574 CHAPTER 24 1955 Guide walls or exposed ceilings, for any combination of outside design tempera ture and transmission coefficient, may be obtained from Fig.. 12. If the inside design temperature is other than 70 F, the values determined from Fig. 12 must be corrected by values obtained from Fig. 13. The follow ing example illustrates the use of Figs. 12 and 13. Example S: The outside walls of a room have a coefficient of heat transfer U = 0.15. Inside and outside design air conditions are 68 F and --20 F, respec tively. Determine the inside surface temperature of the wall. Solution: From Fig. 12 the inside surface temperature for 70 F and --20 F, and a U value of 0.15 is found to be 61.5 F. Then from Fig. 13, for a Af = --2 deg and a Panel Heating WEST 575 Fig. 13. Inside Wald Sdbface Temperature Correction for Inside Air Temperatures Other Than 70 F Ai = -- 70 If A/ is positive: tw' = (w + correction If At is negative: tw' -- tw -- correction = inside air temperature tw = inside wall surface temperature based on fa 70 r t' = actual inside wall surface temperature U value of 0.15, the correction is --1.8 deg. As the correction is negative, the inside surface temperature will then be 61.5 -- 1.8 = 59.7 F. The total panel output can then be determined from Figs. 9, 10, and 11. After the various wall surface temperatures have been determined, as described, the unheated mean radiant temperature UMRT of the space may be calculated as illustrated in Step 3 of the following section on Floor Panel Design Illustration. FLOOR PANEL DESIGN ILLUSTRATION The several steps in the design of a panel heating system are listed and illustrated in the following example of the design of a floor panel for the room shown in Fig. 14. 1. Selection of Design Conditions a. Outside design temperature, --10 F. b. Inside design room air temperature, 70 F. c. In this problem a floor panel heating system will be used. There is ______ ..^suui/ ur L/EiO a Panel Heating System Data: Values of overall heat transfer coefficients as calculated: 1. Outside walls V = 0J0 3. Floor U % Ceiling U = 0.08 4. Windows U 0M 0-55 no basement. Insulation will be used between slab and fill d. Heating medium, hot water. e. Floor surface temperature, 85 F (Maximum). 2. Calculation of Room, Heal Loss liaoteedy iwnotuhled cuosnuvaellnytiboenoabl tmaiannendefrr,oams oCu__h_t_lai_n_p_e_t_ed_r i9_n_.__C__Th^1ha*ep.Htr.eLoOroO1m2w.hceTahKt eTivocesasillccmaunlabTtieoignc.sa1lac4ur.e shown in Table 1. The heat loss through the surface areas containing the heating medium is not included in the calculation. The calculated rate of heat loss will determine the amount of heat which must be supplied by the heating panels to the room. Table 1. Calculated Heat Loss of Room (Fig. 14) Surfaces Ulass Inside walls. . t>euiner Floor.. Infiltration Area Sq Ft 272 80 352 480 480 ------.total heat loss V 0.10 0.55 0.08 -- Calculation 272 x 0.10 x 80 80 x 0.55 x 80 No heat loss 480 x 0.08 x 80 Heating panel 3,840 cu ft x 1.50 x 80 x 0.018 ! Heat Loss Btu/hr 2,176 3,520 0 3,072 0 8,295 17,063 3- Determination of UMRT f e calculations for determining UMRT are shown in Table temperatures shown in the fourth column were determined 2. The inside from Fig. 12. sur-