Document Qgy7azpdxbrk07Vq4Xanm4pok

THE USE AND DISPOSAL OF ELECTRICAL INSULATING LIQUIDS SUB-COUNCIL REPORT June 1971 NATIONAL INDUSTRIAL POLLUTION CONTROL COUNCIL HONS 043737 THE USE AND DISPOSAL OE ELECTRICAL INSULATING LIQUIDS SUB-COUNCIL REPORT June 1971 NATIONAL INDUSTRIAL POLLUTION CONTROL COUNCIL This report has been prepared (or the Secretary of Commerce. It does not necessarily represent the views of the Department of Commerce mons 0<*39 For sale by the Superintendent of Documents, u.S. Government Printing Office. Washington, D C. 20402. Price 25 cents. Stock Number 5254*0028 HONS 043740 National Industrial Pollution Central CeuneH Wn^in DC. KOW June 21 , 1971 Honorable Maurice K. Stans Secretary of Coimerce Washington, D. C. 20230 Dear Mr. Secretary; I have the honor to transmit to you for the President and the Chairman of the Council on Environmental Quality a Progress Report of actions underway by Industry with regard to specific pollution problems. This Report has been prepared by a Sub-Council of the National Industrial Pollution Control Council as an Information paper. It describes the actions and presents the views of those Industries most directly Involved with the particular pollution problems addressed. Such Progress Reports will be prepared by our Sub-Councils on major pollution problems confronting Industry and will be updated from time to time. Bert S. Cross Chairman Enclosure HONS 043741 t National industrial Pollution Control Counoil W*tnrtgton. D C BOB30 June U. 1971 Dear Chairmen Crosst An Chairman of the Beetrie and Huclear Sub-Coisicil of the National Industrial Pollution Control Council, 1 iiava Uie honor of sutmlttlng to you this report on our Industry's efforts to evaluate the pollution problem caused by the discarding of old household appliances. Sincerely, Ehdoaure HONS 0437*2 SUMMARY Electrical insulating liquids (Ell), their application and disposal are studied against a background of similar information relating to pe troleum products in total. Naphthenic mineral oils are found to comprise over 80 percent by volume of the total usage of EIL. Polybutenes are second, at almost 10 percent Thus, 90 percent of EIL are pelroleum-based. Being rela tively non-toxic and biodegradable, they represent no environmental threat when subjected to conventional secondary waste treatment. Furthermore, assistance in reclaiming or proper disposal of used mineral oils can usually be obtained from the suppliers of these products. The third largest-volume Ell group is the askarels, or polycblorobiphcnyls. This group has some toxic properties and contains mem bers which have recently become suspect ecologically. Accordingly, the report contains recommendations regarding the control and dis position of askarels. 6 HONS 043743 INTRODUCTION This study of the use and disposal of electrical insulating liquids has been undertaken in support of the objectives of the Electric and Nuclear Sub-Council of the National Industrial Pollution Control Council. Its purpose is to examine electrical insulating liquids (EIL) for their possible toxicological or ecological impact and, as appro priate, to provide information which may lead to advice concerning government programs which would facilitate private sector efforts directed at environmental improvement, or voluntary actions by in dustry. Specific areas of interest include pollution which may occur from the plants where EIL are used in manufacture of electrical ap paratus, and that which may occur during use or disposal. A variety of insulating liquids is used in electrical apparatus such as transformers, circuit breakers, capacitors, and high-voltage cable in order to optimize, for each application, a range of design parame ters typified by dielectric strength, losses, dissipation factor, arc and flame suppression, heat transfer coefficient, and product life expec tancy. Requirements and conditions to be met will, in a given in stance, quickly narrow the practical options available to the designer down to a very few or even to a single fluid. For this reason it should '] be borne in mind that, even though a particular electrical insulating I liquid may be characterized as containing the potential of conlributing to the pollution of the environment, the socially-desirable and / economically correct action may lie in the adoption of precautions and control measures rather than in the substitution of a material which would not perform the required function as well. 7 MONS 043744 CLASSIFICATION OF ELECTRICAL INSULATING LIQUIDS (EIL) While Ihere are a great many types of electrical insulating liquids used for special purposes, such as scientific apparatus, there are only a few used in such quantity as to be of economic importance to the electrical industry and relevant to the subject of national pollution control. The specifications and general characteristics of the princi pal electrical insulating liquids (hereinafter referred to as EIL) are shown in Table No. 1. TABLE NO. 1: EIL CLASSIFICATION Application Combustible Transformers, Oil Circuit Breakers Capacitors, Cable Capacitors, Cable Cable, low Pressure Cable, High Pressure Specification ASTM 01040-69 HD W-l-530a (Note 1.3) ASTM D2297-68 ASTM D2296-6B ASTM D1818-63 ASTM D1819-66 Type of Material Naphthenic mineral oil Naphthenic mineral oil Polybutene oil Naphthenic mineral oil Naphthenic mineral oil Noncombuslible Capacitors Transformers, Capacitors ASTM 02233-68 (Note 2) ASTM D2283-70a (Note 1.1,1.2, 2.0) FED W-l-1219 (Note 1.1,1.2, 2.0) Polychlorinated biphenyl Polychlorinated biphenyl mixtures with diluents NOlt 1.0 Certain (trades contain smalt Quantities of additives which serve as antioxi dants and/or scavengers for hydrogen chtoride. Commonly used materials and typical concentrations are: 1.1 dicyclo-dlepoxy carboxylate 1.2 phenoxypropene oxide 1.3 2,6 diterliary butyl p-crcsol 014% 0 22% 015% 2.0 Cettain grades contain tticMotobeniene and/or tettacWoiobenzrne as dilu ents. HONS 043745 QUANTITIES AND USAGE OF EIL Six of the nine specifications listed in Table No. 1 are petroleum oils. Table No. 2 provides a breakdown of the principal uses of naphthenic mineral oils as insulating liquids. The information on transformer and cable usage is derived from the market estimates of several oil producers (10).* Switchgear (circuit breaker) and capaci tor data are estimated from knowledge of one manufacturer's usage and assumed market position (10). The second column of data in Table No. 2, field use, may be taken as a measure of the generation of waste oil during the use of the apparatus. The gallonage shown represents direct shipment of oil to users of electrical apparatus, as distinguished from manufacturers. Make-up oil is seen to be about 17 percent of the total usage of naphthenic EIL. The waste percentage varies with the class of appa ratus, being zero in the case of capacitors and highest in the case of cable. TABLE NO. 2: USE OF NAPHTHENIC OIL AS AN INSULATING LIQUID IN U.S., 1968 Apparatus Original Equipment field Use Use (Make-up) Transformers Switchgear Cable Capacitors 39.13 2.07 1.05 .02 Total 42.27 * 1,21 million 42-gal- barrels. 7.57 .40 52 0 8.49 Millions of Gallons Total Percent of Total 46.70 2.47 1.57 .02 50.76*' 92.0 4.9 3.1 TOO Table No. 3 is similarly derived and presents an analysis of the total quantity of EIL according to the apparatus in which it is used The grand total of EIL used In the year 1968 is estimated to be 62 million gallons (or 1.5 million 42-gal. barrels). The subtotal consist ing of the first two entries, naphthenic oil and polybutene liquid, is 57.26 million gallons (1.4 million barrels); thus 91 percent of the Humbert In parentheses are references to the Bibliography at the end of the report 9 u HONS 043746 total annual usage of Ell is petroleum based. The remainder is mostly askarels (polychlorinated biphenyls, abbreviated PCB). The chlorinated benzenes shown are not used alone,'but as diluents for the askarels, in some applications. The category, Other, includes relatively small quantities of such materials as dibutyl scbacale and silicone oil, used in specialized apparatus of low pro duction quantities. TABLE NO. 3: QUANTITIES AND USES OF PRINCIPAL INSULATING LIQUIDS IN THE U.S., 1968 Millions of Gallons liquid Trans- Switch- Capacl- Cable Other Total formers geat tors Liquid, % of Total Naphthenic Mineral Oil Polybutene Liquid Askarels (PCB) Chlorinated Benzenes Castor Oil Other Total Use, Percent of Total 46.70 2.47 .02 1.57 .30 51.06 82.4 6.20 6.20 10.0 1.35 2.46 3.81 6.1 .79 .01 .80 1.3 .10 .10 .2 .01 .02 03 48.84 2.47 2.60 7.77 .32 62.00* 100.0 78.8 4.0 4.2 12.5 .5 100.0 * 1.4ft million 42-gal. barrels. 10 HONS 0437*7 TOXICOLOGY MINERAL OILS Naphthenic oils and polybutenes are essentially non-toxic. The only reported danger is from inhalation of vapor or mist*, in which the maximum allowable concentration is 5 parts per million. TOXICITY AND SAFE HANDLING OF ASKARELS (13) Inhalation At ordinary temperatures the askarels have not presented indus trial toxicological problems. The hazard of potential toxic exposure varies with their volatility: the lower-chlorinated, more-volatile ones present more of a potential problem from the standpoint of both in halation and skin contact. When askarels are used at elevated tem peratures, engineering controls must be applied, either by the use of closed systems or by effective local-exhaust ventilation together with general workroom exhaust. Vapor at room temperature should not be breathed in a confined space, and no vapor of any askarel evolved at elevated temperatures should be allowed to be dispersed into the general workroom. Inhalation tests on animals indicate that the maximum safe con centration of vapor is in the range of from 0.5 to 1.0 milligram of the lower-chlorinated askarels per cubic meter of air. The threshold limit values (maximum allowable concentration for an 8-hour work ing day) set by the American Conference of Government Hygienists are 1.0 milligram of the lower chlorinated askarels per cubic meter of air and 0.5 milligram of the more highly chlorinated compounds per cubic meter of air. Skin Contact Schwartz patch tests on 200 volunteers showed that 54 percent chlorinated askarel was neither a primary skin irritant or a sensitizer. 11 MONS 043748 Prolonged or repeated skin contact with askarels must be avoided by the use of gloves and protective garments, because of the pos sible occurrence of a condition called chlojgcne. Although reports of this condition paused by askarels are rare, it can be produced by excessive skin contact. If any askarel is spilled on the skin, the skin should be washed in the usual manner with a soap solution. A burn caused by contact with a hot askarel should be treated like any ordinary burn. Material adhering to the burned area need not be removed immediately, unless treatment of the burn demands it, in which case either soap and water or repeated washings with a vegetable oil are recommended. ECOLOGY Mineral Oils Mr. Claude E. ZoBell has written, "Mineral oils are susceptible to microbial oxidation, and certain fractions undergo autoxidation. This seems to be Nature's way of remedying oil pollution in soil as well as in sea water. ... In controlled laboratory experiments, we find that oil-oxidizing bacteria convert an average of 30-40 percent of the carbon content of hydrocarbons into bacterial cell substance or protoplasm." (14) Mineral oils and polybutenes are not known to have a long-time effect upon the ecology. In the short term, the effect of large scale spills has received considerable notice in the public press. Small amounts, in isolation, have no detrimental effects. The materials are biodegradable and exist naturally in the environment. Thus, con sideration of possible adverse ecological effects arising from the use of mineral oil in electrical apparatus becomes primarily a matter of scale, rather than properties of the oil. Also there are several well known methods of reclaiming and/or otherwise disposing of these oils satisfactorily. Assistance in this regard can usually be obtained from the supplier of the mineral insulating oil. 12 MONS 043749 Askarels The askarels, particularly those with more than 50 percent chlo rination, have recently been identified as a possible ecological threat to marine and bird lije. The attention of the industry was called to ill is- subject' In a number of published articles and specifically in a widely-distributed letter from the Monsanto Company (sole U.S. producer) under the date of February 18, 1970. (1l) Certain askarels introduced into eco-systems are believed to act in a manner some what analagous to the persistent pesticides, being concentrated in successive links of the food chain. f.9UllG-5]lQ.fl. term, effects of askarels may be kept from the envi ronment by limiting applications to closed systems (of which trans formers and capacitors arc examples) and by the exercise of suitable precautions in the disposition of waste. For the longej term, the producer is working to develop modified chlorinated biphenyls which will be biodegradable. This means that even if minute quantities are released to the environment by acci dental spills the consequences will be minimal, and it will be possi ble to remove the modified materials from waste water streams in conventional secondary treatment facilities. (12) MINERAL INSULATING OIL IN PERSPECTIVE As indicated above, mineral oil is characterized as harmless to the environment if the amount released is not excessively concentrated in time or space. The dala in the Appendix were assembled to place this matter in perspective. For example, it is found that the total use of mineral oil in electrical apparatus is about 0.03 percent of all oils (Tabic A-1); that total field make-up is approximately 0.005 percent of all oils. Perhaps a more realistic comparison is the one drawn in the Appendix, i.e., that total usage as insulating oil is equal to a small fraction--10 percent--of the amount of used lubricating oil now being applied directly to land and stream. These comparisons do not lessen the need for prudent disposal of mineral insulating oil HONS 043750 it in accordance with accepted industry practice, but they do suggest a low action priority in the context of a national assessment of pollu tion problems in the electrical industry. tt is concluded that any recommendation at this time for industry action on mineral oils would serve only to dilute the force of rec ommendations to be made in an area where greater leverage exists: the containment of askarels. RECOMMENDATIONS In view of the suspected ecological hazard piesenled by state-ofthe-art formulations of polychlorinated biphenyls, it is recom mended that the electrical industry employ the following guidelines in the manufacture and servicing of electrical apparatus: 1. Provision is to be made for qualified destruction of PCB waste materials, such that there will be no release of materials to the atmosphere or to ground or surface water significant from the standpoint of toxicity or adverse ecological impact. Initially, the only process which appears to meet these lequirements is incineration under carefully controlled conditions. With proper adjustment of temperature, residence time in the incinerator, and other parameters, products of combustion will be limited to-HCI' COj, and hh-O (in the form of steam). The hydrochloric acid may be absorbed in a scrubber and the resultant solution neutralized with lime to form calcium chloride solution, CaCI*. In the process described, the only effluents to the environment will be a plume of steam, carbon dioxide, and brine, the dis charge of which must be held to regulatory limits. 2. All liquid waste is to be held in impervious containers pending disposal. 3. Solid wastes contaminated by PCB's are to be held in impervi ous containers pending disposal or purging. Purging may be accomplished by cleaning with proper fluids. The resulting contaminated liquids may be incinerated as above. 14 HONS 043751 As the result of programs undertaken since the industry was first alerted to indications of ecological harm from PCB's, the industry has progressed a long way toward the implementation of these rec ommendations. At least two enterprises are accepting liquid wastes for incineration; facilities are being prepared for the processing of contaminated solids; evaluations of improved formulations are in progress; and a committee of the American National Standards In stitute has been authorized to consider what standards may be appropriate. 15 HONS 043752 APPENDIX TOTAL FLOW OF PETROLEUM PRODUCTS Because a high percentage of the total volume of electrical insu lating liquids is petroleum based, the use and disposition of Ell can best be understood againsl a background of the quantities of petro leum products used throughout the economy, and how they are disposed of. Table No. A-1 displays the quantities and uses of petroleum prod ucts in the U.S. for 1968 (the most recent year for which relatively complete data could be searched out). This Table is useful in pro viding a perspective for the viewing of the consumption of electri cal insulating oils. Item 3.12, Electrical Insulating Oil, is the total of naphthenic and polybulene Ell, and corresponds to only 0.04 per cent of "all oils." Disposal of Oils Similar lo Electrical Insulating Oils Lubricating oil (Item 3.7 of Table A-1) was chosen for a compara tive study because of its similarity to electrical insulating grades of petroleum oil. Although no national study has been made, data are available (3) fiom which a reasonable estimate can be formed of what happens to lubricants throughout their life history, on a nation-wide scale, Lubricants may be classified conveniently in two groups: automo tive and industrial. Tabic No. A-2 is an estimate of the usage, waste generation, and disposition of automotive lubricants throughout the country, and Table No. A-3 presents similar data for industrial lubri cating oils. A large portion of the waste generated is collected by scavenging firms, and the fate of this portion is indicated in Table No. A-4. Table No. A-5 summarizes the results of the investigation of lubricating oil waste practices. It will be noted that a little over half of all lubricating oil ends as waste, and of this half, more than half Is dumped on the ground in one way or another--as locally disposed waste, as road oil, in town dumps, etc. 1(> HONS 043753 The concern of (he petroleum industry for this situation, and the vigorous steps being taken to evaluate its effect and to devise ameliorative procedures, where indicated, is the subject of another study. See final Report of (he Task Fotcv on Used Oil Disposal, American Petroleum Institute (9). For the purpose of the present study, it may be pertinent to note that the total usage of petroleum-derived insulating oils (1.4 million barrels) is equal to one-tenth of that portion of waste lubricating oil being dumped on the ground or sewered, according to available estimates of current practices. 17 U MONS 043754 TABLE NO. A-1 QUANTITIES AND USES OF PETROLEUM PRODUCTS IN THE U.S., 1968 Use Category Millions of 42-gallon Barrels Kora- Distil- Rcsidsene laic ual Gaso line Jet Fuel Other Total Per cent 1.0 Healing and Energy Convorsion 1.1 Electric Utilities 1.2 Heating 1.3 Industrial 1.4 Oil Companies 1.5 Off H'w'y Diesel 1.6 Mili. fexcl. jet) 1.7 Fuel for all other 3 0 185 0 76.2 512.0 173.0 458 135.7 9.4 39.3 49.5 12.6 35.0 26.7 126 8.3 188.0 761.2 181,5 48.7 49.5 47,6 47.6 Total 102.9 644.9 576.3 0 0 0 1324.1 27.0 2.0 Transportation 2.1 Railroads 2.2 Highway Diesels 2.3 Motor Vehicles 2.4 Piston Aircraft 2.5 let Aircraft 2.6 Ships bunk'd in U.S. 84.1 127.3 4.3 1925.4 30.6 349.4 18.2 87.6 88.4 127.3 1925.4 30.6 349.4 105 8 Total 0 229.6 91.9 19560 349.4 0 2626.9 53.6 3.0 Material Conversion and Other 3.1 Liquified Cases 3.2 Still Gas 3.3 Asphalt 3.4 Pctrochcm. feedstocks 3.5 Coke 3.6 Ethane, Ethylene 37 Lubricants 3.8 Spcc'l Naphthas 3.9 Not Elsewhere listed 3.10 Road Oil 3.11 Wax 3.12 EIcc. Ins. Oil 330.6 330.6 149.8 149.8 141,2 141.2 92.9 92.9 76.3 76.3 55.2 55.2 48.5 48.5 27.0 27,0 16.4 16.4 7.1 7.1 4.4 4.4 1.4 1.4 Total 4.0 Crandlotal 00 0 0 0 950.8 950.8 19.4 102.9 874.5 668 2 19560 349.4 9508 4901 8 100.0 The basic reference for the fuel oils is (4.2) (see BIBLIOGRAPHY); tor gasoline and jet fuel lo blend of gasoline, kerosene, and distillate), (f.); "Other." (0). (4 4) and (10). Some figures from other sources have been adjusted lo yield totals in 'final summary," refer ence (4.4). 18 HONS 043755 TABLE NO. A-2 LUBRICATING OIL--AUTOMOTIVE ESTIMATE OF USAGE, WASTE GENERATION, AND DISPOSITION IN THE USA (Following the pattern observed in the Commonwealth of Massachusetts) User Service Stations Performing Oil Changes Other Svc. Sta. Car Dealers, Garages Fleet Operators Do-it-yourself Oil Changers Agriculture & Marine Users Total (1) User Distri bution, % 54.9 1.6 16.1 18.8 5.4 3.2 100.0 1968 `2) Ca'c. U.S. Usage at % in (I). Million Callons (3) % End ing as Waste 658 63 19 0 194 90 226 63 65 63 38 50 1200 - (4) Waste, Million Gallons (5) % of (4) Col lected (6) Waste col lected. Mil. Gal. 415 87.7 364 00 0 175 88.0 154 142 60.0 86 40 0 0 19 0 0 791 - 604 (7) Waste uncol lected. Mil. Cal. (9) Dumped on Ground Mi'. Gal. !9) Sewered, Mil. Cal. 51 45 00 21 20 56 52 40 37 19 18 187 172 6 0 1 4 3 1 15 The iota1 U.S. usage. 1200 million gallons i28 6 million barrels) is deiived Irom a 1967 survey bv the Bureau of the Census--see Sources of information, reference <>). The total wj adjusted to 1968 usage bv means of information in reference (*.** Percentage distributions and disposal patterns are drawn from a survey made bv the Arthur 0. little Company in the Commonwealth of Massachusetts, reference <3'. Applying the Massa chusetts pattern to the USA as a whole involves errors of unknown magnitude: a staff estimate bv the CWQA yields a figure of 350 for the first entry m column <4) above (reference an estimate IS." percent below that derives) here. The American Petroleum Institute (reference 9* terms the AOl s'udv indicative of present disposal practices." MONS 043756 TABLE NO. A-3 LUBRICATING OIL--INDUSTRIAL ESTIMATE OF USAGE, WASTE GENERATION, AND DISPOSITION IN THE USA (Following (he pattern observed in the Commonwealth of Massachusetts) 1968 (Millions o* Gallors) Use Cateeorv Lubricating Oil (i) Distri bution % 51.0 '21 Calc. U.S. Usage 426 Oi % Waste 35 (4) Vol of Waste 149 (5) % Collect. ib) Vol Coll. m 18) Vol. Un- % coll'ct'd Burned t9) Vol. Burned not % Volume Sewered Sewered Hydraulic Fluid 27.4 229 20 46 Straight Cutting Oil 10.5 88 30 26 Soluble Cutting Oil Total 11.1 93 30 28 100 28 100.0 836` 249 76 189 60 1.2 3 28 Data in columns 1), O). (5*. elc. are from the A..O. Little report, B-bbographv Reference 13). * Bureau of Mines total lubricants, less automotive use from Table N'o. A-2. HONS 04375? TABLE NO. FATE OF COLLECTED WASTE OIL l Miniate of U.S. Disposal Practices Based on MassacImsctls Pattern 1908 Miliums of Gallons (m.il Disposition Automotive Percent ' Volume Industrial IVnrnl ` Volume 1ni.il Volume Collide! Waslr lul.e Reproc rssed to fuel Oil oi Re refined Used as Road Oil Used cm 1 arms Disposed of Locally down Dumps or local Roads) Unknown (>9.1 217 4.6 4.6 417 131 2B 28 52.6 100 - - 47.4 89 - - Total Collec ted 1(X) 604 ' 100 189 1 Mudy of W.isfe ( >ll Dispos.d f . rices in M.tss.u fur eifs. tiff. it). l' l.ilile No A-2 * l.ilile No. A-V 417 2.11 20 89 28 79.1 TABLE NO. A-5 FATE OF WASTE LUBRICATING Oil U.S., 1968 Summary of Estimates in Collected and Uncollected Catepones Ultimate 1 ate Dumped or Applied on Ground Poured into Srwcrs Reprocessed. Rc-relioed, and/or Burned Unknown Total Lndinji as Waste' lol.il Used, as Memo Item Volume, Millions ol Gallons 549 4.5 420 28 1040 20.16 Volume, Mdl.ons of A J-Hal. It.inek DiUiilnHron. I'e. i enl ol 1ol.il Inhiic.ilii Oi! Used 13.1 27 1.0 2 100 21 0.7 1 24.0 51 40.5 100 MQNS 043758 21 BIBLIOGRAPHY 1. Environmental Quality, 7 he first Annual Report of the Council on Invirunmental Quality, U.S Cov'i. Printing Office, August, 1970. 2. Clean Water lor the 7970'*, A Status Report, June, 1970, U S. Dept. ot llie Interior, Federal Water Quality Administration, U S. Gov't. Print ing Office. 3. Study oI Waste Oil Disposal Practices in Massachusetts, Report to Commonwealth of Massachusetts, Division of Water Pollution Con trol, January, 1969, C-70698, by Arthur D little, tnc. 4,0 Mineral Industry Surveys, U.S Department of the Interior, Bureau ol Mines, Washington, D.C. 20240. 4.7 Idem, Petroleum Statement, Monthly, March 18, 1969 (Preliminary). 4.2 Idem, Fuel Oil Shipments, Annual, Sept. 17,1969. 4.3 Idem, liquified Petroleum Gas Shipments, Annual, Oct. 13, 1%9. 4.4 Idem, Petroleum Statement, Annual, Dec. 16, 1969 (1908 final Sum mary). 4.5 Idem, Petroleum Statement, Monthly, March 24, 1970. 4.6 Idem, Asphalt Shipments, Annual, June 11, 1970. 4.7 Idem, liquified Petroleum Cas Sales, Annual, September 30,1970. 5. Statistical Abstract oi the United States, 1969, Table 758. 6. U.S. Department of Commerce, 7969 Business Statistics, pp. 167, 168, 169. 7. Sales of lubricating a/rd Industrial Oils and Creases, IV67, Nov. 21, 1968, 5cries MA-29C(67)-1, U.S. Department of Commerce, Bureau of the Census, Industry Division, Washington, D C. 20233. 8. Cleaning out environment' The Chemical Basis for Action toooW). American Chemical Society, Washington, D C. 1969. 9. final Report ol the Task Force on Used Oil Disposal, American Petro leum Institute, 1271 Avenue of the Americas, New York, N.Y. 1002Q. 10. General Electric Company, unpublished studies. 11. letter to Electrical Industry from Monsanto Chemical Company, Feb ruary 10, 1970. 12. Congressional Record--House H10214, October 14, 1970. 13. Monsanto Company, St. Louis, Missouri. 14. 7he Occurrence, Effects, and fate of Oil Polluting the Sea, tnt. } Wat. Poll. Pergamon Press 1963, Vol. 7, pp. 173-198. Piintod in Great Britain. 22 HONS 093759 ELECTRIC AND NUCLEAR SUB-COUNCIL NATIONAL INDUSTRIAL POLLUTION CONTROL COUNCIL ctuirmin: D. C. Burnham Chairman Wcstinghousc Electric Corporation Vice Chairman; Fred J. Borch Chairman and Chief (xcrutivp Officer General Electric Company A. P. Fontaine President & Chairman the Bertdix Corporation Raymond H. Ciesecke President & Chief Exec. Officer McGraw-Edison Company Members C. Lester Hogan President & Chief Executive Officer Fairchild Camera & Instrument Corporation Robert W. Sarnoff Chairman of the Board & President RCA Corporation HONS 043760