462
CHAPTER 19
1952 Guide
Table 8. Determination of Free Area and Pressure Loss of Register for No Deflection of Air*' b' *
Register Free Air in Square Inches (Upper value inreach group) -Pressure Loss in Inches of Water Column (Lower value in each group)
CFM
Distance tbom Rbox&tbb to Opposite Wall
19-21 |22-24|25-37|28-30I31-34| 35-39 1 4(M91 50-59 60-69
tl b -
190,-209
63 47 37 so 24 18
0.02 0.03 0.04 0.06 0.09 0.15
CFM 660-699
Distance tbom Rigisteb to Opposite Wall
35 39(40 -49! 50-69 160-69 1 70-79 1 80-89
lV E1*
210 143 95 69 49 0.02 0.03 0.07 0.12 0.22
210-229
76 58 45 36 29 22 0.02 0.02 0.04 0.05 0.08 0.12
700-739
236 160 107 77 54 0.02 0.03 0.06 .0.11 0.21
230-749
69 53 43 34 26 0.02 0.03 0.04 0.07 0.11
740-779
262 179 119 86 61 0.02 0.03 0.06 0.10 0.18
250-269
.81 63 50 40 31 31 0.02 0.03 0.04 0.06 0.09 0.18
780-819
291 198 132 95 67 0.02 0.03 0.05 0.09 0.17
270-299
93 73 69 47 36 24
0.02 0.02 o.os 0.05 0.03 0.16
820-459
320 213 145 105 74 0.02 0.03 0.05 0.08 0.15
300-339
95 77 61 46 32 0.02 0.03 0.04 0.06 0.12
860-899
352 240 160 115 81 0.02 0.02 0.04 0.08 0.14
340-379
120 97 77 59 40 0.02 0.02 0.03 0.05 0.10
900-939
385 262 175 126 89 0.01 0.02 0.04 0.07 0.13
380-419
119 95 73 50 0.02 0.03 0.04 0.08.
940-979
419 285 190 137 97 0.01 0.02 0.04 0.07 0.12
420-459
149 114 88 60 0.02 0.03 0.04 0.07
980-1019
455 309 206 148 0.01 0.02 0.04 0.06
105 0.11
460-499
171 136 105 71 0.03 0.02 0.03 0.06
1020-1059
493 335 223 161 113 0.01 .0.02 0.03 0.06 .0.11
00-539
160 123 84 0.02 0.03 0.05
1060-1099
530 361 241 173 123 0.01 0.02 0.03 0.06 0.10
540-579
186 143 97 0.02 0.02 0.05
65 47 0.09 0.17
1100-1139
571 388 258 136 132 93 0.01 0.02 0.03 0.05 0.09 0.17
580-619
213 164 0.02 0.02
111 74 54. 0.04 0.08 0.15
1140-1179
416 277 199 141 100 0.02 0.03 0.05 0.08 0.16
620-659
180 127 85 . 61 0.03 0.04 0.07 0.14
AB
a If register selected based on distance from register to opposite wall is unsatisfactory on account of size or pressure loss, it is permissible to shift one or more spaces left or nght in the tables to obtain a more suitable register. If requirements fall in blank. space, select two registers in place of one and divide CFM capaoity between the two registers.
k Pressure loss is based on FLAT FACE ADJUSTABLE BAR TYPE and does NOT include stackhead.
c Values on the right of line A and A' should not be used in ap plications such as churches, auditoriums, and concert halls.
d Values on right of line B and B' should not be used in applications such as residential work, motion picture theaters, court rooms and schools.
e For floor and baseboard registers where a velocity of ap
proximately 300 FPM is used, the free area -- ~ `>3qq' ^ 01 ap-
CFM. proximately, --^-- Assume a pressure loss of .01.
* For any volume under 190 CFM use Table 7.
1180-1219 1220-1259 1260-1299 1300-1339 1340-1379 1380-1419 1430-1459 1450-1500
446 297 214 151 107 0.02 0.03 0.04 O.OS 0.15 476 317 228 161 116 0.02 0.03 0.04 0.07 0.14 507 338 243 172 122 0.01 0.03 0.04 0.07 0.13 539 359 258 183 130 0.01 0.03 0.04 0.07 0.12
883 274 195 138 0.03 0.04 0.07 0.12 403 290 206 146 0.02 "0.03 0.06 0.12
30S 218 155
0.03 o.oa 0.10
334 130 183 0.03 0.00 0.10 A' B-
Forced Warm Air Systems
463
Table 9. Suggested BoAnet Pressure Inches of water
Total CFM Through Any One Duct
800-1000 1000-1200 1200-1800 1800-2400 2400 to 3500
Suggested Bonnet Pressure
In. Wateb
0.10 0.10 0.10 0.13 0.14
Total CFM Tbhough
Any One Duct
3500 to 5000 5000 to 7500 7500 to 10,000 10,000 to 12,000 ' 12,000 to 14,000
Suggested Bonnet Pbessube
, In. Wateb
0.15 0.25 0.375 0.500 0.750
the sun or from a fireplace, or by direct heat from any warm air duct, register or chimney.
2. A fan switch control located in the bonnet to start blower operations at tempera tures between 110 and 130 F, and to stop the blower at about 25 to 30 deg below the cut-in point. The lower settings are used for high sidewall register installations, and the higher settings for baseboard register installations. For most satisfactory results these settings should be as low as.is feasible.
3. A protective high limit switch located in the bonnet to stop, the system inde pendently of the thermostat if the bonnet temperature exceeds 175 F.
4. On oil and gas burner installations, a protective control should be included to cut off the fuel supply if the fire is extinguished, or if there is a failure of the igni tion system.
5. On automatic stoker installations, a control is usually included to operate the stoker regardless of thermostat settings whenever the bonnet temperature indicates that the fire is dying, or a time interval contactor is used to cause the stoker to run a few minutes out of each hour.
6. A humidistat to regulate the moisture supplied to the rooms, located either in one of the rooms or in the main return duct near the furnace.
ADJUSTMENT OF SYSTEM FOR CONTINUOUS AIR CIRCULATION
This procedure applies to the adjustment of an automatically-fired forced warm air heating system to provide continuous air circulation, when the control arrangement is of the type where the room thermostat controls the fire and the blower control (fan switch) in the furnace bonnet or warm air , plenum controls the blower operation. This procedure as outlined in detail in Manual 6 of the National Warm Air Heating and Air Conditioning As sociation, is as fpllows :7
1. Adjust the fuel input in proper relation to the heat loss of the Structure.
2. Determine the temperature rise through the furnace.
3. Adjust the air volume to produce a temperature rise through the furnace of about 100 deg.
4. Adjust the fan switch differential to a minimum of about 15 deg.
5. Adjust the fan switch cut-out point as low as practicable.
6. Adjust the room thermostat temperature differential to a minimum which will cause the burner to cycle frequently.
7. Balance the system by adjusting dampers to produce even temperature distri bution between rooms.
8. Set the room thermostat at the desired room temperature.
WARM AIR CEILING PANEL SYSTEMS
Warm air ceiling panel heating systems utilize a false ceiling suspended 3| in. from the ceiling joists which have previously been covered on the bottom with sheets of plasterboard. Special hangers are used'to suspend the false ceiling or heating panel from the joists. Steel supporting rods