceiling area in a suspended ceiling resulted in an h value of over 3, with the panels transferring approximately 6 percent of the room solar load independent of panel surface temperature. In this case, the total fictitious A value reflects not only the IRT but also the heat gain from surfaces in proximity of panels, as does Fig. 6.
USE OF TEST DATA
Example 1 illustrates the use of the performance data. It should be pointed out that this example is used only to
illustrate the significance of some of the existing test data. The data should not be extrapolated to cover any general condition which is different from that on which the tests in the reference material are based.
- Example 1: Determine the heat transfer for the interior and exterior zones of a panel-air system installed in a multi-story building, 100 feet square, with 35 percent window strip nf clear eia&s with white Venetian blinds inside (slate tilted 45 deg up). The ceiling panels are flush mounted, with a narrow (less than
10 ft) exterior zone fully paneled, and 12 ft by 4 ft panels forming 80 percent of the interior zone ceiling area. The panel surface temperature is assumed to be 65 F, with room and floor tempera* tures of 75 F. Lighting is from suspended fluorescent fixtures at 10 watts per sq ft, or 34.1 Btuh per sq ft.
Solution a: (Interior Zone). Radiation Transfer. The AUST wilt approach the floor tem perature of 75 F. From Fig. 1, at AUST = 75 F and panel surface temperature "65F, the heat transferred by radiation is found to be 8.8 Btu per (hr) (sq ft). Convection Transfer. The equivalent diameter D, is 4 (12 X 4) /2(12 + 4) -- 6. As the temperature of the room at approximately the mid-height is being used as a criterion, the convection transfer can be found from fig. 3, using the curve for the ASHRAE Lab oratory data, D -- 6, and a temperature difference between room and panel of 10 F deg (75-65). This value is read as 7.0 Btu per
(hr) (sq ft). Forced Convection Increment. Assuming that the air outlets
are installed to blow the full length of the panels, and assuming an average terminal velocity of 25 fpm, the additional heat trans fer due to forced convection can be found from Fig. 2. The value of velocity times length is 25 X 12 -- 300, and for laminar Sow, the value of y from Fig. 3 is 4.9. Then, h -- yv/1000 -- 4.9 X25/1000 = 0.124 Btu per (hr) (sq ft) (F deg). The heat transfer isthereforeO.124 X 10 -- 1.24 Btu per (hr) (sq ft).
IRT. From Table 1 for suspended fluorescent direct lighting,
IRT -- 16 percent of the source energy. Since the panels form 80 percent of the ceiling area, the heat transfer per square foot of panel area is 0.80 X 0.16 X 34.1 =* 4.2 Btu (hr) (sq it). _ The total heat transfer per square foot of panel area is the sum
of the radiation, convection, forced convection increment and
IRT.
Radiation Transfer
-- 8.8
Convection Transfer
= 7.0
Forced Convection Increment -- 1.24
IRT
- 4.2
Total Heat Transfer
= 21.24 Btu per (hr) (sq ft).
Air must be introduced to absorb the remaining heat load and
to provide ventilation and dehumidification. If the minimum air
quantity required for ventilation and debumidification is greater
than that required to absorb the remaining heat load, the panel
area can be decreased.
Solution b: (Exterior Zone). The transmission and solar loads should be calculated separately and expressed as Btu per (hr) (sq ft of panel area), usmg the full area of the exterior zone. As sume that the transmission load is 10 Btu per (hr) (sq ft) and the solar load is 30 Btu per (hr), (sq ft). With the assumed glass con figuration (similar tothat used in References 11 and 13) the value of IRT would be similar to that found in test conditions, or 13 percent of the source energy. Thus, IRT -- 0.13 X 30 -- 3.9 Btu per (hr) (sq ft).
The performance for the panel must be (30 -f 10) -- 3.9 --36.1 Btu per (hr) (sq ft). Since the exterior zone will operate with a higher AUST due to the effects of warm wall and windows Fig. 6 can be used to determine panel and airheat transfer. Fol low the curve for a 10 F deg temperature difference (U -- tp) until tiie sum of the heat transferred to the panel (read on the ordinate) and the heat transferred to the air (read on the abscissa) is 36.1 Btu per (hr) (sq ft). Thus, at 0.63 cfm per sq ft of floor area, the heat transfer is found to be
Paoel -- 25.8 Btu per (hr) (sq ft) Air = 10.3 Btu per (hr) (sq ft)
36.1
The panel may also remove an additional amount of IRT from
the lighting system. If the lighting intensity is the same as for
the interior zone, the total heat transfer to the panel would be
Solar IRT
- 3.9
Pone! Performance (Fig. 6) --25.8
Lighting IRT - 0.16 X 34.1 - 5.4
35.1 Btu per (hr) (sq ft) The air supply (assumed here at a temperature of 60 F) would
Panel-Air Systems for Air Conditioning
49
Table I .... Values of IRT for Lighting from Specific Tests FvO Ceiling--ftuA too*!
Ugtriing
Air
Soppfy F
Type of Point
(XT bfennet
Bowl Suspended Incandescent
300 w Bare Bulb Suspended incan
descent
6 Single-Tube Fluorescent
4 Fluorescent
Indirect
13 RLM Type 6 Suspended* Direct
13 RLM Type 6 Suspended-Indirect-
60 78 60 60 60 60 60 60 60
--
--
Heat Absorbing Heat Absorbing Regular Heat Absorbing Regular Heat Absorbing Regular Heat Absorbing Regular
Regular
Regular
33 35 20.4 I6!7 10.2 12.3 3.1 24.5 12.5
16
18
3 3 3 3 3 3 3 3 3
10
10
Own have to -be increased to meet the remaining load due to lighting, people, and other sources.
Regardless of the quantity of heat removed by the panels, air must be introduced to provide ventilation and to remove the moisture introduced to the space by infiltration, people, and other sources. In addition, experience has shown that a definite minimum amount of air motion is desirable. Fig. 7 shows the air supply rate in cfm per square foot, and dew point, required for two room conditions and at two rates of infiltration. These curves were derived by assuming 95 F dry-bulb and 78 F wet-bulb for the infiltration air, and assum ing one person per 100 sq ft of floor ares. The infiltration rate 'was calculated for a space 11 ft from floor surface to underside of overhead slab.
The use of the curve for .4 hr per air change is not recom mended unless the building under consideration is of very tight construction.
If the supply air is dehumidified by refrigeration, the drybulb temperature will be near the dew point, and some cooling will be achieved. Thus, the required panel area may be reduced ,and only part of the ceiling area used for the paneL
fig. 7 .... Minimum Dew Point of Supply Air Required to Maintain Room Conditions
efficiency of various types of systems may be represented by an overall resistance factor r which is defined as
t, -I 9
(8)
r -- overall resistance factor, (hour) (square foot) (Fahren heit degree) per Btu.
PANEL SURFACE TEMPERATURE
Surface temperatures discussed in this chapter are assumed to be average panel surface temperatures. Pipe3 or tuning are bonded or clipped to metal panels, or for plaster panels, the pipe is e&bedded in the plaster. The difference in temperature between the water and the panel surface will depend on the effectiveness of the tube bond to the panel, the conductivity and thickness of the panel, and the tube spacing.
Since panel pooling systems operate with much smaller temperature differences than panel heating systems, the difference between-the panel temperature at the tube and between the tubes has much greater significance, and should be considered in the design of cooling panels. ;.Fig. 8 shows an approximate surface temperature distribu te30 assuming a given heat transfer rate with several com binations of panel thickness and tube spacing.
The effect of the tube bond and heat transfer section from tee tubing to the panel must be evaluated separately. The
fig. 8 ..., Estimated Panel Surface Temperatures for Plush Paneb